Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-17 Cont ID  
Sent By hmoser Date 2003-11-17 Time 19:23 Rev Time 0.25
Received By hmoser Date 2003-11-17 Time 19:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-07 Time 14:34 Rev Time 0.25
Received By hmoser Date 2003-10-29 Time 07:39 Sent To  
Notes
2003-10-29 00:00:00DENIED:
 1.RETURN AIR REQUIRED FROM BEDROOM
 AREAS.RETURNS SHALL BE SIZED AS PER
 REVISION TO THE 2001 FBC(M) 601.4,
 EFFECTIVE JUNE 30,2003 SEE ATTACHED.
  
 2.AUXILIARY DRAIN PAN REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.