Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-10-16 Time 16:38 Rev Time 0.40
Received By pkrauss Date 2003-10-21 Time 12:29 Sent To  
Notes
2003-10-21 00:00:00PROVISO:
 1.DUCT SMOKE DETECTOR SHALL BE
 INSTALLED IN THE SUPPLY AIR DUCT AS PER
 2001 FBC(M) 606.2.1.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS AS PER NFPA
 90A 4-4.4.3.
  