Plan Review Details - Permit 03101236
Plan Review Stops For Permit 03101236
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-01-07 Time 16:07 Rev Time 0.00
Received By csiegber Date 2004-01-07 Time 16:07 Sent To P
Notes
2004-01-07 00:00:00TO GAS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-17 Time 11:58 Rev Time 0.00
Received By csiegber Date 2003-11-17 Time 11:58 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-10-21 Time 10:33 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 10:33 Sent To P
Notes
2003-10-21 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-12 Cont ID  
Sent By kstevens Date 2004-01-12 Time 17:32 Rev Time 0.50
Received By kstevens Date 2004-01-12 Time 17:32 Sent To  
Notes
2004-01-12 00:00:00 
  
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
  
  
  
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-12-06 Cont ID  
Sent By csiegber Date 2004-01-07 Time 16:07 Rev Time 1.00
Received By kstevens Date 2003-12-06 Time 16:21 Sent To  
Notes
2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A) THE FOLLOWING INFORMATION STILL RE-
 QUIRED FOR GAS PERMIT.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SEE PLANS OF SECTIONS OF
 PIPE WITH NO MEASURMENTS.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). NOT SHOWN
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. RESPONSE NOTED,
 BUT SECTION 303.3 STATES, "FUEL-FIRED
 APPLIANCES SHALL NOT BE LOCATED IN, OR
 OBTAIN COMBUSTION AIR FROM, ANY OF THE
 FOLLOWING ROOMS OR SPACES:
 1. SLEEPING ROOMS. 2. BATHROOMS. 3. TOI-
 LET ROOMS. 4. STORAGE CLOSETS ECT.
 4) IF THE PRESSURE FOR THIS SYSTEM IS
 2 LBS, THEN REGULATORS SHALL BE REQUIRED
 AT EACH APPLIANCE. 1" PIPE WILL SUPPLY
 UP TO 260,000 BTU'S UP TO 60' WITH .5PSI
 SO 2 LB IS NOT NEEDED. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-25 Cont ID  
Sent By csiegber Date 2003-11-17 Time 11:58 Rev Time 0.75
Received By kstevens Date 2003-10-25 Time 12:54 Sent To  
Notes
2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. KITCHEN AND BAR SINK
 ARE NOT VENTED. SUBMIT SANT. RISER DIA-
 GRAM IN AN ISOMETRIC FORM. SHOW VENTS.
 WASH MACHINE REQUIRES A C/O AT 4' ABOVE
 THE FLOOR. 708.10 - 901.2.1
 2) SEPARATE PERMIT REQUIRED FOR GAS.
 THE FOLLOWING INFORMATION IS REQUIRED AT
 APPLICATION FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304. FOR WATER HEATER
 AND DRYER.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 3) SEE ATTACHED SHEET CONCERNING DESIGN
 PROFESSIONALS. TITLE BLOCK REQUIRED WITH
 INFORMATION STATED PER 61G1-16.004
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]