Plan Review Details - Permit 03101794
Plan Review Stops For Permit 03101794
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2005-04-07 Cont ID  
Sent By jgomez Date 2005-04-07 Time 10:48 Rev Time 0.25
Received By jgomez Date 2005-04-07 Time 10:48 Sent To  
Notes
2005-04-07 00:00:00SLIDING GLASS DOOR PRODUCT APPROVAL
 CHECKLIST:
  
 1- PRODUCT APPROVAL RE-SUBMITTED ON
 FRIDAY 4-1-05. REVIEWED ON MONDAY 4-4-05
 AND FOUND OUT THAT ENGINEER LETTERS AND
 8.5" X 11" DRAWINGS WERE NOT SIGNED AND
 SEALED AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
 BILL STAPLES CALLED ENGINEER. SIGNED AND
 SEALED LETTERS WERE RE-SUBMITTED ON
 TUESDAY 4-5-06 BUT 8.5" X 11" DRAWINGS
 WERE NOT.
 NEED THOSE DRAWINGS TO BE SIGNED AND
 SEALED BY ENGINEER.
  
 2- OTHER CHECKLIST ITEMS ADDRESSED ON
 3-8-05 ARE STILL NOT RESOLVED. SEE
 ATTACHED COPY.
  
 IF YOU HAVE ANY QUESTIONS. PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2005-03-08 Cont ID  
Sent By jgomez Date 2005-03-08 Time 14:41 Rev Time 1.00
Received By jgomez Date 2005-03-08 Time 14:36 Sent To PC
Notes
2005-03-08 00:00:00CHECKLIST:
 1- SLIDING GLASS DOOR PRODUCT APPROVAL
 COMMENTS FROM BILL STAPLES:
 A) PROVIDE 2 COPIES OF F.B.C COVER SHEET
 FILLED OUT.
  
 B) IF DOORS ARE GOING TO BE INSTALLED IN
 2 DIFFERENT LOCATIONS, THEN, APPLY FOR
 LOCAL PRODUCT APPROVAL OR APPLY FOR SITE
 SPECIFIC PRODUCT APPROVAL FOR EACH
 HOUSE.
  
 C) WHO IS THE EVALUATION ENTITYIF
 APLYING FOR LOCAL PRODUCT APPROVAL.
 D) EVERY CHANGE DONE TO SIGN AND SEAL
 DRAWINGS MUST BE INITILALIZED AND DATE
 BY THE ENGINEER OF RECORD.
  
 E) INSPECTION FOR CODE COMPLIANCE IS
 REQUIRED BY THE ENGINEER OF RECORD AFTER
 ASSEMBLY IS INSTALLED.
  
 2- REVISION COMMENTS:
 A) PROVIDE COMPLETE UL LISTING AND SPECS
 FOR INTERIOR FIREPLACE. SEC. 2806 FBC.
 B) PROVIDE COMPLETE LISTING AND SPECS
 FOR BBQ GRILL. SEC. 2808 FBC 2001.
 ****NOTE: MAKE SURE THAT MANUFACTURER
 SPECS ALLOW INSTALLATION OF GRILL IN THE
 PORCH SINCE THEY ARE DESIGN TO BE
 INSTALLED OUTDOORS.
  
 B) MASTER BATHROOM WINDOWS BY THE
 WHIRPOOL NEED TO BE SPECIFIED AS SAFETY
 GLASSS. SEC. 2405.2 FBC 2001.
  
 C) ATTIC SPACE WAS ORIGINALLY DESIGNED
 FOR ATTIC STORAGE WITH 30PSF LIVE LOAD.
 ATTIC WAS REVISED FOR NON-STORAGE. BUT
 NEEDS TO BE DESIGNED FOR 10PSF ATTIC
 LIVE LOAD AS REQUIRED BY TABLE 1604.1
 FBC 2001. NOW, THE PROBLEM IS THAT ROOF
 TRUSSES WERE DESIGNED FOR 0 PSF ATTIC
 LIVE LOAD. TRUSSES NEED TO COMPLY WITH
 TABLE 1604.1 FBC 2001.
  
 D) BREAKFAST AREA WINDOW IS TO BE USED
 FOR EMERGENCY EGRESS. STORM SHUTTERS
 INSTALLATION SCHEDULE SHOWS WINDOW TO BE
 SHUTTERED. PROVIDE CERTIFICATION THAT
 THIS WINDOW WAS INSTALLED WITH MISSILE
 IMPACT GLAZING IN ORDER TO COMPLY WITH
 SEC. 1005.4.5 FBC 2001.
  
