Plan Review Details - Permit 03101791
Plan Review Stops For Permit 03101791
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-07-12 Cont ID  
Sent By rmcdouga Date 2004-07-12 Time 10:48 Rev Time 1.00
Received By rmcdouga Date 2004-07-12 Time 14:02 Sent To E
Notes
2004-07-12 00:00:00REVISED SHEETS A2, A3, A4, A5 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-03-02 Cont ID  
Sent By rmcdouga Date 2004-03-02 Time 14:18 Rev Time 0.33
Received By rmcdouga Date 2004-03-02 Time 14:17 Sent To  
Notes
2004-03-02 00:00:00REVISIONS TO SHEETS A3 AND A4 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-03-01 Cont ID  
Sent By rmcdouga Date 2004-03-01 Time 11:05 Rev Time 1.00
Received By rmcdouga Date 2004-03-01 Time 11:05 Sent To P
Notes
2004-03-01 00:00:00REVISION DENIED
  
 1) THERE IS NO DETAIL THAT CORRESPONDS
 TO ID MARK #6 ON SHEET A3.
  
 2) THE FOURTH REVISION IS INCORRECTLY
 LISTED AS #3 IN THE REVISION HEADER BOX
 ON SHEETS A3 AND A4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-04 Cont ID  
Sent By rmcdouga Date 2004-02-04 Time 12:16 Rev Time 2.00
Received By rmcdouga Date 2004-02-04 Time 12:16 Sent To  
Notes
2004-02-04 00:00:00BUILDING PROVISO
  
 1) SUBMIT PRODUCT APPROVALS FOR IMPACT
 RATED CASEMENT WINDOW, SINGLE OUTSWING
 GLAZED DOOR WITHOUT SIDELITES.
  
 2) SUBMIT THE APPROVED INSTALLATION
 DRAWINGS FOR THE DOUBLE OUTSWING ENTRY
 DOORS.
  
 3) A SEPARATE PERMIT WITH ADDITIONAL
 FEES WILL BE REQUIRED FOR THE STORM
 PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-08 Cont ID  
Sent By dpalmer Date 2004-01-28 Time 12:11 Rev Time 2.50
Received By rmcdouga Date 2004-01-08 Time 14:57 Sent To  
Notes
2004-01-08 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ENERGY CALCULATION FORM APPEARS
 TO CONTAIN ERRORS. THE CEILING AREA
 SHOULD BE MORE THAN THE FLOOR AREA DUE
 TO THE COFFERED CEILINGS IN SEVERAL OF
 THE ROOMS. SEE FBC CHAPTER 13 SECT.604.
 THE FORM LISTS THE R-VALUE OF THE FRAMED
 ADJACENT WALL AS R9. SHOULDN'T THIS BE
 R19 AT THE 2X6 WALL AND R11 AT THE 2X4
 PORTION OF THE WALL?
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 SOME OF THIS INFORMATION IS NOT ON THE
 PLANS.
  
 4) ON SHEET A5 THE D CONNECTION DETAIL
 IS INCORRECTLY SPECIFIED FOR THE GIRDER
 CONNECTION AT THE FRONT WALL OF BEDROOM.
 THERE IS NO COLUMN AT THIS LOCATION.
  
 5) PLEASE REVISE THE ANCHOR SCHEDULE ON
 A5. ROWS G,H & I HAVE INCORRECT VALUES
 IN THE F1 AND F2 COLUMNS FOR LATERAL
 LOADS. NO LATERAL LOADS ARE GIVEN IN THE
 CATALOG FOR THESE CONNECTORS. THE
 ULTIMATE UPLIFT VALUE IS LISTED FOR THE
 SIMPSON HTT22 CONNECTOR. USE THE DESIGN
 VALUE WHICH INCLUDES A SAFETY FACTOR.
  
 6) SPECIFY SAFETY GLASS FOR THE LIVING
 ROOM WINDOWS. SEE FBC 2405.2.1(4).
  
