Plan Review Stops For Permit 03100990 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-10-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-10-28 |
Time |
09:35 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-10-28 |
Time |
09:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-10-23 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-16 |
Time |
15:30 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-10-23 |
Time |
16:09 |
Sent To |
|
|
Notes |
2003-10-23 00:00:00 | ************** UNSAT ********** | | | | 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE | | SHOWING ALL MIN REQ'D CIRCUITS, OCP AND | | WIRE SIZE. | | LIST ALL DEDICATED CIRCUITS ETC. | | KITCHEN/BATHS/ARC FAULT/WASHER/ETC ETC | | 220, 210, 215.5 ,210.12,210.52,210.11 | | SHOW LOAD CALC AND EXISTING SERVICE SIZE | | | | 2)NOTE: PLEASE SEE 210.52E FOR FRONT | | AND REAR RECEPTS. | | | | 3)NOTE: PLEASE SEE SOME RECEPTS MISSING | | IN WHAT APPEARS TO BE KITCHEN.210.52 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|