 E) OWES $80.00 REVISION FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2005-01-14 Cont ID  
Sent By jgomez Date 2005-01-14 Time 14:16 Rev Time 0.50
Received By jgomez Date 2005-01-14 Time 14:16 Sent To  
Notes
2005-01-14 00:00:00CHECKLIST:
 1-PRODUCT APPROVAL INFORMATION FOR
 SLIDING GLASS DOORS LOCAL PRODUCT
 APPROVAL IS INCOMPLETE. COMPLETE FORM
 REQUIRED BY THE FLORIDA BUILDING
 COMMISSION WHEN APPLYING FOR LOCAL
 PRODUCT APPROVAL AND PROVIDE ALL
 REQUIRED INFORMATION. SEE
 WWW.FLORIDABUILDING.ORG FOR ALL
 INFORMATION REQUIRED TO COMPLY WITH
 CHAPTER 9B-72.
  
 2-DADE COUNTY NOA IS VOIDED IF SYSTEM
 IS
 ALTERED. INFORMATION SUBMITTED IS
 DIFFERENT THAT ONE SUBMITTED FOR DADE
 COUNTY PRODUCT APPROVAL.
  
 3-NEED TO VERIFY EMERGENCY EGRESS WHEN
 STORM SHUTTERS ARE INSTALLED.PLANS
 CALL FOR IMPACT GLASS WINDOW AT
 BREAKFAST AREA TO COMPLY WITH THE
 EGRESS
 REQUIREMENT. BUT, ON THE OTHER HAND,
 STORM SHUTTERS INSTALLATION SCHEDULE
 SHOW ALL OPENINGS TO BE PROTECTED WITH
 SHUTTERS INCLUDING THE EGRESS OPENING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2005-01-10 Cont ID  
Sent By jgomez Date 2005-01-10 Time 13:10 Rev Time 0.50
Received By jgomez Date 2005-01-10 Time 13:10 Sent To PC
Notes
2005-01-10 00:00:00REVISION CHECKLIST:
  
 1-SHEET A4 AND SHEET A5 SPECIFICATIONS
 FOR ATTIC LIVE LOAD DO NOT MATCH.
 BESIDES AREAS TO HAVE STORAGE ARE
 REQUIRED TO BE DESIGNED FOR 30PSF LIVE
 LOAD AS REQUIRED BY TABLE 1604.1 FBC
 2001.
  
 2-TRUSS ENGINEER DID NOT FOLLOW
 ARCHITECT'S SPECIFICATIONS REQUIRING
 30PSF ATTIC LIVE LOAD DESIGN ON AREAS
 DESIGNATED TO BE FOR STORAGE.
  
 3-FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 SLIDING GLASS DOORS HAS NOT BEING
 RESUBMITTED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-01-04 Cont ID  
Sent By jgomez Date 2005-01-04 Time 10:49 Rev Time 0.50
Received By jgomez Date 2005-01-04 Time 10:49 Sent To PC
Notes
2005-01-04 00:00:00CHECKLIST:
 1-DADE COUNTY NOA #02-1206.01 FILE FOR
 SLIDING GLASS DOOR IS SUSPENDED.
 THEREFORE NOA IS NOT ACCEPTABLE. NEED
 CURRENT NOA.
  
 2-DRAWING #3070HI-900X-XO-1DG IS NOT
 PART OF THE DADE COUNTY NOA PACKAGE.
 THEREFORE IS NOT ACCEPTABLE TO BE PART
 OF THE SAME PRODUCT APPROVAL PACKAGE.
  
 3-LETTER BY W.W. SCHAEFER ENGINEERING TO
 MODIFY NOA PRODUCT APPROVAL PACKAGE IS
 NOT ACCEPTABLE. SEE NOA TERMINATION
 NOTE.
  
