Plan Review Details - Permit 03100433
Plan Review Stops For Permit 03100433
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2005-04-27 Cont ID  
Sent By rbrown Date 2005-04-26 Time 11:23 Rev Time 0.00
Received By rbrown Date 2005-04-26 Time 11:23 Sent To  
Notes
2005-04-26 00:00:00TRUSS ENGINEERING SUBMITTAL ON 4/25/05,
 ORIGINALLY SUBMITTED 3/21/05 (INDEX
 SHEETS ORIGINALLY SUBMITTED ON 3/28/05).

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date   Cont ID  
Sent By   Date 2005-04-19 Time   Rev Time 0.00
Received By rbrown Date 2005-04-19 Time 10:38 Sent To  
Notes
2005-04-19 00:00:00STRUCTURAL SUBMITTAL FOR PRE-CAST
 SPECIALTIES, INC. LETTER DATED 3/18/05
 SUMMARIZING SLAB INSPECTION FINDINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2005-04-19 Cont ID  
Sent By rbrown Date 2005-04-19 Time 08:44 Rev Time 0.00
Received By rbrown Date 2005-04-19 Time 08:13 Sent To  
Notes
2005-04-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL ON 4/14/05 FOR
 PRE-CAST SPECIALTIES, INC. PRE-CAST
 HOLLOWCORE SLAB SHOP DRAWINGS AND
 CALCULATIONS.
  
 1) FBC 1604.1LIVE LOADS.UNDER
 'LOADING DATA', THE SUBMITTED
 CALCULATIONS STATE A LIVE LOAD OF 30 PSF
 WAS INPUT.SHEET 1, NOTE 11 STATES THE
 SAME.THE REQUIRED LIVE LOAD FOR
 DWELLINGS IS 40 PSF (30 PSF IN SLEEPING
 ROOMS ONLY).AMEND THE PLANS AND
 CALCULATIONS TO DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-04-18 Cont ID  
Sent By rbrown Date 2005-04-18 Time 12:53 Rev Time 0.00
Received By rbrown Date 2005-04-18 Time 12:48 Sent To  
Notes
2005-04-18 00:00:00ARCHITECTURAL SUBMITTAL ON 4/14/05 FOR
 ADDITIONAL SHEET A.5 NOTE STATING 'NO
 ATTIC STORAGE'

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-03-28 Cont ID  
Sent By rbrown Date 2005-03-28 Time 15:23 Rev Time 0.00
Received By rbrown Date 2005-03-28 Time 15:23 Sent To  
Notes
2005-03-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 TRUSS ENGINEERING SUBMITTAL ON 3/21/05
 AND INDEX SHEET SUBMITTED ON 3/28/05.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) COMMENT ALREADY ADDRESSED BY
 SUBMITTAL OF CALCULATION INDEX SHEETS.
 BUT, WILL NEED NEW INDEX SHEETS WHEN
 ADDRESSING COMMENTS 2 AND 3 BELOW.
  
 2) FBC 1604.1ROOF TRUSS LOADING.THE
 SUBMITTED ROOF TRUSS DESIGN CALCULATIONS
 STATE A BOTTOM CHORD LIVE LOAD OF 10PSF.
 THE REQUIRED MINIMUM BOTTOM CHORD LIVE
 LOAD FOR RESIDENTIAL ATTICS WITH STORAGE
 IS 30 PSF.AMEND THE CALCULATIONS.
  
 3) FBC 1606.1STRESS INCREASE FOR STEEL
 IS NOT ALLOWED.THE WRITERS OF THE
 MITEK SOFTWARE USED FOR DESIGN OF THE
 TRUSSES HAVE ADVISED THAT WHEN THE CODE
 IS STATED AS 'FBC2001/ANSI95' THE
 SOFTWARE USES THE STRESS INCREASE.
 AMEND THE CALCULATIONS TO SHOW
 COMPLIANCE WITH THE PROCEDURE DESCRIBED
 IN THE ATTACHED LETTER FROM MITEK.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-03-23 Cont ID  
Sent By rbrown Date 2005-03-23 Time 13:22 Rev Time 0.00
Received By rbrown Date 2005-03-23 Time 13:22 Sent To  
Notes
2005-03-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 TRUSS ENGINEERING SUBMITTAL ON 3/21/05.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 471.025 F.S.THE SUBMITTED TRUSS
 LAYOUT AND TRUSS DESIGN SHEETS EACH HAVE
 A STAMPED SIGNATURE OF ALI YEMENICILER,
 P.E.ALL PLANS/DOCUMENTS PREPARED BY A
 PROFESSIONAL ENGINEER AND BEING FILED
 FOR PUBLIC RECORD SHALL BEAR THE
 ENGINEER'S ORIGINAL SIGNATURE.THE
 ORIGINAL SIGNATURE OF THE ENGINEER IS
 REQUIRED ON THE TRUSS LAYOUT AND ON A
 CALCULATION INDEX SHEET THAT LISTS EACH
 TRUSS DESIGN SHEET.IF AN INDEX SHEET
 IS PROVIDED, EACH INDIVIDUAL TRUSS
 DESIGN SHEET DOES NOT REQUIRE A SEAL AND
 ORIGINAL SIGNATURE (REF: 61G15-31.003
 FLORIDA ADMIN. CODE).
  
