Plan Review Details - Permit 03100564
Plan Review Stops For Permit 03100564
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-10 Cont ID  
Sent By jleech Date 2003-12-10 Time 17:11 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To P
Notes
2003-12-10 00:00:00DENIED
  
 1) SUBMIT THE SUBSURFACE SOIL REPORT FOR
 THE PROJECT SIGNED AND SEALED BY THE
 SOIL ENGINEER, SEE FBC 1804.2.2 AS
 AMENDED BY THE CITY OF WPB.
  
 2) PLANS WERE SUBMITTED FOR BOTH A RIGHT
 AND LEFT MODEL. SUBMIT ENERGY CALCS. FOR
 BOTH MODELS.
  
 3) PLEASE REVISE THE GLASS BLOCK
 INSTALLATION DETAIL ON SHEET 2 TO
 COMPLY WITH MANUFACTURER'S INSTALLATION
 FOR ONE HOUR FIRE RATED GLASS BLOCK.
  
 4) THE DIMENSIONS FOR THE FIXED GLASS
 TRANSOM ABOVE THE FRONT DOOR ARE
 REVERSED. PLEASE CORRECT.
  
 5) REVISE THE FASTENING NOTE FOR THE
 HIGH RIB METAL LATH ON THE CEILING AT
 THE REAR PORCH SECTION ON SHEET 4. THE
 FASTENERS ARE REQUIRED TO PENETRATE THE
 FRAMING A MINIMUM OF 1-3/4", THEREFORE,
 A 2" NAIL WOULD BE REQUIRED. SEE ASTM C
 1063.
  
 6) THE PRODUCT APPROVALS FOR THE
 BENCHMARK DOOR IS PENDING STATE APPROVAL
 A LOCAL PRODUCT APPROVAL FORM FROM THE
 CITY OF WPB IS REQUIRED ALONG WITH THE
 METRO-DADE NOA.
  
 7) THE GLASS BLOCK WILL REQUIRE CITY
 PRODUCT APPROVAL FORM WITH A MIAMI-DADE
 NOA.
  
 8) WRONG STATE PRODUCT APPROVAL COVER
 SHEET WAS SUBMITTED FOR THE ALL AMERICAN
 SHUTTERS.
  
 9) SUBMIT THE APPROPRIATE STATE COVER
 SHEETS LISTING THE SPECIFIC WINDOW AND
 DOOR MODELS THAT WILL BE INSTALLED IN
 THE STRUCTURE. PROVIDE THE APPROPRIATE
 INSTALLATION INFORMATION, LIMITATIONS,
 TEST INFORMATION AS REQUIRED BY RULE 9B-
 72.
  
 10) SUBMIT THE APPROPRIATE CITY FORM
 AND THE INFORMATION REQUIRED FOR
 EVALUATION REPORT SUBMITTALS FOR LOCAL
 PRODUCT APPROVAL,PER RULE 9B-72.040(5)
 FOR THE COLLIER GARAGE DOORS.
  
 11) TRUSSES: THE WRONG CODE INFORMATION
 IS LISTED ON THE TRUSS DRAWINGS. CHANGE
 SBC TO FBC. PROVIDE TRUSS LAYOUTS FOR
 BOTH THE RIGHT AND LEFT MODELS. THE
 TRUSS LAYOUT IS TO BE SIGNED AND SEALED
 BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD AND
 SO NOTED ON THE DRAWINGS. THE BOTTOM
 CORD LIVE LOAD IS LISTED ON THE TRUSS
 DRAWINGS AND LAYOUT AS 0. THE FBC
 REQUIRES A 10 PSF BOTTOM CORD LIVE LOAD
 FOR ATTICS WITHOUT STORAGE. SEE FBC
 TABLE 1604.1.
  
 12) THE UPLIFTS FOR TRUSSES GRE-DH AND
 GRC EXCEED THE UPLIFTS OF THE SPECIFIED
 TRUSS CONNECTORS. PLEASE REVISE. THE
 CENTER POINT BEARING UPLIFT IS 3587# FOR
 GRE-DH AND 1202# AT BEARING PT. 10 OF
 GRC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-30 Cont ID  
Sent By rmcdouga Date 2003-10-30 Time 16:42 Rev Time 4.00
Received By rmcdouga Date 2003-10-30 Time 07:18 Sent To P
Notes
2003-10-30 00:00:00DENIED
  
 1) SUBMIT THE SUBSURFACE SOIL REPORT FOR
 THE PROJECT SIGNED AND SEALED BY THE
 SOIL ENGINEER. SEE FBC 1804.2.2 AS
 AMENDED BY THE CITY OF WPB.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. REQUIRED FOR EACH
 PERMIT.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
 REQUIRED FOR EACH PERMIT.
  
 4) TWO COPIES OF A SIGNED AND SEALED
 SURVEY SHOWING THE LOCATION OF STRUCTURE
 IS REQUIRED FOR EACH SUBMITTAL.
  