 4-PROVIDE CURRENT FLORIDA PRODUCT
 APPROVAL OR APPLY FOR LOCAL PRODUCT
 APPROVAL PROVIDING ALL INFORMATION
 REQUIRED ON APPLICATION FOR LOCAL
 PRODUCT APPROVAL. SEE FORM NO
 9B-72.130(4) FROM RULE CHAPTER 9B-72.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-01-04 Cont ID  
Sent By jgomez Date 2004-12-27 Time 11:12 Rev Time 0.00
Received By jgomez Date 2004-12-27 Time 16:02 Sent To PC
Notes
2004-12-27 00:00:00CHECKLIST:
 1-COMPLETE FLORIDA OR LOCAL PRODUCT
 APPROVALREQUESTED ON PROVISO DATED
 2-3-04 FOR SLIDING GLASS DOORS AS SHOWN
 ON PLANS WAS NEVER SUBMITTED. SUBMIT IT
 FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-12-06 Cont ID  
Sent By jgomez Date 2004-12-06 Time 14:23 Rev Time 1.00
Received By jgomez Date 2004-12-06 Time 14:23 Sent To PC
Notes
2004-12-06 00:00:00BUILDING SUBMITTAL CHECKLIST:
 1-ITEMS #3 AND 4 A) WERE NEVER SUBMITTED
 FOR REVIEW. SEE ATTACHED COPY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-07-15 Cont ID  
Sent By jgomez Date 2004-07-15 Time 14:27 Rev Time 0.75
Received By jgomez Date 2004-07-15 Time 14:27 Sent To PC
Notes
2004-07-15 00:00:00REVISION CHECKLIST:
 1-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR ENTRY DOORS WITH
 TRANSOM ABOVE SINGLE ASSEMBLY AS SHOWN
 ON PLANS.
 2-PROVIDE COMPLETE UL LISTING AND SPECS
 FOR OUTDOOR FIREPLACE AND ANOTHER FOR
 THE INDOOR FIREPLACE AS REQUIRED BY
 SECTION 2806 FBC 2001.
 ARCHITECT OF RECORD TO REVIEW THEM
 PRIOR TO SUBMITTAL TO THIS OFFICE.
 3-LEFT SIDE EXTERIOR ELEVATION DOESN'T
 SHOW REVISED WINDOW FOR DINING ROOM.
 REVISE AS REQUIRED.
 4-PROVIDE COMPLETE DETAIL/SPECS FOR
 INSTALLATION OF ARCHED WINDOW ABOVE
 AND SPECIFY IF THERE IS A LINTEL BET.
 BOTTOM AND TOP ROUNDED WINDOW. FRAMING
 PLANS DON'T CALL FOR ANY LINTEL. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-PROVIDE ALL INFORMATION REQUESTED ON
 PROVISO DATED 2-3-04. SEE ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-05-25 Cont ID  
Sent By jgomez Date 2004-05-25 Time 15:27 Rev Time 0.50
Received By jgomez Date 2004-05-25 Time 15:27 Sent To PC
Notes
2004-05-25 00:00:00BUILDING SUBMITTAL CHECKLIST:
  
 **NOTE:
 PROVIDE 2 COPIES OF ANY SUBMITTAL AND
 PLEASE, BRING INFORMATION IN PERSON
 TO FILL OUT PROPER SUBMITTAL FORM AND
 ALLOW TO TRACK SUBMITTALS.
  
 1-FIREPLACE PACKAGE: A)PROVIDE SPECIFIC
 UL LISTING NUMBER AND MODEL TO VERIFY
 WITH LATEST UL LISTING.
 B)ARCHITECT TO REVIEW FIREPLACE PACKAGE.
 CHECK REQUIRED CLEARANCES & LOCATION
 MEET HIS DESIGN.
 C)REVISE PLANS/ELEVATIONS TO INCLUDE
 CHIMNEY.
  
 2-ENGINEER CALCS: A)ENGINEER NEEDS TO
 PROVIDE ALL HIS INFORMATION AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING INFO. FOR PUBLIC RECORDS.
 ENGINEER TO REVIEW CHAPTER 61G15-23
 OF THE FLORIDA ADMINISTRATIVE CODE
 FOR SEALS & ENGINEER RESPONSIBILITIES
 3-PROVIDE ALL INFORMATION AS REQUESTED
 ON PROVISO DATED 2/3/04 PRIOR TO
 INSTALLATION OR CONSTRUCTION TO AVOID
 ANY DELAYS OR CONFLICTS.
 SEE ATTACHED COPY WITH PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-03 Cont ID  
Sent By pkrauss Date 2004-02-06 Time 07:23 Rev Time 2.00
Received By jgomez Date 2004-02-03 Time 18:17 Sent To E
Notes
2004-02-03 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE LEGIBLE DRAWINGS FOR OUTDOORS
 FIREPLACE AND IDENTIFY UL # LISTED.
 PRIOR TO INSTALLATION.
 2-PROVIDE COMPLETE/CORRECT INFORMATION
 FOR STORM SHUTTERS UNDER A SEPARATE
 PERMIT.
 3-PROVIDE ORIGINAL ENGINEERING CALCULATI
 ONS FOR TRUSS ANCHOR SCHEDULE MODIFI-
 CATIONS TO TESTED & PUBLISHED ANCHORS
 BY USP TO COMPLY WITH SEC. 1609.4.3
 FBC 2001. SEC. 104.2.1.2 CITY AMEND-
 MENTS TO FBC 2001. ALSO, ENGINEER TO
 PROVIDE ALL HIS INFORMATION & PROJECT
 INFORMATION AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING
 INFORMATION FOR PUBLIC RECORDS.
 4-FLORIDA PRODUCT APPROVAL & DWGS MUST
 MATCH. PROVIDE DRAWINGS THAT MATCH
 SUBMITTED PRODUCT APPROVAL FOR:
 A)SLIDING GLASS DOORS.
 B)ALL STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
 C)CASEMENT WINDOWS.
 D)SINGLE HUNG WINDOWS.
 E)WINDOW MULLIONS.
 F)GARAGE DOORS NEED FLORIDA APPROVAL.
 G)MASONITE INTERNATIONAL ENTRY DOORS.
 H)FRENCH DOORS.
  
