Plan Review Details - Permit 03101403
Plan Review Stops For Permit 03101403
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-04 Cont ID  
Sent By jwitmer Date 2003-12-04 Time 08:26 Rev Time 0.75
Received By jwitmer Date 2003-12-04 Time 08:25 Sent To  
Notes
2003-12-04 00:00:00SUBMITTAL: 12/02/03 CEILING RATING FOR
 STAIRWELL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-11-13 Cont ID  
Sent By csiegber Date 2003-12-02 Time 16:26 Rev Time 1.50
Received By jwitmer Date 2003-11-13 Time 11:41 Sent To  
Notes
2003-11-13 00:00:00BUILDING PROVISO: FBC 803.4
 FOAM COLUMNS NOT ALLOWED, SEE INTERIOR
 FINISHES, 803.1.2 COLUMNS!

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-03 Cont ID  
Sent By jwitmer Date 2003-11-03 Time 07:49 Rev Time 3.50
Received By jwitmer Date 2003-11-03 Time 07:49 Sent To  
Notes
2003-11-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101403
 ADD: 310 EVERNIA
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) SHEET A-1 INDICATES THAT THIS BUILD-
 ING IS TO BE FIRE SPRINKLERED, BUT NO
 PLANS WERE SUBMITTED?
  
 2) DUCTWORK IN STAIRWELL: 1006.1.3.1.
 PENETRATIONS INTO AND OPENINGS THROUGH A
 STAIRWAY ENCLOSURE ASSEMBLY ARE PROHIBIT
 ED EXCEPT FOR REQUIRED EXIT DOORS, DUCT-
 WORK AND EQUIPMENT NECESSARY FOR INDEPEN
 DENT STAIR PRESSURIZATION, SPRINKLER
 PIPING, STANDPIPES AND ELECTRICAL CON-
 DUIT SERVING THE STAIRWAY AND TERMINAT-
 ING AT A STEEL BOX NOT EXCEEDING 16 SQ
 INCHES.
  
 3) FOAM COLUMNS AND PILASTERS: 803.4
 FOAM PLASTIC TRIM SHALL NOT BE FOR TRIM,
 SEE EXCEPTIONS! PROVIDE ADDITIONAL INFOR
 MATION.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 STAIRS RISE & RUN GUARDRAILS, HANDRAILS
 AND EXTENSIONS.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 AC-1 INDICATES A SKYLIGHT IS THIS EXIST-
 ING OR IS IT NEW?
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORT:
 A) FRENCH DOORS/ STORM SHUTTERS
  
 7) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 8)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-01-28 Cont ID  
Sent By dpalmer Date 2004-01-28 Time 12:44 Rev Time 0.50
Received By dpalmer Date 2004-01-28 Time 12:44 Sent To  
Notes
2004-01-28 00:00:00WAITING FOR SECOND SET OF FA SIGNED
 AND SEALED BY ENG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-07 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 16:31 Rev Time 0.33
Received By dpalmer Date 2003-11-07 Time 16:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 08:05 Rev Time 0.50
Received By dpalmer Date 2003-10-28 Time 08:04 Sent To  
Notes
2003-10-28 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE INCLUDE ALL INFORMATION
 AS SET FORTH IN FAC 61G15-23.002 IN A
 TITLE BLOCK. PER FS 471
  
 2)NOTE: PLEASE SEE THAT AS OF JULY 1ST,
 2003 WE ARE NOW UNDER THE 2002 NEC.
 PLEASE ADJUST PLANS.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS THAT NAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-13 Cont ID  
Sent By mcarsill Date 2003-11-13 Time 07:17 Rev Time 0.00
Received By mcarsill Date 2003-11-13 Time 07:17 Sent To  
Notes
2003-11-13 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM INSTALLATION.
  
 2) FIRE ALARM CIRCUITS SHALL BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE. AS OF
 AUGUST 1, 2003, ALL FIRE ALARM SYSTEMS
 THAT SUPERVISE FIRE SPRINKLERS SHALL
 BE UL LISTED FOR CENTRAL STATION
 SERVICE.
  
 3) CENTRAL FIRE SPRINKLERS ARE CALLED
 OUT FOR USE. PLEASE VERIFY AT
 WWW.SPRINKLERREPLACEMENT.COM THAT
 THESE HEADS ARE NOT ON ANY RECALL LIST.
  
 4) A KNOX-BOX WILL BE REQUIRED.
  
 5) FOAM COLUMNS STILL SHOWN ON PLANS
 BUT PLAN REVIEW COMMENTS INDICATES
 THAT FOAM COLUMNS ARE NOT GOING TO
 BE USED. THIS ISSUE WILL BE CONSIDERED
 CLOSED BASED ON THE INFORMATION
 PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-30 Cont ID  
Sent By mcarsill Date 2003-10-30 Time 16:18 Rev Time 0.00
Received By mcarsill Date 2003-10-30 Time 16:18 Sent To  
Notes
2003-10-30 00:00:001) LIFE SAFETY ANALYSIS BOX MAKES
 SEVERAL REFERENCES TO THE BUILDING
 BEING FIRE SPRINKLER PROTECTED. NO
 FIRE SPRINKLER DRAWINGS HAVE BEEN
 PROVIDED. THE ANALYSIS BOX ALSO
 INDICATES EXCEPTIONS TO THE CODE BY
 USING THE FIRE SPRINKLER EXCEPTIONS.
  
