Plan Review Stops For Permit 03101472 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-10-24 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-24 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-24 |
Time |
10:07 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-11-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-11-03 |
Time |
13:30 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2003-11-03 |
Time |
13:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-10-30 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-24 |
Time |
10:07 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2003-10-30 |
Time |
07:54 |
Sent To |
|
|
Notes |
2003-10-30 00:00:00 | PLEASE NOTE: | | RETURN TRANSFER DUCTS ARE NOT SIZED | | IN ACCORDANCE WITH 2001 FBC(M) 601.4 | | REVISED JUNE 30, 2003. SEE ATTACHED | | REQUIREMENTS FOR RETURN TRANSFER DUCTS | | AND TRANSFER GRILLES.PLEASE REVISE | | PLANS TO REFLECT PROPER DUCT SIZE FOR | | RETURN TRANSFER DUCTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|