 NOTE: PROVIDE AL INFORMATION PRIOR TO
 INSTALLATION TO AVOID DELAYS OR CONFLICT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-08 Cont ID  
Sent By dpalmer Date 2004-01-28 Time 12:12 Rev Time 4.00
Received By jgomez Date 2004-01-07 Time 18:34 Sent To PC
Notes
2004-01-07 00:00:00BUILDING REVIEW CHECKLIST:
 1-MISSING ONE DWG A1 & A2. ONLY ONE COPY
 OF REVISED A1 AND A2 DWG WAS SUBMITTED
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-ARCHITECT TO PROVIDE ALL INFORMATION
 LISTED ON SEC. 1606.1.7 FBC 2001.
 4-WHEN HAVING THE OPTION OF HAVING THE
 FIREPLACE, THEN ALL DETAILS & SPECS
 SHALL BE INCLUDED IN THE CONSTRUCTION
 DOCUMENTS. OTHERWISE, DELETE OPTION.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-LIVING ROOM AREA: PROVIDE COMPLETE
 SECTION/DETAIL AT COLUMN SHOWING HOW
 ARE WINDOWS GOING TO BE ATTACHED.
 **NOTE: CHECK WINDOW PRODUCT APPROVAL
 FOR REQUIRED SUBSTRATE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 6-PLANS NEED TO SPECIFY SAFETY GLASS AT
 LIVING ROOM WINDOWS. SEC. 2405.2 FBC.
 7-PROVIDE FLORIDA PRODUCT APPROVAL FOR
 ENTRY DOOR WITH SIZE AS SHOWN ON PLAN.
 8-ROOF TILE FASTENING SPECIFIED IS NOT
 ADEQUATE. SEE PRODUCT APPROVAL FOR MIN
 REQUIRED SIZES. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 9-RE-SUBMIT FLORIDA PRODUCT APPROVAL FOR
 A)"THERMA-TRU" ENTRY DOORS:*NEED SIZE AS
 SHOWN ON PLANS. **NO GOOD: PENDING FBC
 APPROVAL. ***NEED SWING OF DOOR AS
 SHOWN ON PLANS. ****SLIDING DOOR IS
 MISSING DRAWINGS AND IS PENDING FBC
 APPROVAL. NEED TO CHECK FOR SIZE AND
 SPECIFIC APPLICATION AS SHOWN ON PLANS
 B)GARAGE DOOR PRODUCT APPROVAL IS NOT
 APPROVED YET. IT'S APLIED FOR ONLY.
 C)IF USING FIXED WINDOWS BY "WINDSOR",
 THEN PROVIDE COMPLETE APPROVED DWGS &
 CHECK SIZES SHOWN ON PLANS.
 D)PGT PRODUCT APPROVAL PACKAGE: ONLY
 SUBMIT PRODUCT APPROVAL AND DRAWINGS
 FOR WINDOWS/DOORS, MULLIONS TO BE USED
 ON THIS PROJECT TO AVOID UNNECESSARY
 PAPERWORK.
 **NEED DRAWINGS FOR CASEMENT WINDOWS,
 WINDOW MULLIONS, FIXED WINDOWS (CHECK
 SIZES SHOWN ON PLANS)
  
 10-NEED FL. PRODUCT APPROVAL FOR FRENCH
 DOORS. CHECK SIZE AND SWING.
 11-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR FIREPLACE AND BBQ AS REQ'D BY
 SECTIONS 2806 AND 2808 FBC 2001.
 12-STORM SHUTTERS: A)PROVIDE 2 COPIES
 SIGNED,SEALED AS REQ'D BY ENGINEER.
 B)MEAN ROOF HEIGHT IS INCORRECT.
 C)ACCORDING TO INSTALLATION SCHEDULE
 SOME PANELS WILL ALLOW LESS THAN 2"
 EDGE DISTANCE. REVISE AS REQ'D.
 D)CLEARLY MARK ON ENGINEERED DRAWINGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE & SPACING TO BE USED ACCORDING TO
 THE DESIGN PRESSURES, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND STRUC-
 TURE TO BE ATTACHED TO (CONCRETE BLOCK
 OR CONCRETE).
 E)NEED TO INDICATE EMERGENCY EGRESS AS
 REQ'D BY SECTION 1005.4.5. EGRESS TO
 BE ACCESSIBLE FOR EVERYBODY WITHOUT
 GOING THRU ROOMS THAT MAY BE LOCKED.
  