 2) EXITS DO NOT APPEAR TO MEET ONE
 HALF THE DIAGONAL RULE IF YOU DO NOT
 SPRINKLER PROTECT THE BUILDING. PLEASE
 EXPLAIN. SPRINKLER PROTECTION AFFORDS
 THE ONE THIRD THE DISTANCE RULE.
  
 3) PLEASE PROVIDE DETAILS ON FOAM
 COLUMNS.
  
 4) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION.
  
 5) IT APPEARS MECHANICAL EQUIPMENT IS
 PRESENT WITHIN THE NORTHEAST STAIRWELL.
 PLEASE ADVISE IF THIS EQUIPMENT MEETS
 THE FBC OR THE FFPC FOR PERMITTED
 EQUIPMENT.
  
 6) TACTILE SIGNAGE REQUIRED AT STAIRWELL
 DOORS.
  
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 8) SHAFTWAYS ARE TO BE MARKED.
  
 9) SINGLE OR MULTIPLE TENANTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-01-21 Time 14:01 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 14:01 Sent To  
Notes
2004-01-21 00:00:00TO COMM BD#9

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-02 Cont ID  
Sent By csiegber Date 2003-12-02 Time 16:25 Rev Time 0.00
Received By csiegber Date 2003-12-02 Time 16:25 Sent To B
Notes
2003-12-02 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-07 Cont ID  
Sent By csiegber Date 2003-11-07 Time 16:49 Rev Time 0.00
Received By csiegber Date 2003-11-07 Time 16:49 Sent To  
Notes
2003-11-07 00:00:00TO COMM BD #30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-14 Cont ID  
Sent By kstevens Date 2003-11-14 Time 14:22 Rev Time 0.00
Received By kstevens Date 2003-10-22 Time 16:20 Sent To  
Notes
2003-10-22 00:00:00TO COMM BD#10

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-12-22 Cont ID  
Sent By pkrauss Date 2003-12-22 Time 16:51 Rev Time 0.33
Received By pkrauss Date 2003-12-22 Time 16:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-13 Cont ID  
Sent By pkrauss Date 2003-11-13 Time 13:17 Rev Time 0.40
Received By pkrauss Date 2003-11-13 Time 13:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-30 Cont ID  
Sent By pkrauss Date 2003-10-30 Time 09:54 Rev Time 0.45
Received By pkrauss Date 2003-10-30 Time 09:54 Sent To  
Notes
2003-10-30 00:00:00DENIED:
 SECOND FLOOR EAST STAIRWELL INDICATES
 DUCT RUNNING THROUGH THE STAIRWELL.AS
 PER 2001 FBC 1006.1.3.1 THE ONLY DUCT
 WORK ALLOWED IN A STAIRWELL IS FOR THE
 PURPOSE OF STAIRWELL PRESSURIZATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-11-14 Cont ID  
Sent By kstevens Date 2003-11-14 Time 14:22 Rev Time 1.50
Received By kstevens Date 2003-11-14 Time 14:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-11-12 Cont ID  
Sent By kstevens Date 2003-11-12 Time 14:16 Rev Time 0.33
Received By kstevens Date 2003-11-12 Time 14:16 Sent To  
Notes
2003-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW:
 SHT A-1 BREAK ROOM SINKS, ROOM 105 & 203
 SHALL BE ACCESSIBLE PER SECTION 11-4.24.
 SUBMIT A DETAIL SHOWING HEIGHT 11-4.24.2
 DEPTH 11-4.24.4, CLEAR FLOOR SPACE 11-4.
 24.5, AND FAUCETS 11-4.24.7. NO DETAIL
 WAS FOUND AS REQUESTED.
 2) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 553.80(2)(B) DESIGN PROFESSIONAL
 DOCUMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-30 Cont ID  
Sent By kstevens Date 2003-10-30 Time 09:42 Rev Time 0.00
Received By kstevens Date 2003-10-30 Time 15:43 Sent To  
Notes
2003-10-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) SHT A-1 BREAK ROOM SINKS, ROOMS 105
 AND 203 SHALL BE ACCESSIBLE PER SECTION
 11-4.24. SUBMIT A DETAIL SHOWING WITH
 THAT SECTION AND ALL SUBSECTIONS.
 2) SHEETS AC1 & AC2 SEE ATTACHED SHEET
 CONCERNING 61G15-23.002(2) TITLE BLOCK.
 3) SHT P1 SEE ATTACHED SHEET CONCERNING
 G1615-23.002(1) CONCERNING SEAL, SIGNAT-
 URE, & DATE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]