 2) FBC 1604.1ROOF TRUSS LOADING.THE
 SUBMITTED ROOF TRUSS DESIGN CALCULATIONS
 STATE A BOTTOM CHORD LIVE LOAD OF 10PSF.
 THE REQUIRED MINIMUM BOTTOM CHORD LIVE
 LOAD FOR RESIDENTIAL ATTICS WITH STORAGE
 IS 30 PSF.AMEND THE CALCULATIONS.
  
 3) FBC 1606.1STRESS INCREASE FOR STEEL
 IS NOT ALLOWED.THE WRITERS OF THE
 MITEK SOFTWARE USED FOR DESIGN OF THE
 TRUSSES HAVE ADVISED THAT WHEN THE CODE
 IS STATED AS 'FBC2001/ANSI95' THE
 SOFTWARE USES THE STRESS INCREASE.
 AMEND THE CALCULATIONS TO SHOW
 COMPLIANCE WITH THE PROCEDURE DESCRIBED
 IN THE ATTACHED LETTER FROM MITEK.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-10-12 Cont ID  
Sent By csiegber Date 2004-10-19 Time 12:36 Rev Time 0.00
Received By rbrown Date 2004-10-12 Time 13:49 Sent To  
Notes
2005-04-18 00:00:00REVISION FIRST SUBMITTED 6/30/04 FOR
 ADDITION TO PERMITTED BUILDING SIZE.
 AREA WILL BE INCREASED BY 4557 SQ FT

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-09-21 Cont ID  
Sent By rbrown Date 2004-09-21 Time 17:42 Rev Time 0.00
Received By rbrown Date 2004-09-21 Time 17:42 Sent To  
Notes
2004-09-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION FIRST SUBMITTED 6/30/04 FOR
 ADDITION TO PERMITTED BUILDING SIZE.
 AREA WILL BE INCREASED BY 4557 SQ FT
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 7/21/04:
  
 2) IMPACT FEES. THE AREA OF THE BUILDING
 HAS INCREASED. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE THE REVISION CAN BE
 PERMITTED.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 FORMS.THE STATED CONDITIONED AREAS
 STILL DO NOT CORRELATE WITH THE AREAS
 STATED ON THE PLANS.
 (A) ONE FORM IS STATED TO APPLY TO BOTH
 UNITS R9 AND R8.THESE UNITS ARE NOT
 SIMILAR.SHOULD THE FORM BE TITLED
 'UNIT R7 AND R8' (WHICH ARE SIMILAR, AT
 1,670 SQFT)?
 (B) IN THAT CASE, SHOULD THE FORM
 CURRENTLY TITLED R7 ACTUALLY BE R9
 (1,817 SQFT)?
 (C) THE FORM SUBMITTED FOR R10 IS FOR A
 CONDITIONED AREA OF 1987 SQFT.THIS
 DOES NOT CORRELATE WITH THE AREA STATED
 ON THE PLANS, WHICH IS 1,422 SQFT.
 (D) THE FORM SUBMITTED FOR C5 STATES A
 "CONDITIONED FLOOR AREA" OF 1,997 SQFT.
 THE AREA STATED ON THE PLANS IS 960 SQFT
 (E) THE FORM SUBMITTED FOR C8 STATES A
 "CONDITIONED FLOOR AREA" OF 1,040 SQFT.
 THE AREA STATED ON THE PLANS IS
 1,770 SQFT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-07-21 Cont ID  
Sent By rbrown Date 2004-07-21 Time 15:51 Rev Time 0.00
Received By rbrown Date 2004-07-21 Time 11:09 Sent To  
Notes
2004-07-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 6/30/04 FOR ADDITION
 TO PERMITTED BUILDING SIZE.AREA WILL
 BE INCREASED BY 4557 SQ FT
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) PERMIT FEES.THE PERMIT AND RADON
 FEES HAVE BEEN REVISED TO REFLECT THE
 INCREASED AREA/VALUATION.THE BALANCE
 OUTSTANDING IS $3349.26
  
