Plan Review Details - Permit 03100551
Plan Review Stops For Permit 03100551
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-06-21 Cont ID  
Sent By shill Date 2004-06-21 Time 14:33 Rev Time 0.50
Received By shill Date 2004-06-21 Time 14:33 Sent To  
Notes
2004-06-21 00:00:00REV 5/5

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-05-14 Cont ID  
Sent By btrobaug Date 2004-06-17 Time 08:05 Rev Time 1.00
Received By shill Date 2004-05-14 Time 09:22 Sent To  
Notes
2004-05-14 00:00:00FL STATE PA FOR WINDOW PUT IN PACKAGE
 REVISION DATED 5/5/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-01-12 Cont ID  
Sent By btrobaug Date 2004-05-11 Time 14:57 Rev Time 1.00
Received By shill Date 2004-01-12 Time 12:48 Sent To  
Notes
2004-01-12 00:00:00***PROVISO***
  
 SUBMIT STATEWIDE OR SITE SPECIFIC
 PA FOR WINDOW (TRACO) BEFORE INSTALLATIO
  
 SUBMIT REVISION WITH ENGINEER'S TITLE
 BLOCK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-01-02 Cont ID  
Sent By csiegber Date 2004-01-12 Time 09:56 Rev Time 1.00
Received By shill Date 2004-01-02 Time 18:40 Sent To  
Notes
2004-01-02 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE SURVEY DOESN'T MATCH THE PLAN.
 THE SURVEY SHOWS A 20' EDGE OF THE EXIST
 BUILDING, YOUR PLAN SHOWS A 24' EXISTING
 BUILDING.NOTE THAT THERE IS A 4' WOOD
 SHED ON THE END THAT YOU ARE ADDING ON
 TO.THIS IS THE 3RD TIME FOR THIS
 CORRECTION.IF YOU DO NOT UNDERSTAND
 THIS COMMENT, PLEASE CALL ME FOR AN
 APPOINTMENT.
  
 2.)SEE THE PREVIOUS LISTS.THE
 ENGINEER AUTHORIZATION NUMBER FOR
 SJE DESIGN & CONSTRUCTION IS DELINQUENT
 AND HAS BEEN DELINQUENT SINCE 2/03.
 PRACTICING ENGINEERING WITH A DELINQUENT
 LICENSE IS SUBJECT TO DISCIPLINARY
 ACTION.
  
 3.)THIS PERMIT WILL BE ISSUED WITH A
 PROVISO THAT EITHER STATEWIDE OR SITE
 SPECIFIC PRODUCT APPROVALS BE SUBMITTED
 FOR THE TRACO WINDOW BEFORE INSTALLATION
  
 4.)PROVIDE A SECOND COPY OF THE
 MULLION PRODUCT APPROVAL.
  
 5.)ADDITIONAL FEES (RADON), $5.76,
 SEE ATTACHED BZ235297.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-31 Time 13:50 Rev Time 1.00
Received By shill Date 2003-12-16 Time 11:50 Sent To  
Notes
2003-12-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)SEE PREVIOUS LIST, ITEM #3. PROVIDE
 AREA CALCULATIONS ON THE PLAN.EXISTING
 WAS NOT PROVIDED.BE SURE THAT THE
 AREAS MATCH THE ENERGY CALCS.ADDITIONS
 OF OVER 25% ARE TO COMPLY WITH FBC
 3401.7.2, 2003 AMENDMENT.
  
 4.)THE DIMENSIONS ON THE PLAN ARE
 24X24, PLANS CALL IT A 441 SF ADDITION,
 IMPACT FEE STAMP IS FOR 551 SF.TOTAL
 ADDITION AREA IS STILL NOT CLEAR.
  
 5.)SEE PREVIOUS LIST, ITEM #4.THE
 SURVEY DOES NOT MATCH THE PLAN.
  
 6.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC13-103.1.2.
  
 7.)SEE PREVIOUS LIST, ITEM #6.NOTES
 IN INK ARE TO BE INITIALED BY THE
 ENGINEER.
  
 8.)SEE PREVIOUS LIST, ITEM #8,
 CITY OF WEST PALM BEACH AMENDMENTS TO
 THE FBC1804.1.7, LOWEST BUILDING FLOOR
 ELEVATION AT THE PERIMETER OF A
 MONOLOTHIC FOUNDATION AT HABITABLE
 AREAS SHALL BE A MINIMUM OF 4" ABOVE THE
 FINISHED GRADE.SHOW ON WALL SECTION.
  
 9.)SEE PREVIOUS LIST, ITEM #11,
 ADDITIONAL FEES MAY BE DUE, TO BE
 CALCULATED AFTER THE SQUARE FOOTAGE OF
 THE ADDITION IS DETERMINED.
  
