Plan Review Details - Permit 03101193
Plan Review Stops For Permit 03101193
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-11 Cont ID  
Sent By lsmith Date 2003-12-11 Time 09:58 Rev Time 0.50
Received By lsmith Date 2003-12-11 Time 09:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By csiegber Date 2003-12-08 Time 14:24 Rev Time 0.50
Received By lsmith Date 2003-12-04 Time 12:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-04 Cont ID  
Sent By lsmith Date 2003-10-21 Time 08:48 Rev Time 0.50
Received By lsmith Date 2003-10-21 Time 08:48 Sent To  
Notes
2003-11-04 00:00:00**********BUILDING FAILED************
  
 1. SEE NOTES UNDER ELECTRICAL.PLANS
 ARE SIGNED & SEALED BUT ARE MISSING THE
 ARCHITECT LIACENSE NUMBER REQUIRED UNDER
 STATE STATUTE 481.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-07 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 06:14 Rev Time 0.25
Received By dpalmer Date 2003-11-07 Time 06:14 Sent To  
Notes
2003-11-07 00:00:00OK FOR RECEPTS.
 SEE POSSIBLE FIRE REVIEW NOTES.
 NO EM/EXT LTS ADDED PER PREVIOUS REVIEW.
 PASSED PENDING FIRE REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2003-10-30 Cont ID  
Sent By dpalmer Date 2003-10-30 Time 07:28 Rev Time 0.25
Received By dpalmer Date 2003-10-30 Time 07:28 Sent To  
Notes
2003-10-30 00:00:00CONT CALLED.
 WILL APPLY FOR SEPARATE ELECTRICAL
 PERMIT AND SUBMIT PLAN AT THAT TIME.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 07:25 Rev Time 0.25
Received By dpalmer Date 2003-10-28 Time 07:24 Sent To  
Notes
2003-10-28 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE ONE SET HAS HAND
 WRITTEN ELECTRICAL AND OTHER SET HAS
 NOTHING. PLEASE SEE THAT HANDWRITTEN
 ITEMS MAY NOT BE DONE ON SIGNED AND SEAL
 -ED PLANS UNLES EACH CHANGE IS DATED AND
 SIGNED/INITIALED BY THE ARCH OR ENGINEER
 OF RECORD. 481.221/ 471.025
  
 2)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK FOR ARCH AS REQ'D UNDER
 FAC 61G1-16.004 AND FS 471.
  
 PLEASE NOTE: AN ELECTRICAL PERMIT IS
 NOT BEING APPLIED FOR AND MAY BE REQUEST
 NO ELECTRICAL REVIEW TO BE DONE AND MAY
 SUBMIT DRAWING LATER W/ ELECTRICAL
 PERMIT APPLICATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. OR PLEASE CALL TO HAVE ELEC
 REVIEW TAKEN OUT.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By mcarsill Date 2003-11-24 Time 16:13 Rev Time 0.00
Received By mcarsill Date 2003-11-24 Time 16:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-06 Cont ID  
Sent By mcarsill Date 2003-11-06 Time 14:49 Rev Time 0.00
Received By mcarsill Date 2003-11-06 Time 14:49 Sent To  
Notes
2003-11-06 00:00:001) PLANS DOES NOT REFLECT ANY
 EXISTING EXIT SIGNS OR EMERGENCY
 LIGHTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-08 Cont ID  
Sent By csiegber Date 2003-12-08 Time 14:24 Rev Time 0.00
Received By csiegber Date 2003-12-08 Time 14:24 Sent To B
Notes
2003-12-08 00:00:00TO LS DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 16:54 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 16:54 Sent To  
Notes
2003-11-06 00:00:00TO COMM BD#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-10-20 Time 15:57 Rev Time 0.00
Received By csiegber Date 2003-10-20 Time 15:57 Sent To  
Notes
2003-10-20 00:00:00TO COMM BD#9