 7) INDICATE HOW THE WINDOWS/BUCKS ARE TO
 BE ATTACHED TO THE STEEL HEADER AND
 COLUMNS AT THE LIVING ROOM WINDOWS.
  
 8) SUBMIT MANUFACTURER'S SPECS. AND UL
 LISTING INFORMATION FOR OPTIONAL BBQ IF
 IT WILL BE INSTALLED.
  
 9) THE STORM PANEL KEY PLAN AND SCHEDULE
 CONTAINS SOME ERRORS. THE FRONT DOORS
 ARE SHOWN AS SOLID DOORS ON PLANS AND
 THEIR HEIGHT IS NINE FEET. THE GUEST
 ROOM DOOR IS IMPACT RESISTANT FOR EGRESS
 AND THE WRONG OPENING IS INDICATED ON
 THE KEY PLAN. OPENING #34 IS MARKED AS
 24 ON THE KEY PLAN. CHECK OPENING SIZES
 AND SPANS. CLEARLY MARK ON THE
 ENGINEERED DRAWINGS THE SPECIFIC TYPE OF
 MOUNTI, THE ANCHOR TYPE AND SPACING
 BASED ON DESIGN PRESSURES, EDGE DISTANCE
 PLANEL SPAN, ETC.
  
 10) PLEASE ATTACH THE COVER SHEETS FROM
 THE STATE PRODUCT APPROVALS TO THE
 APPROPRIATE DRAWINGS FOR THAT SPECIFIC
 ITEM (WINDOW, DOOR, ETC.). ONLY SUBMIT
 PRODUCT APPROVALS FOR ITEMS THAT WILL BE
 USED IN THIS PROJECT.
  
 11) SUBMIT INSTALLATION DRAWINGS FOR THE
 FIXED WINDOWS. ONLY THE STATE COVERSHEET
 WAS SUBMITTED.
  
 12) SUBMIT DRAWINGS FOR THE CASEMENT
 WINDOWS. ONLY STATE COVERSHEET SUBMITTED
  
 13) SUBMIT DRAWINGS FOR THE MULLIONS.
  
 14) THERE ARE NO STOREFRONT DOORS SHOWN
 ON THE PLANS. REMOVE THESE FROM THE
 SUBMITTAL OR SHOW THEIR LOCATION ON THE
 PLANS.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE AND DOUBLE FRENCH DOORS.
  
 16) DOUBLE HUNG AND HORIZONTAL SLIDING
 WINDOWS ARE NOT SHOWN ON THE PLANS.
 REMOVE THESE PRODUCT APP. FROM SUBMITTAL
  
 17) SUBMIT PRODUCT APPROVALS FOR BUTT
 GLASS WINDOW. SEE FBC 2406.2.
  
 18) SUBMIT PRODUCT APPROVALS FOR DOUBLE
 OUTSWING 9' HIGH ENTRY DOORS.
  
 19) CONTRACTOR'S WORKERS COMP. MUST BE
 UPDATED BEFORE PERMIT WILL BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-01 Cont ID  
Sent By pkrauss Date 2004-01-05 Time 16:39 Rev Time 4.00
Received By rmcdouga Date 2003-12-01 Time 10:07 Sent To M
Notes
2003-12-01 00:00:00UNSAT
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ON SHEET A3 THE C8 COLUMN IS NOT
 LISTED IN THE COLUMN SCHEDULE.
  
 3) SAFETY GLAZING IS REQUIRED IN WINDOWS
 THAT ARE WITHIN 3' HORIZONTALLY OF A TUB
 OR SHOWER. SEE FBC 2405.2. SPECIFY ON
 PLANS.
  
 4) INSULATED OR SOLID CORE DOORS ARE
 REQUIRED BETWEEN THE GARAGES AND THE
 CONDITIONED SPACE PER FBC CHAPTER 13.
 SPECIFY ON PLANS.
  
 5) SPECIFY THE SIZE OF THE ATTIC ACCESS
 IN HER CLOSET. SEE FBC 2309.6.
  
