2003-10-24 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE MAKE THE FOLLOWING CHANGES TO |
| PLAN FOR CODE COMPLIANCE,AND RESUBMIT |
| FOR REVIEW. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 2} PLEASE NOTE THAT ALL PLANS |
| THAT ARE SIGNED AND SEALED BY ARCH/ OR |
| ENGINEER ARE REQ`D PER 61G15-23.002 FOR |
| ENGINEER AND 61G1-16.004 FOR ARCH. |
| SHALL HAVE A TITLE BLOCK.ALSO A WET |
| SIGNATURE. |
| |
| 3} PLEASE NOTE THAT THE DRYER LISTED ON |
| THE PANEL SCHEDULE IS SHOWN AT 20 AMPS. |
| SEE 220.18. |
| |
| 4} PLEASE DO LOAD CALCULATIONS PER |
| 220.30,220.31 OR SHOW A GENERAL LOAD |
| CALC PER ARTICLE 220. |
| |
| 5} PLEASE NOTE THE GEC MUST COMPLY WITH |
| 250.66,INDICATE ON THE RISER DIAGRAM. |
| |
| 6} THE PANEL SCHEDULE INDICATES NEW |
| SMALL APPLIANCE CIRCUITS,BUT NO WORK TO |
| THE KITCHEN IS INDICATED IN THE SCOPE |
| OF WORK FOR THIS PERMIT.THE LAST |
| ELECTRICAL PERMIT ISSUED BESIDES LOW |
| VOLTAGE WAS IN 1997 AND FOR A PANEL |
| RELOCATION.IF THE KITCHEN IS TO BE |
| REWIRED PLEASE INDICATE SAME ON THE |
| PERMIT APPLICATION AND INCLUDE IN THE |
| VALUE OF THE JOB. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |