Plan Review Details - Permit 03101365
Plan Review Stops For Permit 03101365
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-08 Cont ID  
Sent By lsmith Date 2003-12-08 Time 13:12 Rev Time 1.00
Received By lsmith Date 2003-12-08 Time 13:12 Sent To  
Notes
2003-12-08 00:00:00PLANS HAVE TO BE TAKEN BACK TO PBC FOR
 ADJUSTMENT OF IMPACT FEES. SQ FOOTAGE
 WAS UNDERSTATED ON APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-30 Cont ID  
Sent By jleech Date 2003-10-28 Time 19:08 Rev Time 1.50
Received By lsmith Date 2003-10-30 Time 15:00 Sent To  
Notes
2003-10-30 00:00:00*******BUILDING REVIEW FAILED*********
  
 1. SQUARE FOOTAGE NOT SHOWN ON PLANS.
  
 2. SEVERAL OF THE SHEETS ARE PHOTO COPY
 FROM ANOTHER HOUSE.SS STATES THE
 PLANSHAVE TO HAVE ORIGINAL SIGNATURE &
 SEAL CLEARLY SHOWN SS 471.025
  
 3. WHEN COPIES OF PLANS ARE REPLACED
 THEY CAN BE TAKEN TO PALM BEACH COUNTY
 AND IMPACT FEES PAID.A COPY OF THE
 RECEIPT AND STAMPED PLANS CAN BE
 RETURNED FOR A PERMIT.
  
 4. PRODUCT APPROVALS ARE EXPIRED FOR THE
 FIXED WINDOWS.SUBMIT UPDATED PRODUCT
 APPROVAL.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-10-27 Cont ID  
Sent By dpalmer Date 2003-10-27 Time 13:58 Rev Time 0.40
Received By dpalmer Date 2003-10-27 Time 13:58 Sent To M
Notes
2003-10-27 00:00:00REDLINED 2002 NEC REQUIREMENTS.
 ALSO REDLINED ADDRESS ON E-SHEETS ONLY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 15:55 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 15:55 Sent To M
Notes
2003-12-01 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-30 Cont ID  
Sent By mmclean Date 2003-10-22 Time 15:40 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 15:31 Sent To  
Notes
2003-10-22 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By rregueir Date 2003-12-04 Time 18:46 Rev Time 0.25
Received By rregueir Date 2003-12-04 Time 18:46 Sent To  
Notes
2003-12-04 00:00:00PROVISO:MINIMUM ALLOWABLE R/A FOR THIS
 MASTER SUITE IS 14" ROUND
 PER FBC,M 601.4
  
 RONALD J REGUEIRO
 561-805-6734

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By csiegber Date 2003-12-01 Time 15:55 Rev Time 0.33
Received By pkrauss Date 2003-10-28 Time 06:54 Sent To P
Notes
2003-10-28 00:00:00DENIED:
 RETURN AIR NOT SIZED PROPERLY, SEE
 ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-28 Cont ID  
Sent By pkrauss Date 2003-10-28 Time 06:55 Rev Time 0.33
Received By jleech Date 2003-10-28 Time 19:08 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-22 Cont ID  
Sent By mmclean Date 2003-10-22 Time 15:40 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***