Plan Review Stops For Permit 03101014 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-10-16 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-16 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-16 |
Time |
16:38 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-10-21 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-16 |
Time |
16:38 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2003-10-21 |
Time |
12:29 |
Sent To |
|
|
Notes |
2003-10-21 00:00:00 | PROVISO: | | 1.DUCT SMOKE DETECTOR SHALL BE | | INSTALLED IN THE SUPPLY AIR DUCT AS PER | | 2001 FBC(M) 606.2.1. | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | IN NORMALLY OCCUPIED AREAS AS PER NFPA | | 90A 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|