Plan Review Details - Permit 03100897
Plan Review Stops For Permit 03100897
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-10-27 Cont ID  
Sent By btrobaug Date 2003-10-27 Time 09:48 Rev Time 0.50
Received By lsmith Date 2003-10-27 Time 09:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-05 Cont ID  
Sent By btrobaug Date 2003-11-05 Time 18:29 Rev Time 0.33
Received By btrobaug Date 2003-11-05 Time 18:16 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-11-05 Time 15:36 Rev Time 0.33
Received By btrobaug Date 2003-10-27 Time 09:40 Sent To B
Notes
2003-10-27 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION FOR
 ALL NEW AND EXISTING EQUIPMENT.ALSO
 INDICATE THE SIZE OF THE SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-11-05 Time 15:35 Rev Time 0.00
Received By csiegber Date 2003-11-05 Time 15:34 Sent To E
Notes
2003-11-05 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-10-15 Time 16:47 Rev Time 0.00
Received By csiegber Date 2003-10-15 Time 16:47 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-11-08 Cont ID  
Sent By kstevens Date 2003-11-08 Time 13:35 Rev Time 0.50
Received By kstevens Date 2003-11-08 Time 13:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-25 Cont ID  
Sent By btrobaug Date 2003-11-05 Time 18:29 Rev Time 0.50
Received By kstevens Date 2003-10-25 Time 07:41 Sent To E
Notes
2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) MORE INFORMATION REQUIRED FOR THE
 CARETAKER 99 FLOOR CLEANING SYSTEM.
 NOTE #5 STATES "THIS SYSTEM REQUIRES 100
 PERCENT OF THE FLOW GENERATED BY THE
 PUMPS WE HAVE LISTED. OPERATION OF ADD-
 ITIONAL WATER FEATURES WILL AFFECT THE
 CARETAKER SYSTEM PERFORMANCE". THE POOL
 SPECIFICATIONS INDICATE A 4' SHEER DES-
 CENT BEING RETURNED TO THE POOL FROM THE
 SAME PUMP. WILL THIS AFFECT THE CARE-
 TAKER SYSTEM PERFORMANCE?
 NOTE #6 STATES "STEPS MUST BE FLARED
 ENOUGH TO INSURE PROPER CLEANING AND
 ACCOMMODATE GUARANTEE. SEE ATTACHED
 BULLETIN". NO ATTACHED BULLETIN FOUND.
 PLEASE CLAIRFY.
 2) NO INTERNAL MEANS OF INTERNAL WATER
 RETENTION SHOWN SO A EXTERNAL HARTFORD
 LOOP WILL BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-15 Time 16:47 Rev Time 0.00
Received By mmclean Date   Time   Sent To P
Notes
***NONE***