 6)SPECIFY THE ATTIC ACCESS FOR SERVICING
 OF THE AHU IN ATTIC OF GOLF CART GARAGE.
 SEE FBC MECHANICAL 306.3. CLARIFY THE
 LOCATION OF THIS UNIT. THE ROOF FRAMING
 PLAN INDICATES THAT IT IS HUNG FROM THE
 TRUSSES AND NOT IN THE ATTIC.
  
 7) SUBMIT MANUFACTURER'S SPECS. AND UL
 LISTING INFORMATION FOR THE BBQ ON THE
 LANAI.
  
 8) THE ROOF FRAMING PLAN ON A5 SPECIFIES
 DETAILS B,C & D ON A4. THESE DETAILS ARE
 ON SHEET A5 AND ARE INCORRECTLY LABELED
 AS A4. PLEASE CORRECT.
  
 9) THE STEEL COLUMN CAPS HAVE THE WRONG
 CONFIGURATIONS SPECIFIED AT SEVERAL
 LOCATIONS. HANGERS ARE INDICATED AT STL.
 COLUMNS AND CAPS ARE SPECIFIED WHERE
 THERE ISN,T A COLUMN. SEE SHEET A5 AND
 DETAILS ON A5.
  
 10) PROVIDE DETAILS FOR THE 3"X 6" TUBE
 STEEL COLUMN BASES AND CAPS.
  
 11) SOME OF THE GIRDERS DO NOT HAVE A
 CONNECTOR SPECIFIED. SEE THE NOTES ON
 A5.
  
 12) THE NOTE ON THE WALL SECTION ON A8
 EXCLUDES SOFFIT VENTS AT CROWN FACIA
 AREAS. SPECIFY THAT ATTIC VENTS SHALL
 PROVIDE A NET FREE VENT AREA WITH A
 RATIO OF 1/150 OF CEILING AREA. SEE FBC
 2309.7.
  
 13) PLEASE UPDATE THE REFERENCE TO THE
 SBC 97 TO THE 2001 FBC ON A8. ALSO
 UPDATE THE SPECIFIED HUGHES CONNECTOR TO
 A CURRENT CONNECTOR. HUGHES IS NO LONGER
 IN BUSINESS.
  
 14) CORRECT THE R VALUES LISTED ON THE
 ENERGY CALCULATION FORM. THE CEILING
 INSULATION IS R30 ON THE PLANS. THE R
 VALUE OF THE INSULATION AT THE CMU
 EXTERIOR WALLS IS 4.2. THE ADJACENT
 FRAME WALL SHOULD BE R-19 FOR 2X6 OR
 R-11 FOR 2X4 WALLS.
  
 15) CHANGE THE R VALUE OF THE INSULATION
 AT THE ATTIC ACCESS DETAIL ON A9 TO
 R-30 TO CORRESPOND WITH THE WALL SECTION
 ON A8.
  
 16) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT.
  
 17) SUBMIT ENGINEERING FOR BUTT GLASS
 WINDOW PER FBC 2406.2.
  
 18) SUBMIT PRODUCT APPROVALS FOR FIXED
 GLASS, ARCHED FIXED GLASS AND CASEMENT
 WINDOWS, STRUCTURAL MULLIONS, OUTSWING
 ENTRY DOORS AND STORM PANELS.
  
 19) SUBMIT THE APPROVED DRAWINGS FOR THE
 OVERHEAD GARAGE DOORS.
  
 20) PLEASE CLARIFY WHERE THE ALUMINUM
 STOREFRONT DOORS WILL BE INSTALLED.
 NOTE THE LIMITATION ON THE PRODUCT
 APPROVAL FOR WATER INTRUSION WITHOUT AN
 ADEQUATE OVERHANG.
  
 21) PRODUCT APPROVALS FOR IMPACT AND
 NON-IMPACT RESISTANT SH WINDOWS AND
 STOREFRONT DOORS WERE SUBMITTED. PLEASE
 CLARIFY.
  
 22)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED AT THE OPTIONAL GUEST SUITE.
 THE KEY PLAN INDICATES IMPACT GLASS FOR
 EGRESS AT THE WRONG LOCATION.
  
 IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE
 RETURN OLD PLANS WITH RESUBMITTAL.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-01-07 Cont ID  
Sent By dpalmer Date 2005-01-07 Time 10:31 Rev Time 0.30
Received By dpalmer Date 2005-01-07 Time 10:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 17:31 Rev Time 0.33
Received By dpalmer Date 2004-11-18 Time 17:31 Sent To  
Notes
2004-11-18 00:00:00*********** UNSAT *********
  
 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU#2.
  
 2)NOTE: PLEASE SEE 250.24, 250.6, NO
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 TO FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66 1/0
  
 4)NOTE: PLEASE SEE LOAD ON 1P20 BRKR FOR
 FRIG. THIS IS SHOWN ON ONE CIRCUIT.
 PLEASE NOTE: THIS IS THE SAME ON LOT
 #17, BUT WAS NOT TYPED IN NOTES.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-07-12 Cont ID  
Sent By rmcdouga Date 2004-07-12 Time 14:18 Rev Time 0.33
Received By dpalmer Date 2004-07-12 Time 17:59 Sent To  
Notes
2004-07-12 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE PANELS AND
 RISER DIAGRAM. PANEL SHOWN AS 150A AND
 RISER SHOWS 200A'S.
  
 2)NOTE: PELASE CORRELATE LOADS , AWG AND
 OCP FOR A/C AHU'SETC.
 PLEASE SEE 424.3B MIN OCP TO BE 125%.
  
 3)NOTE: PLEASE SEE JACUZZI/WHIRLPOOL TUB
 LISTED ON PANEL SCHEDULE BUT NOT SHOWN
 ON PLANS.
  
 4)NOTE: PLEASE SEE GENERAL NOTES TO
 ELECTRICAL. PLEASE SEE NOTES #2 AND 4.
 PLEASE ADJUST NOTES.
 PLEASE SEE 210.12.
  
 5 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-07-08 00:00:00NO ELECTRICAL REVISION SUBMITTED.

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-07-06 Time 10:22 Rev Time 0.00
Received By dpalmer Date 2004-01-28 Time 12:11 Sent To B
Notes
2004-01-28 00:00:00PASSED ON PREVIOUS REVIEW WITH PROVISO
 NO CHANGES MADE FOR ELEC.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-22 Cont ID  
Sent By csiegber Date 2004-01-22 Time 14:03 Rev Time 1.00
Received By dpalmer Date 2003-12-22 Time 12:10 Sent To P
Notes
2003-12-22 00:00:00********** NOTES REDLINED *************
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO
 PANELS.250.122
  
 2)NOTE: PLEASE SEE OCP FOR AHU/HEAT
 NEEDS TO BE SIZED PER 424.3B
  
 3)NOTE: GROUNDING ELECTRODE CONDCUTOR
 PER 250.66, MIN #2
  
 PLEASE SEE THAT THE ABOVE HAS BEEN
 REDLINED ON PLANS. PLEASE MAKE CORRECT-
 -IONS ALONG W/ ANY REV'S.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-12-16 Time 12:11 Rev Time 0.75
Received By dpalmer Date 2003-11-06 Time 15:52 Sent To M
Notes
2003-11-06 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SIZE SEC'S PER 310.16
 OR 310.15B6 FOR A MIN.
 SHOWS 1/0'SFOR 200A'S?
  
 2)NOTE: PLEASE SEE THE GEC TO FOOTER
 STEEL SHOULD BE SIZE PER 250.66.
 THE #2 SHOWN SEEMS TO BE REVERSED WITH
 THE # 4..
  
 3)NOTE: PLEASE SEE THAT WE ARE UNDER THE
 2002 NEC AND 210.12 HAS CHANGED FROM
 WHAT IS NOTED ON PLANS FOR ARC FAULT.
 PLEASE LIST THE REQ'D ARC FAULT PROTECT-
 -ED CIRCUITS ON PANEL SCHEDULE.
 210.12
  
 4)NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING, THERE ARE A FEW MISSING.
  