 13-CONTRACTOR SAID THAT HE WILL PROVIDE
 ADDITIONAL SOIL BORINGS AS REQ'D BY
 SOIL TEST REPORT.
 14-PROVIDE FLORIDA PRODUCT APPROVAL FOR
 TRUSS ANCHORS.
 15-REVISE ENERGY CALCULATIONS: A)UNDER
 ATTIC AREA IS INCORRECT. SEE SECTION
 604.1.A.1 CHAPTER 13 FBC 2001.
 16-REVISE TRUSS ANCHOR SCHEDULE:
 A)AVERAGE ULTIMATE TENSION CANN'T BE
 USED FOR DESIGN PURPOSES. SEE SIMPSON
 CONNECTOR HTT22. ALSO, CLARIFY WHAT
 ARE LATERAL FORCES F1 AND F2 TAKEN
 FROM. SEE CATALOGUE.
 **WHERE ARE LATERAL LOADS F1 & F2 TAKEN
 FROM?. PROVIDE ENGINEERING CALCS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 17-CONTRACTOR TO UPDATE WORKERS COMP.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ @ (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-03 Cont ID  
Sent By pkrauss Date 2004-01-06 Time 06:32 Rev Time 3.50
Received By jgomez Date 2003-12-02 Time 10:49 Sent To PC
Notes
2003-12-02 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-ARCHITECT TO PROVIDE COMPLETE INFO. ON
 PLANS AS REQ'D BY SEC. 1606.1.7 FBC.
 3-CLARIFY IF HAVING THE OPTION OF FIRE-
 PLACE OR NOT. IF SO, THEN PROVIDE
 COMPLETE SECTION/DETAILS AND SPECS FOR
 CHIMNEY AND UL LISTING AND SPECS.
 OTHERWISE REMOVE FIREPLACE AND CHIMNEY
 FROM PLANS ON ORIGINAL DWGS. DON'T
 CROSS OUT ORIGINAL PLANS.
 4-DESIGN CRITERIA TO INCLUDE 30PSF OR
 10PSF ATTIC LIVE LOAD AS REQUIRED BY
 TABLE 1604.1 FBC 2001.
 5-FOOTING DETAILS AND WALL SECTIONS TO
 CLEARLY INDICATE THE 4"MIN. ELEVATION
 ABOVE GRADE AND THE 12" BELOW GRADE
 REQ'D BY SEC. 1804.1.7 CITY AMENDMENTS
 TO FBC AND SEC. 1804.1.3 FBC 2001.
 6-AS OF OCTOBER 1ST 2003 ALL PRODUCT
 APPROVAL FOR DOORS, WINDOWS AND
 STRUCTURAL COMPONENTS NEED TO HAVE THE
 FLORIDA PRODUCT APPROVAL, LOCAL
 PRODUCT APPROVAL OR SITE SPECIFIC. SEE
 CHAPTER 9B-72 DCA. PLEASE GO TO WWW.
 FLORIDABUILDING. ORG FOR MORE INFO.
 7-PROVIDE COMPLETE SECTION/DETAIL AND
 SPECS (TOP & BOTT.) FOR STEEL COLS. AT
 FAMILY RM WINDOW.
 **NOTE: INCLUDE ATTACHMENT OF WINDOW TO
 COL. SEE APPROVED PRODUCT APPROVAL.
 8-SPECIFY ATTIC ACCESS SIZE ON PLANS.
 SEE PLANS AND SEC. 2309.6 FBC 2001.
 9-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS & SEC. 2405.2 FBC 2001.
 10-PROVIDE COMPLETE SPECS FOR AHU DETAIL
 INCLUDE SIZE OF BOLTS AND CHAINS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 11-SPECIFY ROOF TILE FASTENING AS REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS FBC.
 12-PROVIDE COMPLETE DETAILS/SPECS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCHES. SEE ASTM C-926 & ASTM C-1063
 FOR STUCCO AND FASTENER SPECS.
 SEC. 2504.2 FBC 2001.
 13-INFORMATION ON SURVEY ISN'T COMPLETE.
 IS LOT BEING RECORDED?.SEE DESCRIPTION
 14-PROVIDE SOIL TEST REPORT W/ COMPLETE
 INFORMATION, SUCH AS SOIL PREPARATION
 AND SOIL BEARING CAPACITY. INFORMATION
 SUBMITTED ALSO RECOMMENDS ADDITIONAL
 BORINGS TO BE PERFORMED FOR FINAL
 GEOTECHNICAL RECOMMENDATIONS.
 15-STORM SHUTTERS INFO. IS INCOMPLETE.
 NEED FLORIDA PRODUCT APPROVAL. LOCAL
 APPROVAL OR SITE SPECIFIC DRAWINGS.
 ALSO, CLEARLY MARK ON DWGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING. SEC. 104.2.1.2 CITY AMENDMENT
 TO FBC 2001.
 16-ENERGY CALCULATIONS: A)REVISE UNDER
 ATTIC AREA. SEE SEC. 604.1.A.1 CHAPTER
 13 FBC 2001.
 B)CLARIFY HOW ARE INSULATION VALUES
 FOR CONCRETE SLAB, EXTERIOR CONCRETE
 WALL AND UNDER ATTIC GOING TO BE
 ACHIEVED. NOTE: ARCHITECTURAL PLANS &
 ENERGY CALCS NEED TO MATCH.
 17-SPECIFY FOOTING FOR ENTRY COLUMN. SEE
 FOUNDATION PLAN FOR COMMENTS & RETURN
 REVIEWED SET AFTER CORECTIONS ARE DONE
 TO CAD DWGS TO EXPEDITE REVIEW.
 18-SPECIFY MULLION/LINTEL ABOVE WINDOWS
 IN FAMILY ROOM. SEE BLDG SECTION A-A.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 19-SHEET A8: A)UPDATE GENERAL NOTES. SEE
 COMMENTS ON PLAN.
 B)COMPLETE/REVISE TYP. WALL SECTION.
 C)COMPLETE INFO. ON AHU DETAIL.
  