 2) IMPACT FEES. THE AREA OF THE BUILDING
 HAS INCREASED.THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) THE PROPOSED BUILDING STRUCTURE NOW
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 4) FBC* 104.2.4SITE SURVEY.THE SITE
 BOUNDARY HAS CHANGED. A REVISED SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 LICENSED SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES)
  
 5) ON ONE SET OF PLANS, THE RETAIL AND
 RESIDENTIAL UNIT REFERENCES HAVE BEEN
 STRUCK OUT ON STRUCTURAL PLAN SHEETS
 S1.0, S2.0 AND S3.0 BECAUSE THEY DO NOT
 CORRELATE TO THE REFERENCES ON THE
 ARCHITECTURAL PLANS.AMEND THE OTHER
 TWO SETS TO SUIT.
  
 6) FBC 13-103.0EACH COPY OF THE
 SUBMITTED ENERGY CODE COMPLIANCE FORMS
 SHALL HAVE THE CORRECT PERMIT NUMBER
 (03100433), PROJECT ADDRESS
 (1930 S DIXIE HWY), AND BUILDER NAME
 ENTERED IN THE ALLOCATED SPACES.ALSO,
 THE STATED UNIT REFERENCES (R6, R7 ETC)
 DO NOT CORRELATE CORRECTLY WITH THE
 'CONDITIONED AREAS' STATED ON THE CODE
 COMPLIANCE FORMS.SUBMIT COMPLETE AND
 CORRECT FORMS.
  
 7) FBC 13-101.1.6SHELL RETAIL UNITS.
 THE WHOLE BUILDING (INCL. FUTURE TENANT
 SPACE) SHALL BE CONSIDERED. SHELL RETAIL
 UNITS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED, AT A
 LATER DATE, TO THE ACTUAL SYSTEMS
 PROPOSED BY THE FUTURE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.SUBMIT CODE
 COMPLIANCE FORMS FOR THE RETAIL UNITS.
  
 8) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-26 Cont ID  
Sent By rbrown Date 2004-02-26 Time 08:19 Rev Time 0.00
Received By rbrown Date 2004-02-26 Time 08:19 Sent To  
Notes
2004-02-26 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FIRE SPRINKLERS TO BE INSTALLED AS PER
 FIRE SPRINKLER PERMIT # 03100535

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-16 Cont ID  
Sent By rbrown Date 2004-01-16 Time 16:54 Rev Time 0.00
Received By rbrown Date 2004-01-16 Time 09:09 Sent To  
Notes
2004-01-16 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 **BUILDING G**
 **NOTE: READ THESE COMMENTS INDIVIDUALLY
 THEY ARE NOT EXACTLY THE SAME AS THE
 COMMENTS FOR BUILDING H**
  
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 11/18/03:
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3) 61G1-16.004FL. ADMIN. CODE. SHEETS
 A.1 TO A.20 HAVE A TITLE BLOCK THE
 INCLUDES ONLY THE FIRM'S LICENSE NUMBER
 AA26000691.EACH SHEET SHALL ALSO
 INCLUDE THE PRINTED ARCHITECT'S LICENSE
 NUMBER AR0014128.THE MISSING LICENSE
 NUMBERS MAY BE HANDWRITTEN ON THE PLANS.
  
 5) FBC 13-103.1.2THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED. THE ONLY ENERGY
 CODE COMPLIANCE FORM THAT HAS BEEN
 SIGNED IS THE FIRST/TOP ONE IN EACH
 PACKAGE (I.E. RESIDENTIAL UNIT 62). NONE
 OF THE FORMS FOR THE OTHER RESIDENTIAL
 UNITS HAS BEEN SIGNED BY THE BUILDING
 OWNER, THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER.
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 13-101.1.6NO ENERGY CODE
 COMPLIANCE FORMS HAVE BEEN SUBMITTED
 FOR THE FIRST FLOOR COMMERCIAL UNITS.
 THE WHOLE BUILDING (INCL. FUTURE TENANT
 SPACE) SHALL BE CONSIDERED.SHELL
 BUILDINGS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED, AT A
 LATER DATE, TO THE ACTUAL SYSTEMS
 PROPOSED BY THE FUTURE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.
  
