Plan Review Stops For Permit 03101365 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2003-12-08 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2003-12-08 |
Time |
13:12 |
Rev Time |
1.00 |
Received By |
lsmith |
Date |
2003-12-08 |
Time |
13:12 |
Sent To |
|
|
Notes |
2003-12-08 00:00:00 | PLANS HAVE TO BE TAKEN BACK TO PBC FOR | | ADJUSTMENT OF IMPACT FEES. SQ FOOTAGE | | WAS UNDERSTATED ON APPLICATION. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-10-30 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2003-10-28 |
Time |
19:08 |
Rev Time |
1.50 |
Received By |
lsmith |
Date |
2003-10-30 |
Time |
15:00 |
Sent To |
|
|
Notes |
2003-10-30 00:00:00 | *******BUILDING REVIEW FAILED********* | | | | 1. SQUARE FOOTAGE NOT SHOWN ON PLANS. | | | | 2. SEVERAL OF THE SHEETS ARE PHOTO COPY | | FROM ANOTHER HOUSE.SS STATES THE | | PLANSHAVE TO HAVE ORIGINAL SIGNATURE & | | SEAL CLEARLY SHOWN SS 471.025 | | | | 3. WHEN COPIES OF PLANS ARE REPLACED | | THEY CAN BE TAKEN TO PALM BEACH COUNTY | | AND IMPACT FEES PAID.A COPY OF THE | | RECEIPT AND STAMPED PLANS CAN BE | | RETURNED FOR A PERMIT. | | | | 4. PRODUCT APPROVALS ARE EXPIRED FOR THE | | FIXED WINDOWS.SUBMIT UPDATED PRODUCT | | APPROVAL. | | | | ANY QUESTIONS PLEASE CALL: | | LEA SMITH, BUILDING PLANS EXAMINER | | 805-6713 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2003-10-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-10-27 |
Time |
13:58 |
Rev Time |
0.40 |
Received By |
dpalmer |
Date |
2003-10-27 |
Time |
13:58 |
Sent To |
M |
|
Notes |
2003-10-27 00:00:00 | REDLINED 2002 NEC REQUIREMENTS. | | ALSO REDLINED ADDRESS ON E-SHEETS ONLY. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-12-01 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-12-01 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-12-01 |
Time |
15:55 |
Sent To |
M |
|
Notes |
2003-12-01 00:00:00 | TO PK BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-10-30 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2003-10-22 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-21 |
Time |
15:31 |
Sent To |
|
|
Notes |
2003-10-22 00:00:00 | TO Z | | TO SFD RACK/E |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-12-04 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2003-12-04 |
Time |
18:46 |
Rev Time |
0.25 |
Received By |
rregueir |
Date |
2003-12-04 |
Time |
18:46 |
Sent To |
|
|
Notes |
2003-12-04 00:00:00 | PROVISO:MINIMUM ALLOWABLE R/A FOR THIS | | MASTER SUITE IS 14" ROUND | | PER FBC,M 601.4 | | | | RONALD J REGUEIRO | | 561-805-6734 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2003-10-28 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-12-01 |
Time |
15:55 |
Rev Time |
0.33 |
Received By |
pkrauss |
Date |
2003-10-28 |
Time |
06:54 |
Sent To |
P |
|
Notes |
2003-10-28 00:00:00 | DENIED: | | RETURN AIR NOT SIZED PROPERLY, SEE | | ATTACHED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2003-10-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-10-28 |
Time |
06:55 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2003-10-28 |
Time |
19:08 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-10-22 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2003-10-22 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
|
Time |
|
Sent To |
I |
|
Notes |
|
|