 20-ALL STRUCTURAL CONNECTORS NEED TO
 HAVE FLORIDA PRODUCT APPROVAL AS WELL.
 CHECK WITH USP OR SIMPSON FOR ANCHORS
 THAT HAVE SUCH APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CALL JULIO GOMEZ AT 805-6712.
  
 **PLEASE RETURN REVIEWED SET TO EXPEDITE
 THE REVIEW PROCESS.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-02-24 Cont ID  
Sent By dpalmer Date 2005-02-24 Time 13:15 Rev Time 0.40
Received By dpalmer Date 2005-02-24 Time 13:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-01-07 Cont ID  
Sent By dpalmer Date 2005-01-07 Time 10:18 Rev Time 0.33
Received By dpalmer Date 2005-01-07 Time 09:45 Sent To B
Notes
2005-01-07 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE RISER AND
 PANELS, PANEL "A" SHOWN AS 150A AND
 200A
 ON RISER.
 PLEASE ALSE SEE PLANS INDICATE A MAIN
 DISC ON THE OUTSIDE OF DWELLING, YET
 RISER DOES NOT CONFRIM THIS.?
 215.5
  
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES A WHIRLPOOL TUB, HOWEVER,
 PLANS DO NOT INDICATE ANY GFI FOR THIS
 AT WHAT APPEARS TO BE WP TUB AT MASTER
 BATH LOCATION.
 215.5
  
  
 3)NOTE: PLEASE SEE 210.70 FOR REQUIRED
 LT FOR AHU/ EQUIPMENT IN ATTIC.
  
  
  
 4)NOTE: PLEASE SEE 220.3B4 AN OUTLET
 SUPPLYING RECESSED LUMINAIRE(S)
 [LIGHTING FIXTURE(S)] SHALL BE COMPUTED
 BASED ON THE MAXIMUM VOLT-AMPERE RATING
 OF THE EQUIPMENT AND LAMPS FOR WHICH
 THE
 LUMINAIRE(S) [FIXTURE(S)] IS RATED.
  
 5)NOTE: PLEASE VERIFY OCP FOR 7.5KW
 AHU#3, SHOWN AS 60A. ONLY A NOTE:
  
 PLEASE SEE ONE SET OF PLANS HAVE BEEN
 REDLINED FOR AREAS OF NOTES AND
 LOCATIONS FOR SOME OF THE ITEMS LISTED
 ABOVE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 16:54 Rev Time 0.33
Received By dpalmer Date 2004-11-18 Time 16:54 Sent To  
Notes
2004-11-18 00:00:00************ UNSAT ***************
  
 PLEASE SEE THAT REDLINED ITEMS FROM
 PREVIOUS REVIEWS HAVE NOT BEEN
 ADDRESSED.
 PLEASE ALSO SEE NEW COMMENTS FOR PLAN
 CHANGES.
  
 1)NOTE: PLEASE SEE 250.24,250.6, THERE
 IS NO EQUIPMENT GROUNDING CONDUCTOR
 FROM
 METER TO FIRST MEANS OF DISCONNECT.
  