 11) FBC 1606.2.4SHEET S4.0, WOOD TRUSS
 CONNECTOR MARK D IS STATED AS HAVING AN
 UPLIFT CAPACITY OF 1490#.THE SIMPSON
 HETA 20 WITH 10-10DX1-1/2 NAILS HAS A
 CAPACITY OF 1240#.AMEND THE PLAN.
  
 12) PRODUCT APPROVALS
 THE PROPOSED PRODUCTS SHALL HAVE STATE-
 WIDE OR LOCAL PRODUCT APPROVAL IN
 ACCORDANCE WITH RULE 9B-72 FAC (FOR
 STATEWIDE PRODUCT APPROVAL SEE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP):
 (A) THE DOOR SCHEDULE, SHEET A.19,
 STATES THAT DOORS 5, 11 & 18 (SECOND
 FLOOR ENTRANCE DOORS TO THE RESIDENTIAL
 UNITS) ARE TO BE IMPACT RATED.THE
 SUBMITTED MIAMI-DADE PRODUCT APPROVAL
 NOA# 02-0109.03 WHICH IS FOR NON-RATED
 FIBERGLASS DOORS.SUBMIT THREE COPIES
 OF A PRODUCT APPROVAL FOR AN ALTERNATIVE
 DOOR.
 NOTE: PRINT AND ATTACH THE RELEVANT
 STATEWIDE PRODUCT APPROVAL LISTING
 REFERENCE SHEET FL### (FOR EXAMPLE, SEE
 SHEET ATTACHED TO EACH OF THE SUBMITTED
 PRODUCT APPROVALS, DURING PLAN REVIEW,
 TO EXPEDITE PERMIT ISSUE).
  
 14) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO THE BUILDING
 BEING OVER 2 STORIES IN HEIGHT.
  
 15) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 16) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-18 Cont ID  
Sent By rbrown Date 2003-11-18 Time 20:00 Rev Time 0.00
Received By rbrown Date 2003-11-18 Time 20:00 Sent To  
Notes
2003-11-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) 61G1-16.004(6) FACTHE TITLE BLOCK
 ON THE ARCHITECTURAL PLANS SHALL INCLUDE
 THE PRINTED NAME OF THE ARCHITECT
 SEALING THE DOCUMENT.
  
 4) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES)
  
 5) FBC 13-103.1.2THE SUBMITTED ENERGY
 CODE COMPLIANCE FORMS FOR THE
 RESIDENTIAL UNITS SHALL BE SIGNED BY THE
 BUILDING OWNER, OWNER'S ARCHITECT OR
 OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.
  
 6) FBC 13-101.1.6NO ENERGY CODE
 COMPLIANCE FORMS HAVE BEEN SUBMITTED
 FOR THE FIRST FLOOR COMMERCIAL UNITS.
 THE WHOLE BUILDING (INCL. FUTURE TENANT
 SPACE) SHALL BE CONSIDERED.SHELL
 BUILDINGS SHALL BE SHOWN TO COMPLY WITH
 METHOD B (SEE SUB-CHAPTER 4).ALL
 ASSUMPTIONS MADE ABOUT SYSTEMS, NOT
 SHOWN ON THE CURRENT PLANS, SHALL BE
 LISTED AND APPENDED TO THE FORM 400B FOR
 SUBMITTAL.THIS WILL BE COMPARED TO THE
 ACTUAL SYSTEMS PROPOSED, AT A LATER, FOR
 INSTALLATION BY THE TENANT(S).THE
 ASSUMPTIONS LISTED ON THE APPENDIX SHEET
 SHALL BE AT LEAST THE MINIMUM STANDARD
 (LIGHTING, HVAC ETC) TO ALLOW THE WHOLE
 BUILDING TO BE OCCUPIED FOR IT'S
 INTENDED PURPOSE.
  
 7) FBC* F102.2.4ROOF COVERING IN THE
 FIRE DISTRICT.ANNOTATE THE PLANS TO
 SPECIFY FIRE BARRIER BOARD AND AN
 APPROPRIATE UNDERLAYMENT TO ACHIEVE THE
 REQUIRED CLASS A OR B RATING.
  
