Plan Review Details - Permit 03100543
Plan Review Stops For Permit 03100543 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-11-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-11-24 |
Time |
16:07 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2003-11-24 |
Time |
16:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-10-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-10-14 |
Time |
19:54 |
Rev Time |
0.75 |
Received By |
dpalmer |
Date |
2003-10-14 |
Time |
19:45 |
Sent To |
|
|
Notes |
2003-10-14 00:00:00 | ******** UNSAT ***************** | | | | 1)NOTE: PLEASE CORRELATE PLANS SUBMITTED | | FOR REVIEW AND PERMITTING. | | ONE SET FROM ARCH MENTIONS ; SERVICE TO | | FEED SPORTS LIGHTING? YET, E-PLANS | | SUBMITTED BY ENGINEER SHOWS A COMPLETELY | | DIFFERENT SERVICE AND MENTIONS THAT | | SERVICE FEDDING SPORTS LIGHTING? | | PLEASE EITHER CORRELATE PLANS OR IF | | INDEED THESE ARE TWO SEPARATE AREAS, | | PLEASE CLARIFY AND PERMIT SEPARATELY IF | | NEED BE. | | | | 2)NOTE: PLEASE SEE SERVICE ONE, PLEASE | | SEE MISSING GROUNDING ELECTRODE CONDUCT- | | -OR PER 250.24/250.66 ETC? | | | | 3)NOTE: PLEASE SHOW CIRCUITING AND | | CORRELATE WITH A SUBMITTED PANEL | | SCHEDULE. | | | | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | AT 125%. 215.3/230.42 ETC. | | | | 5)NOTE: PLEASE SEE THAT RISER MENTIONS; | | NEW METER AND PLANS MENTIONS EXIST TO | | REMAIN? | | | | 6)NOTE: PLEASE SEE SERVICE #2, SHOW ALL | | CONTINUOUS LOADS AT 125%. 215.3/230.42 | | ETC. | | PLEASE ALSO CLARIFY AND CORRELATE? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2003-11-25 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-11-25 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-11-25 |
Time |
10:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2003-10-16 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-10-16 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-10-16 |
Time |
12:38 |
Sent To |
|
|
Notes |
2003-10-16 00:00:00 | 1) PLEASE PROVIDE AND SHOW EXIT SIGN AND | | EMERGENCY LIGHTS FOR THE PRESS BOX AND | | STAIRS. | | | | 2) PLEASE PROVIDE AND SHOW EMERGENCY | | LIGHTS FOR THE RESTROOMS. | | | | NATE MCCRAY, CAPTAIN | | 805-6722 OR 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-10-09 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-09 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-09 |
Time |
14:15 |
Sent To |
|
|
Notes |
2003-10-09 00:00:00 | TO COMM BD#23 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2003-10-16 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-10-16 |
Time |
07:57 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-10-16 |
Time |
07:57 |
Sent To |
|
|
Notes |
|
|
|