Plan Review Details - Permit 03101002
Plan Review Stops For Permit 03101002
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-03-12 Cont ID  
Sent By rmcdouga Date 2004-03-12 Time 15:02 Rev Time 1.00
Received By rmcdouga Date 2004-03-12 Time 15:02 Sent To  
Notes
2004-03-12 00:00:00PRODUCT APPROVAL FOR SINGLE OUTSWING
 ENTRY DOOR IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-02-23 Cont ID  
Sent By csiegber Date 2004-03-05 Time 08:02 Rev Time 0.50
Received By rmcdouga Date 2004-02-23 Time 11:15 Sent To  
Notes
2004-02-23 00:00:00PRODUCT APPROVAL SUBMITTAL IS DENIED.
 THE SUBMITTAL IS FOR AN OUTSWING DOOR
 WITH SIDELITES AND THE PLANS SPECIFY A
 SINGLE OUTSWING DOOR WITHOUT SIDELITES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-02-20 Time 15:59 Rev Time 1.00
Received By rmcdouga Date 2004-01-16 Time 16:28 Sent To  
Notes
2004-01-16 00:00:00SUBMITALS FOR STATE PROD. APP. OK FOR
 ALL EXCEPT SINGLE OUTSWING ENTRY DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By csiegber Date 2004-01-16 Time 07:47 Rev Time 3.00
Received By rmcdouga Date 2003-12-04 Time 08:41 Sent To  
Notes
2003-12-04 00:00:00PROVISO
  
 1) SUBMIT STATE OF FLORIDA PRODUCT
 APPROVALS FOR REVIEW FOR THE ITEMS
 LISTED BELOW BEFORE INSTALLING.
 - OVERHEAD GARAGE DOORS
 - ONE HOUR FIRE RATED GLASS BLOCK
 - RECTANGULAR FIXED GLASS WINDOWS
 - ARCHED FIXED GLASS WINDOWS
 - STRUCTURAL MULLIONS
 - SLIDING GLASS DOORS
 - HORIZONTAL SLIDING WINDOWS
 - SINGLE OUTSWING DOOR (ENTRY)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-17 Cont ID  
Sent By btrobaug Date 2003-11-24 Time 11:55 Rev Time 3.00
Received By rmcdouga Date 2003-11-17 Time 14:22 Sent To  
Notes
2003-11-17 00:00:00UNSAT
  
 1) THE LETTER FROM THE ARCHITECT
 ADDRESSING THE TRUSSES DOES NOT HAVE AN
 ORIGINAL WET SIGNATURE. THERE IS NOTHING
 ON THE PLANS INDICATING THE MODEL TO
 WHICH THE LETTER REFERS.
  
 2) SPECIFY ON THE PLANS THAT THE WWF IN
 THE SLAB WILL BE SUPPORTED AT 3'OC AS
 REQUIRED BY FBC 1909.3.
  
 3) THE STAIRS FROM THE LOFT TO THE BED
 ROOMS DO NOT COMPLY WITH FBC 1007.3. THE
 SUM OF TWO RISERS AND A TREAD EXCLUSIVE
 OF THE NOSING SHALL BE NO LESS THAN 24"
 NOR MORE THAN 25".
  
 4) HANDRAILS 34"- 38" HIGH ARE REQUIRED
 FOR STAIRWAYS WITH FOUR OR MORE RISERS
 PER FBC 1007.5. HANDRAILS MUST PROVIDE
 GRASPABILITY AS REQUIRED BY FBC 1007.5.3
 GUARDRAILS FOR DWELLING SHALL BE A MIN.
 OF 36" HIGH PER FBC 1026.5.
  
 5) THE 120 SQ.IN. VENT IN THE GARAGE CAN
 NOT BE LOCATED IN THE WALL ON THE ZERO
 LOT LINE. NO OPENINGS ARE ALLOWED IN
 THIS WALL PER FBC TABLE 600.
  