 10.)SEE PREVIOUS LIST, ITEM#14,
 A TITLE BLOCK FOR THE ENGINEER IS
 REQUIRED, FAC61G15-23.001.SJE DESIGN
 & CONSTRUCTION HAS A DELINQUENT
 GENERAL CONTRACTOR LICENSE AND
 ENGINEERING AUTHORIZATION NUMBER.
 BOTH NUMBERS ARE REQUIRED TO BE ON THE
 TITLE BLOCK.ADDRESS.
  
 11.)SEE PREVIOUS LIST, ITEM #16.A
 STATEWIDE OR SITE SPECIFIC PRODUCT
 APPROVAL IS REQUIRED IN ADDITION TO
 THE DADE COUNTY NOAS PROVIDED; SEE
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.
  
 12.)SEE PREVIOUS LIST, ITEM #17,
 SHOW COMPLIANCE WITH EGRESS REQUIREMENTS
 BY GIVING WINDOW SIZE AND TYPE ON THE
 PLAN.A 24X20 OPENING DOES NOT COMPLY.
  
 13.)SEE PREVIOUS LIST, ITEMS #18 AND
 21.IF A HURRICANE SHUTTER INSTALLATION
 SCHEDULE IS NOT PROVIDED, A SEPARATE
 PERMIT WILL BE REQUIRED.
  
 14.)SEE ATTACHED NOTICE IN REGARDS TO
 FS553.80(2)(B).A 4X FEE WILL BE
 CHARGED IF ITEMS ARE NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-30 Cont ID  
Sent By btrobaug Date 2003-12-02 Time 11:02 Rev Time 1.50
Received By sthyng Date 2003-10-30 Time 09:36 Sent To  
Notes
2003-10-30 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)PROVIDE AREA CALCULATIONS ON THE
 PLAN.ADDITIONS OF OVER 25% MUST COMPLY
 WITH FBC3401.7.2, 2003 AMENDMENT.
  
 4.)THE FLOOR PLAN OVERALL DIMENSION
 HAS BEEN WRITTEN OVER AND IS NOT CLEAR
 AND DOES NOT APPEAR TO MATCH THE SURVEY.
 THE DIMENSIONS MUST ADD UP TO THE TOTAL,
 AND MUST BE THE SAME AS THE SITE PLAN.
  
 5.)ENERGY CALCS, SIGNED BY BOTH THE
 PREPARER AND THE OWNER/AGENT, ARE
 REQUIRED FBC13-103.1.2.
  
 6.)THERE ARE MANY NOTES IN INK ON THE
 PLAN.THE NOTES MUST BE INITIALED BY
 THE DESIGNER OF RECORD.
  
 7.)NOTE THAT ON THE WALL SECTION YOU
 HAVE SPECIFIED R19 UNDER ATTIC, 4.2 ON
 THE WALL.IF A 600C ENERGY CALC IS
 SUMBITTED THE MINIMUM INSULATION
 REQUIRED WOULD BE R30 AND R5
 RESPECTIVELY.
  
 8.)CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC1804.1.7, LOWEST BUILDING
 FLOOR ELEVATION AT THE PERIMITER OF
 A MONOLITHIC FOUNDATION AT HABITABLE
 AREAS SHALL BE A MINIMUM OF 4" ABOVE THE
 FINISHED GRADE.SHOW ON WALL SECTION.
  
 9.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 10.) TWO COPIES OF ALL DOCUMENTS MUST
 BE SUBMITTED.ONE WILL BE RETAINED AT
 THE CITY AND ONE WILL BE YOUR PERMIT
 SET.
  
 11.) ADDITIONAL FEES MAY BE DUE.THESE
 FEES WILL BE DETERMINED AFTER AREA
 CALCULATIONS ARE SUBMITTED ON THE PLAN.
  
 12.) THIS JOB IS A SUBSTANTIAL
 IMPROVEMENT TO A RESIDENCE LOCATED IN A
 FLOOD ZONE. CITY OF WEST PALM BEACH
 MUNICIPAL CODE REQUIRES THAT THE
 LOWEST FLOOR BE ELEVATED TO 6" ABOVE THE
 BASE FLOOD ELEVATION, 94-546.PROVIDE
 AN ELEVATION CERTIFICATE FOR THE
 EXISTING HOUSE AND SHOW COMPLIANCE ON
 THE PLAN.
  
 13.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 14.)A TITLE BLOCK FOR THE ENGINEER
 IS REQUIRED, FAC61G15-23.001.
  
 15.)GABLE ENDS ARE TO BE STRUCTURALLY
 CONTINUOUS, FBC2117.1.
  
 16.)A STATEWIDE OR LOCAL PRODUCT
 APPROVAL IS REQUIRED FOR WINDOWS, DOORS,
 TRUSS ANCHORS AND IMPACT PROTECTION,
 FAC9B-72.SEE THE DCA WEBSITE,
 WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/
 PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM
 FOR MORE INFORMATION.
  