 5) ENERGY CALCULATIONS ARE REQUIRED TO
 BE SIGNED AND DATED BY THE OWNER/AGENT.
 THE ENERGY CALCS. SHOULD BE DONE AS
 WORST CASE. IF NOT EACH ONE WILL BE
 DIFFERENT BASED ON THE ORIENTATION OF
 THE STRUCTURE. IF WORST CASE IS
 SPECIFIED ON THE FORM THE SAME
 INFORMATION CAN BE SUBMITTED FOR EACH
 UNIT OF THE SAME MODEL.
  
 6) REVISE THE BUCK ANCHORING SPECIFIED
 UNDER #1 OF RESIDENTIAL NOTES ON SHEET 2
 TO CORRESPOND WITH THE BUCK DETAILS ON
 SHEET 4.
  
 7) PLEASE CLARIFY IF THE SPACE BETWEEN
 THE ENTRY DOOR AND THE FIXED GLASS
 TRANSOM IS TO BE A LINTEL OR STRUCTURAL
 MULLION.
  
 8) SPECIFY THE CEILING TYPE FOR THE
 FRONT AND REAR PORCHES ON THE PLANS. IF
 THEY ARE WIRE RIB LATH AND STUCCO,
 SPECIFY THAT RIB LATH WILL BE FASTENED
 AT EACH RIB (4"OC) WITH NAILS OR STAPLES
 THAT PROVIDE AT LEAST 1-3/4" PENETRATION
 INTO THE VERTICAL FRAMING MEMBERS.
  
 9) PRODUCT APPROVALS SUBMITTED AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL SYSTEM
 FOR INFORMATION SEE THE STATE WEB SITE
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET WHICH LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE (SEE SAMPLE ATTACHED). IF THE
 PRODUCT DOES NOT HAVE STATEWIDE APPROVAL
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL PER RULE 9B-72.
  
 10)INDICATE THE MOUNT TYPE AND ANCHOR
 TYPE THAT WILL BE USED FOR THE STORM
 PANELS. CIRCLE OR HIGHLIGHT THE
 APPROPRIATE ITEMS ON THE APPROVED STORM
 PANEL DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By dpalmer Date 2003-12-04 Time 09:07 Rev Time 0.50
Received By dpalmer Date 2003-12-04 Time 15:34 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-12-01 Time 09:19 Rev Time 0.33
Received By dpalmer Date 2003-10-20 Time 16:30 Sent To M
Notes
2003-10-20 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE THAT TWO SETS OF
 ELECTRICAL PLANS WERE SUBMITTED FOR
 REVIEW UNDER THIS MASTER.
 APPEARS TO BE A LEFT HAND AND A RIGHT
 HAND.
 IT IS MY UNDERSTANDING THAT IN ORDER TO
 BE A MASTER, YOU WOULD HAVE TO HAVE LEFT
 MODEL COME IN SEPARATE FROM RH MODEL.
  
 2)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
  
 3)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT(S) IN LIVING RM? AND MIDDLE BED-
 -ROOM.
  
 4)NOTE: PLEASE SEE NOTE ABOVE PANEL
 SCHEDULE. MENTIONS TO HAVE ALL BEDROOM
 AND DEN RECEPTS CON TO ARC FAULT BRKRS.
 PLEASE SEE THAT AS OF 7/1/2003 WE ARE
 NOW UNDER THE 2002 NEC AND THE REQ'MENT
 FOR ARC FAULT PROTECTION HAS EXTENDED TO
 ALL OUTLETS, INCLUDING, SD'S, LTS ETC.
 220.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 09:19 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 09:19 Sent To E
Notes
2003-12-01 00:00:00TO DP DESK/DRAWING REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 15:51 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 15:51 Sent To  
Notes
2003-10-09 00:00:00TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-12-08 Cont ID  
Sent By pkrauss Date 2003-12-08 Time 08:04 Rev Time 0.45
Received By pkrauss Date 2003-12-08 Time 08:04 Sent To P
Notes
2003-12-08 00:00:00PLAN CHECK - DENIED
 BOTH MODELS 1632-L & 1632-R, RETURN AIR
 JUMPER FROM THE MASTER BEDROOM NOT SIZED
 PROPERLY.PER REVISED 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30, 2003, TRANSFER DUCTS
 (JUMPERS) SHALL BE 1 1/2 TIMES THE TOTAL
 SUPPLY AIR TO THE MASTER BEDROOM.THE
 DOOR SHALL HAVE A 1" CLEAR UNDERCUT.
 SEE ATTACHED AND REVISE PLANS
 ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-22 Cont ID  
Sent By dpalmer Date 2003-12-04 Time 16:19 Rev Time 0.25
Received By pkrauss Date 2003-10-22 Time 07:49 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-10 Cont ID  
Sent By jleech Date 2003-12-10 Time 17:11 Rev Time 0.50
Received By jleech Date 2003-12-10 Time 17:11 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-11-01 Cont ID  
Sent By rmcdouga Date 2003-12-10 Time 11:59 Rev Time 0.50
Received By kstevens Date 2003-11-01 Time 06:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2003-10-31 Cont ID  
Sent By rmcdouga Date 2003-10-31 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2003-10-31 Time 13:06 Sent To  
Notes
***NONE***