 6) ON THE FRAMING PLAN ON A7 A LINTEL
 (L1) IS INDICATED AT THE SHOWER IN THE
 MASTER BEDROOM. NO OPENING IS SHOWN ON
 THE FLOOR PLAN AT THIS LOCATION. PLEASE
 CLARIFY.
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 APPLICATIONS AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE STATE OF
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION SEE THE STATE WEBSITE AT WWW
 FLORIDABUILDING.ORG. PRODUCTS WITH STATE
 APPROVAL ARE REQUIRED TO BE SUBMITTED
 WITH A COVER SHEET WHICH LISTS THE
 PRODUCT IDENTITY NUMBER FROM THE STATE.
 IF THE PRODUCT DOES NOT HAVE A STATEWIDE
 PRODUCT APPROVAL, SUBMIT AN APPLICATION
 FOR LOCAL PRODUCT APPROVAL PER RULE
 9B-72. SEE ATTACHMENT.
  
 8) FBC 1606.1.4 REQUIRES EXTERIOR
 GLAZING PROTECTION IN WINDBORNE DEBRIS
 REGIONS. PROVIDE (2) PRODUCT APPROVALS,
 KEY PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 9)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE SINGLE OUTSWING FRONT
 DOOR. THE ONE THAT WAS SUBMITTED IS FOR
 DOUBLE OUTSWING DOORS ONLY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-18 Cont ID  
Sent By btrobaug Date 2004-06-18 Time 16:23 Rev Time 0.50
Received By btrobaug Date 2004-06-18 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By btrobaug Date 2003-11-24 Time 11:55 Rev Time 0.50
Received By btrobaug Date 2003-11-24 Time 11:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-11-21 Time 16:57 Rev Time 0.75
Received By dpalmer Date 2003-10-27 Time 14:58 Sent To M
Notes
2003-10-27 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL SERVICE EQUIPMENT. MAINS/PANELS/BRKR
 -S ARE ALL TO BE RATED FOR THE THE
 AVIALABLE FAULT CURRENT. 110.9/ 215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPT IN
 WAHT APPEARS TO BE DINING RM? 2' OF WALL
 SPACE. 210.52
  
 3)NOTE: PLEASE SEE MISSING RECEPT FOR
 KITCHEN COUNTERSPACE PER 210.52C1
  
 4)NOTE : PLEASE SEE OCP SHOWN FOR 5KW
 AHU, SHOWS 2P60? PLEASE CORRELATE.
 PER 424.3B
  
 5)NOTE: PLEASE SEE PLACEMENT OF RECEPT
 IN MASTER BATH. TO BE W/IN 3' OF SINK.
 210.52D
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR]
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL..
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-05 Time 08:02 Rev Time 0.00
Received By csiegber Date 2004-03-05 Time 08:02 Sent To B
Notes
2004-03-05 00:00:00TO RM DESK/PA

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 15:59 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 15:59 Sent To B
Notes
2004-02-20 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 07:46 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 07:46 Sent To B
Notes
2004-01-16 00:00:00TO RM DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-21 Cont ID  
Sent By csiegber Date 2003-11-21 Time 16:57 Rev Time 0.00
Received By csiegber Date 2003-11-21 Time 16:57 Sent To E
Notes
2003-11-21 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2203-11-17 Cont ID  
Sent By mmclean Date 2004-05-05 Time 15:52 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 12:05 Sent To  
Notes
2003-10-22 00:00:0010-17-2003 TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-29 Cont ID  
Sent By jleech Date 2003-10-28 Time 20:13 Rev Time 0.50
Received By hmoser Date 2003-10-29 Time 17:44 Sent To B
Notes
2003-10-29 00:00:00PASS PRIVISO
 1) REFER TO SECTION 601.4 BALANCED
 RETURN AIR (GLITCH)
 2) REFER TO SECTION 307.2.3 AUXILLARY
 DRAIN PANS.AUXILIARY DRAIN PANS SHALL
 BE INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-28 Cont ID  
Sent By jleech Date 2003-10-28 Time 20:13 Rev Time 0.33
Received By jleech Date 2003-10-28 Time 20:13 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-17 Time 13:26 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***