 2)NOTE: PLEASE SEE PLANS STILL NOTE
 MAINS NEXT TO METER.??
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66.
 ORIG PLANS CALLED FOR SMALLER SERVICE
 AND THIS WAS REDLINED ON PREVIOUS
 REVIEWS. TO BE SIZED PER 250.66
  
 4)NOTE: PLEASE SEE HAND DRAWN ITEMS MAY
 NOT BE DONE ON PLANS WHICH ARE SIGNED
 AND SEALED BY AN ARCH OR ENGINEER.
 FS 481.221
  
 5)NOTE: PLEASE SEE SD PLACEMENT,
 REQUIRES SD OUTSIDE MASTER BEDRM AND
 ALSO OUTSIDE GUEST SUITE.
 NFPA-72 8-1.4.1.6.2
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2004-07-12 Cont ID  
Sent By dpalmer Date 2004-07-12 Time 11:25 Rev Time 0.25
Received By dpalmer Date 2004-07-12 Time 11:25 Sent To  
Notes
2004-07-12 00:00:00NO REV SUBMITTED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-02-04 Cont ID  
Sent By dpalmer Date 2004-02-04 Time 10:21 Rev Time 0.33
Received By dpalmer Date 2004-02-04 Time 10:21 Sent To M
Notes
2004-02-04 00:00:00PLANS REVISED, DID NOT REVISE ORIG
 REDLINES.
 REDLINED PLANS FOR GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66 #2 MIN
 AND MISSING EQUIPMENT GROUNDING CONDUCT-
 ORS BETWEEN MAINS AND PANELS.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2004-01-28 Cont ID  
Sent By jgomez Date 2004-02-03 Time 18:17 Rev Time 0.00
Received By dpalmer Date 2004-01-28 Time 12:12 Sent To B
Notes
2004-01-28 00:00:00NO CHANGES MADE TO PLANS. PASSED WITH
 REDLINES ON PREVIOUS REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-22 Cont ID  
Sent By csiegber Date 2004-01-22 Time 14:04 Rev Time 1.00
Received By dpalmer Date 2003-12-22 Time 13:16 Sent To P
Notes
2003-12-22 00:00:00********** NOTES REDLINED ************
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO PANELS
 PER 250.110, 250.24,250.122
  
 2)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR FROM 250.66./ 310.15B6
  
 3)NOTE: PLEASE SEE 210.52 BEDROOM.
  
 ABOVE HAS BEEN REDLINED. IF REV'S ARE
 DONE, PLEASE MAKE ABOVE CORRECTIONS
 AND SUBMIT W/ REVISIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-12-16 Time 11:27 Rev Time 0.75
Received By dpalmer Date 2003-11-06 Time 16:40 Sent To M
Notes
2003-11-06 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ROOM DESIGNATIONS
 ON PLANS.
  
 2)NOTE: PLEASE SEE 210.52 FOR REQ'D
 RECEPT SPACING.
  
 3)NOTE: PLEASE SEE 210.52D FOR REQ'D
 RECEPTS TO BE W/IN 3' OF SINKS.
  
 4)NOTE: PLEASE SEC`S SHOWN AS 1/0'S.
 PLEASE SEE PER 310.16 OR MIN 310.15B6
 FOR EACH 200A MAIN.
  
 5)NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR A/C COND UNITS. 210.63
  
 6)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 210.12 OF THE
 2002 NEC.
  
 7)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF GR ELEC CONDUCTOR. SEEMS THE #4 AND
 #2 IS REVERSED.
  
 8)NOTE: PLANS DO NOT SHOW MAIN DISC
 NEXT TO METER.
  