 5)NOTE: PLEASE SEE 210.63 FOR REQ'D
 GFI RECEPT FOR A/C COND UNITS.
  
 6)NOTE: PLEASE SEE 210.52D FOR RECEPT
 SPACING FROM SINKS/LAV.
  
 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS FOR ALL ROOMS.
  
 8)NOTE: PLEASE SEE MISSING SD FOR WHAT
 APPEARS TO BE A BEDROOM/ADAPTABLE BEDRM
 PER NFPA-72 8-1.4.2. SD IS ALSO REQ'D
 TO BE INSIDE BEDROOM(MASTER?).
  
 9)NOTE: PLEASE SEE PLANS, DOES NOT SHOW
 MAIN DISCONNECT NEXT TO METER?
 215.5
  
 10)NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. 210.8.A6
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 16:24 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 16:24 Sent To E
Notes
2005-01-03 00:00:00TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 13:39 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 13:39 Sent To E
Notes
2004-11-17 00:00:00SENT TO "E" TO DP DESK /REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-07-06 Time 10:22 Rev Time 0.00
Received By csiegber Date 2004-07-06 Time 10:22 Sent To E
Notes
2004-07-06 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 15:32 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 15:32 Sent To M
Notes
2004-07-01 00:00:00REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:18 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 14:18 Sent To P
Notes
2004-02-27 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-01-22 Time 14:03 Rev Time 0.00
Received By csiegber Date 2004-01-22 Time 14:02 Sent To E
Notes
2004-01-22 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-16 Cont ID  
Sent By mmclean Date 2003-12-16 Time 10:29 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 09:47 Sent To E
Notes
2003-12-16 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-01 Cont ID  
Sent By mmclean Date 2004-05-05 Time 15:54 Rev Time 0.00
Received By csiegber Date 2003-10-30 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-07-08 Cont ID  
Sent By pkrauss Date 2004-07-08 Time 10:25 Rev Time 0.30
Received By pkrauss Date 2004-07-08 Time 09:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-05 Cont ID  
Sent By csiegber Date 2004-07-01 Time 15:32 Rev Time 0.15
Received By pkrauss Date 2004-01-05 Time 16:32 Sent To B
Notes
2004-01-05 00:00:00PLANS APPROVED BY HAROLD MOSER 12-1-03,
 REVISED ENERGY & MANUAL J CALCS
 SUBMITTED WITH RE-SUB.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-01 Cont ID  
Sent By kstevens Date 2003-12-30 Time 09:59 Rev Time 0.50
Received By hmoser Date 2003-12-01 Time 19:31 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-03-01 Cont ID  
Sent By kstevens Date 2004-03-01 Time 16:34 Rev Time 0.50
Received By kstevens Date 2004-03-01 Time 16:34 Sent To  
Notes
2004-03-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 NO PLUMBING REVISIONS FOUND.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-30 Cont ID  
Sent By rmcdouga Date 2004-03-01 Time 11:14 Rev Time 0.50
Received By kstevens Date 2003-12-30 Time 09:58 Sent To M
Notes
2003-12-30 00:00:00PASSED/PROVISO - REVISION REQUIRED, NO
 BAR SINK ON RISER, NO LAV SHOWN ON RISER
 FOR BATH #3, TRAP REQUIRED FOR WASH
 MACHINE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-03 Cont ID  
Sent By dpalmer Date 2003-12-22 Time 12:10 Rev Time 0.50
Received By jleech Date 2003-12-03 Time 18:55 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-12-16 Cont ID  
Sent By mmclean Date 2003-12-16 Time 10:29 Rev Time 0.00
Received By mmclean Date 2003-12-16 Time 10:29 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-12-16 Time 09:47 Rev Time 0.00
Received By mmclean Date 2003-11-03 Time 11:24 Sent To I
Notes
2003-11-03 00:00:0011/03/03 MADE AN PROVISO REGARDING
 SIDE SETBACK MUST BE 3'1" CALLED & LEFT
 MSG ON ROY CELL VOICE MAIL MM