 8) FBC* F102.2.7ARCHITECTURAL TRIM ON
 BUILDINGS IN THE FIRE DISTRICT SHALL BE
 CONSTRUCTED OF APPROVED NON-COMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD.THE ELEVATIONS SHOW P.T. CEDAR
 WOOD SHAKE SIDING AND FASCIA, DECORATIVE
 WOOD TRELLIS MEMBERS AND OUTRIGGERS, AND
 WOOD BEAMS.AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 9) FBC*F102.2.8THE CANVAS AWNING
 SUPPORTS SHALL BE OF NON-COMBUSTIBLE
 MATERIALS AND THE COVERING SHALL BE
 FLAME RESISTANT AS DETERMINED IN
 ACCORDANCE WITH FBC 3103.1.AMEND THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 10) FBC 1604.1SHEET S0.2,
 PRE-ENGINEERED WOOD TRUSSES NOTE 4.THE
 TRUSSES SHALL BE DESIGNED FOR A BOTTOM
 CHORD LIVE LOAD NOT LESS THAN 10 PSF
 (RESIDENTIAL ATTICS WITHOUT STORAGE).
 ANNOTATE THE PLANS TO COMPLY.
  
 11) FBC 1606.2.4SHEET S4.0, WOOD TRUSS
 CONNECTION MARK B AND C (DOUBLE ANCHORS)
 ARE STATED AS HAVING TWICE THE UPLIFT
 CAPACITY OF A SINGLE ANCHOR.THIS IS
 NOT CORRECT FOR EMBEDDED ANCHORS SUCH
 HETA & HHETA BECAUSE THE FAILURE MODE IS
 INFLUENCED BY OVERLAPPING OF THE
 CONCRETE 'PULL-OUT CONES' FOR THE TWO
 ANCHORS (SEE 2003 SIMPSON CATALOGUE).
 AMEND THE SCHEDULE.
  