 17.)THERE IS A NOTE ON THE PLAN TO
 "MAKE EXIST WINDOW COMPLY W/EGRESS".
 SHOW HOW THIS COMPLIES WITH FBC1005.4
 BY GIVING THE WINDOW SIZE AND TYPE.
  
 18.)IMPACT PROTECTION REQUIRED FBC
 1606.1.4.
  
 19.)THERE IS A REFERENCE TO SBC (NOTE
 AT THE WALL SECTION); CURRENT CODE IS
 FBC.
  
 20.)ATTIC ACCESS REQUIRED TO COMPLY
 WITH FBC2309.
  
 21.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE IF SHUTTERS ARE TO
 BE USED, SEE ATTACHED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-06-17 Cont ID  
Sent By btrobaug Date 2004-06-17 Time 08:03 Rev Time 0.50
Received By btrobaug Date 2004-06-17 Time 07:33 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-14 Cont ID  
Sent By btrobaug Date 2004-05-11 Time 14:57 Rev Time 0.66
Received By msmith Date 2004-05-11 Time 14:52 Sent To B
Notes
2004-05-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} ADD EGRESS LIGHTING TO COMPLY WITH
 210.70(A)(2)(B), AS REDLINED ON PERMIT
 SET.
  
 2} THERE ARENO RECEPTACLES IN THE ROOM
 WITH NO DESIGNATION IN THE SOUTH EAST
 CORNER OF THE ADDITION. MUST COMPLY
 WITH 210.52(ALL).
  
 3} THE RECEPTACLE SPACING IN THE NEW
 BEDROOM DOES NOT COMPLY WITH 210.52.
  
 4} SUPPLY A LOAD CALCULATION PER 215.5.
 USE 220.3 OR 220.31 FOR CALCS, INDICATE
 THE ONE USED.
  
 5} INDICATE THE SIZE OF THE EXISTING
 SERVICE.
  
 6} THE FRAMING PLAN DOES NOT CORRELATE
 WITH THE FLOOR PLAN. CHANGE TO INDICATE
 ACTUAL CONDITIONS.
  
 7} RECEPTACLE SPACING IN THE FAMILY ROOM
 MUST COMPLY WITH 210.52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-02 Cont ID  
Sent By csiegber Date 2004-05-11 Time 08:39 Rev Time 0.33
Received By btrobaug Date 2003-12-02 Time 10:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-23 Cont ID  
Sent By csiegber Date 2003-12-01 Time 16:09 Rev Time 0.50
Received By btrobaug Date 2003-10-23 Time 09:37 Sent To B
Notes
2003-10-23 00:00:00FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY AN
 ENGINEER ARE REQ`D PER 61G15-23.002
 TO HAVE A TITLE BLOCK.THIS AND
 SIMILAR COMMENTS, MADE REPEATEDLY,
 REGADING NON COMPLIANCE WITH ART 471 FS.
 STATUTES HAVE COMPELLED US TO START
 RETAINING ONE SET OF PLANS TO BE FILED
 AND TURNED INTO THE FPBE FOR SAID
 VIOLATIONS.
  
 2} PLEASE SHOW COMPLIANCE PER
 210.70(A)(1),IN THE NEW FAMILY ROOM.
  
 3} PLEASE NOTE ON THE PLANS COMPLIANCE
 WITH ARTICLE 210.12 NEC,FOR THE
 BEDROOMS.
  
 4} THE BEDROOMS NEED TO HAVE RECEPTACLES
 ADDED PER 210.52(A)(1) & (2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-11 Time 08:31 Rev Time 0.00
Received By csiegber Date 2004-05-11 Time 08:30 Sent To E
Notes
2004-05-11 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-12 Time 09:56 Rev Time 0.00
Received By csiegber Date 2004-01-12 Time 09:56 Sent To B
Notes
2004-01-12 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-31 Cont ID  
Sent By csiegber Date 2003-12-31 Time 13:50 Rev Time 0.00
Received By csiegber Date 2003-12-31 Time 13:50 Sent To B
Notes
2003-12-31 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 16:09 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 16:09 Sent To E
Notes
2003-12-01 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-10 Cont ID  
Sent By csiegber Date 2003-10-10 Time 15:51 Rev Time 0.00
Received By csiegber Date 2003-10-10 Time 15:51 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-10 Cont ID  
Sent By mmclean Date 2003-10-10 Time 15:23 Rev Time 0.00
Received By csiegber Date   Time   Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 10:21 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 10:21 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-10-10 Cont ID  
Sent By mmclean Date 2003-10-10 Time 15:23 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-10 Time 10:25 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-10-09 00:00:0010/9/03 DENIED, NEED TO SHOW WORK ON
 SURVEY CALLED CONTR FILE T MM