Plan Review Details - Permit 03100543
Plan Review Stops For Permit 03100543
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By btrobaug Date 2003-11-24 Time 16:07 Rev Time 1.00
Received By btrobaug Date 2003-11-24 Time 16:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2003-10-14 Time 19:54 Rev Time 0.75
Received By dpalmer Date 2003-10-14 Time 19:45 Sent To  
Notes
2003-10-14 00:00:00******** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE PLANS SUBMITTED
 FOR REVIEW AND PERMITTING.
 ONE SET FROM ARCH MENTIONS ; SERVICE TO
 FEED SPORTS LIGHTING? YET, E-PLANS
 SUBMITTED BY ENGINEER SHOWS A COMPLETELY
 DIFFERENT SERVICE AND MENTIONS THAT
 SERVICE FEDDING SPORTS LIGHTING?
 PLEASE EITHER CORRELATE PLANS OR IF
 INDEED THESE ARE TWO SEPARATE AREAS,
 PLEASE CLARIFY AND PERMIT SEPARATELY IF
 NEED BE.
  
 2)NOTE: PLEASE SEE SERVICE ONE, PLEASE
 SEE MISSING GROUNDING ELECTRODE CONDUCT-
 -OR PER 250.24/250.66 ETC?
  
 3)NOTE: PLEASE SHOW CIRCUITING AND
 CORRELATE WITH A SUBMITTED PANEL
 SCHEDULE.
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3/230.42 ETC.
  
 5)NOTE: PLEASE SEE THAT RISER MENTIONS;
 NEW METER AND PLANS MENTIONS EXIST TO
 REMAIN?
  
 6)NOTE: PLEASE SEE SERVICE #2, SHOW ALL
 CONTINUOUS LOADS AT 125%. 215.3/230.42
 ETC.
 PLEASE ALSO CLARIFY AND CORRELATE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-25 Cont ID  
Sent By nmccray Date 2003-11-25 Time 10:26 Rev Time 0.00
Received By nmccray Date 2003-11-25 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-16 Cont ID  
Sent By nmccray Date 2003-10-16 Time 14:59 Rev Time 0.00
Received By nmccray Date 2003-10-16 Time 12:38 Sent To  
Notes
2003-10-16 00:00:001) PLEASE PROVIDE AND SHOW EXIT SIGN AND
 EMERGENCY LIGHTS FOR THE PRESS BOX AND
 STAIRS.
  
 2) PLEASE PROVIDE AND SHOW EMERGENCY
 LIGHTS FOR THE RESTROOMS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 14:15 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 14:15 Sent To  
Notes
2003-10-09 00:00:00TO COMM BD#23

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-16 Cont ID  
Sent By kstevens Date 2003-10-16 Time 07:57 Rev Time 0.50
Received By kstevens Date 2003-10-16 Time 07:57 Sent To  
Notes
***NONE***