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 09:37 Rev Time 0.00
Received By adarroug Date   Time   Sent To E
Notes
2005-02-18 00:00:00TO DPALMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-01-10 Cont ID  
Sent By mjacobs Date 2005-01-10 Time 16:08 Rev Time 0.00
Received By mjacobs Date 2005-01-10 Time 16:08 Sent To B
Notes
2005-01-10 00:00:00TO "JG" DESK./SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 16:15 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 16:15 Sent To B
Notes
2005-01-03 00:00:00TO "JG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-12-23 Cont ID  
Sent By mjacobs Date 2004-12-23 Time 07:27 Rev Time 0.00
Received By mjacobs Date 2004-12-23 Time 07:26 Sent To B
Notes
2004-12-23 00:00:00SENT TO "JG" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 13:36 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 13:36 Sent To E
Notes
2004-11-17 00:00:00SENT TO "E" TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 10:49 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 10:48 Sent To B
Notes
2004-11-17 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-06 Time 10:20 Rev Time 0.00
Received By csiegber Date 2004-07-06 Time 10:20 Sent To  
Notes
2004-07-06 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:08 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 16:08 Sent To M
Notes
2004-07-01 00:00:00TO PK DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:17 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 14:17 Sent To P
Notes
2004-02-27 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-22 Time 14:04 Rev Time 0.00
Received By csiegber Date 2004-01-22 Time 14:04 Sent To E
Notes
2004-01-22 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 11:27 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 11:27 Sent To E
Notes
2003-12-16 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-02 Cont ID  
Sent By mmclean Date 2003-12-02 Time 12:00 Rev Time 0.00
Received By jgomez Date 2003-10-30 Time 12:16 Sent To PC
Notes
2003-11-04 00:00:0010/30/03TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2004-07-08 Cont ID  
Sent By pkrauss Date 2004-07-08 Time 11:08 Rev Time 0.25
Received By pkrauss Date 2004-07-08 Time 11:08 Sent To  
Notes
2004-07-08 00:00:00CALLED CONTRACTOR, FLOOR PLAN ON THE
 MECHANICAL REVISION SUBMITTED DOES NOT
 MATCH THE FLOOR PLAN ON THE ARCHITECURAL
 DRAWINGS.PLEASE PROVIDE ADDITIONAL
 INFORMATION.LEFT A MESSAGE ON THE
 OFFICE & CEL PHONE ANSWERING MACHINES.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-07-01 Time 16:08 Rev Time 0.33
Received By pkrauss Date 2004-02-06 Time 06:57 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By dpalmer Date 2004-02-04 Time 10:22 Rev Time 0.15
Received By pkrauss Date 2004-01-06 Time 06:31 Sent To B
Notes
2004-01-06 00:00:00REVISED ENERGY CALCS ONLY, PLANS
 APPROVED BY HAROLD MOSER 11-22-03.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-22 Cont ID  
Sent By kstevens Date 2003-12-30 Time 10:33 Rev Time 0.50
Received By hmoser Date 2003-11-22 Time 10:46 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-03-05 Cont ID  
Sent By kstevens Date 2004-03-05 Time 11:21 Rev Time 0.50
Received By kstevens Date 2004-03-05 Time 11:21 Sent To  
Notes
2004-03-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SHT A4 REVISION #4 APPEAR TO BE BLDG.
 REVISIONS AND NOT PLUMBING REVISIONS.
 INDICATE REVISIONS FOR PLUMBING WITH A
 # AND A CLOUD.
 2) ALL REVISIONS OF A SIGNED AND SEALED
 SET OF PLANS SHALL BE SIGNED, SEALED AND
 DATED BY THE ARCHITECT OF RECORD. SHEET
 SHALL HAVE A TITLE BLOCK AS REQUIRED BY
 61G1-16.004 WITH ALL INFORMATION REQUIR-
 ED. FS 481.219
 3) REVISION SHALL BE IN ISOMETRIC FORM
 WITH CORRECTIONS AS SHOWN ON SHEET A7
 OF THE STAMPED SET OF PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-02-02 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:17 Rev Time 0.50
Received By kstevens Date 2004-02-02 Time 18:43 Sent To  
Notes
2004-02-06 00:00:00PASSED/PROVISO - REVISION REQUIRED - W/M
 REQUIRES A TRAP & STANDPIPE - BATH #3
 TUB ON RISER, LAV NOT SHOWN - DOWNSTREAM
 OF LAUNDRY ROOM (ON RISER) - SINK NOT
 SHOWN ON FLOOR PLAN - BIDET REQUIRES A
 TRAP.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-30 Cont ID  
Sent By kstevens Date 2003-12-30 Time 10:33 Rev Time 0.50
Received By kstevens Date 2003-12-30 Time 10:32 Sent To M
Notes
2003-12-30 00:00:00PASSED/PROVISO - REVISION REQUIRED - W/M
 REQUIRES A TRAP AND A STANDPIPE, BATH #3
 TUB NOT SHOWER & LAV NOT SHOWN ON RISER,
 BIDET TRAP TO BE UNDERGROUND, SINK NOT
 FOUND ON FLOOR PLAN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-11-24 Cont ID  
Sent By dpalmer Date 2003-12-22 Time 13:16 Rev Time 0.50
Received By jleech Date 2003-11-24 Time 19:07 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-02-04 Cont ID  
Sent By mmclean Date 2004-02-04 Time 09:31 Rev Time 0.00
Received By mmclean Date 2004-02-04 Time 09:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-04 Time 16:45 Rev Time 0.00
Received By mmclean Date 2003-11-03 Time 11:12 Sent To I
Notes
***NONE***