 12) PRODUCT APPROVALS
 THE PROPOSED PRODUCTS SHALL HAVE STATE-
 WIDE OR LOCAL PRODUCT APPROVAL IN
 ACCORDANCE WITH RULE 9B-72 FAC (FOR
 STATEWIDE PRODUCT APPROVAL SEE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP):
 (A) THE SECOND FLOOR ENTRANCE DOORS TO
 THE RESIDENTIAL UNITS ARE SPECIFIED ON
 THE DOOR SCHEDULE AS HOLLOW METAL.THIS
 DOES NOT CORRELATE WITH THE SUBMITTED
 PRODUCT APPROVAL NOA# 02-0109.03 WHICH
 IS FOR FIBERGLASS DOORS.AMEND THE DOOR
 SCHEDULE OR SUBMIT A RELEVANT DOOR
 PRODUCT APPROVAL.
 (B) THE SUBMITTED ALUMINUM FRENCH DOOR
 PRODUCT APPROVAL NOA# 02-0701.12 DOES
 CORRELATE WITH A STATEWIDE PRODUCT
 APPROVAL (#FL253) BUT IT IS A POOR COPY
 AND IS ALSO MISSING DRAWING SHEET
 2 OF 4.SUBMIT TWO LEGIBLE COPIES OF A
 COMPLETE PRODUCT APPROVAL.
 (C) THE SUBMITTED KAWNEER STOREFRONT
 DOOR PRODUCT APPROVAL NOA# 02-0523.05
 DOES CORRELATE WITH A STATEWIDE PRODUCT
 APPROVAL (#FL629) BUT IT IS A POOR COPY.
 SUBMIT TWO LEGIBLE COPIES OF THE PRODUCT
 APPROVAL.
 (D) THE SUBMITTED KAWNEER WINDOW WALL
 PRODUCT APPROVAL NOA# 02-0220.01 DOES
 CORRELATE WITH A STATEWIDE PRODUCT
 APPROVAL (FL#627) BUT ONLY ONE COPY WAS
 SUBMITTED BETWEEN BUILDINGS G & H.
 SUBMIT NOT LESS THAN TWO COPIES PER
 BUILDING.
 (E) THE SUBMITTED PGT INDUSTRIES
 ALUMINUM SINGLE HUNG WINDOW
 NOA# 02-0419.13 DOES CORRELATE WITH A
 STATEWIDE PRODUCT APPROVAL (#FL239) BUT
 ONLY ONE COPY WAS SUBMITTED BETWEEN
 BUILDINGS G & H.SUBMIT NOT LESS THAN
 TWO COPIES PER BUILDING.
 (F) THE SUBMITTED PGT INDUSTRIES
 ALUMINUM FIXED WINDOW NOA# 02-0806.04
 DOES CORRELATE WITH A STATEWIDE PRODUCT
 APPROVAL (#FL243) BUT THIS PRODUCT HAS
 NO IMPACT RATING SO SHUTTERS WILL BE
 REQUIRED.ALSO ONLY ONE COPY WAS
 SUBMITTED BETWEEN BUILDINGS G & H.
 SUBMIT NOT LESS THAN TWO COPIES PER
 BUILDING AND SUBMIT A CORRESPONDING
 PRODUCT APPROVAL FOR THE PROPOSED
 SHUTTERS OR IMPACT RATED FIXED WINDOWS.
 (G) SUBMIT AT LEAST TWO COPIES OF A
 PRODUCT APPROVAL FOR IMPACT RATED
 MULLIONS TO SUIT THOSE WINDOW
 CONFIGURATIONS WHICH REQUIRE WINDOWS TO
 BE MULLED TOGETHER.
 (H) THE SUBMITTED MBCI 5V CRIMP PANEL
 PRODUCT APPROVAL NOA# 02-0628.02 DOES
 NOT CORRELATE WITH ANY STATEWIDE PRODUCT
 APPROVAL.SPECIFY A PRODUCT THAT HAS
 STATEWIDE OR LOCAL PRODUCT APPROVAL.
 (I) THE SUBMITTED ELK CORP. VERSASHIELD
 UNDERLAYMENT PRODUCT APPROVAL
 NOA# 02-0327.03 DOES NOT CORRELATE WITH
 ANY STATEWIDE PRODUCT APPROVAL.SPECIFY
 A PRODUCT THAT HAS A STATEWIDE PRODUCT
 APPROVAL.
 (J) NOTE:
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS/SIZES ARE TO
 BE USED.
 (K) NOTE:
 STATEWIDE PRODUCT APPROVAL STATUS CAN
 BE CHECKED AT THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 13) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-11-15 Cont ID  
Sent By dpalmer Date 2005-11-15 Time 10:46 Rev Time 1.00
Received By dpalmer Date 2005-11-15 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-10-22 Cont ID  
Sent By dpalmer Date 2004-10-22 Time 11:49 Rev Time 0.50
Received By dpalmer Date 2004-10-22 Time 11:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-08-25 Cont ID  
Sent By dpalmer Date 2004-08-25 Time 10:08 Rev Time 0.33
Received By dpalmer Date 2004-08-25 Time 10:08 Sent To  
Notes
2004-08-25 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE SHEETS E-1, AND E-5
 STILL NEED TO BE SIGNED BY THE ENGINEER
 WITH FULL SIGNATURE.
 FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-07-13 Cont ID  
Sent By dpalmer Date 2004-07-13 Time 10:18 Rev Time 1.50
Received By dpalmer Date 2004-07-13 Time 09:40 Sent To  
Notes
2004-07-13 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED BY
 ENGINEER WITH FULL LEGAL SIGNATURE AS
 SHOWN ON ORIGINAL PLANS FILE WITH ORIG-
 -INAL PLANS AND PERMIT.
 FS 471.025
  
 2)NOTE: PLEASE CORRELATE RISER AND UNITS
 SHOWN ON PLANS ALONG WITH LOAD CALCULAT-
 -IONS.PLEASE ALSO CORRELATE WITH PANEL
 SCHEDULES.
 SOME UNITS DO NOT MATCH.
  
 3)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS ALONG 2' OF WALL SPACE.
  
 4)NOTE: PLEASE SEE FBC 104.6.5 FOR
 INCREASE OF VALUE FOR PERMIT. PLEASE SEE
 BUILDING PLAN REVIEW COMMENTS FOR THIS.
 DUE TO INCREASE OF AREA OF BLDG TO
 INCLUDE ALL TRADES.
  
 5)NOTE: PLEASE SEE POSSIBLE MISPRINT IN
 LOAD CALCS FOR "DETAIL UNITS". SHOULD
 READ RETAIL UNITS. THIS IS ONLY A NOTE.
  
 6 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 NOTED ON PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE SET
 -S FOR REVIEW AND STAMPING.
 PLEASE SEE ONE SET HAS SOME ITEMS
 REDLINED FOR AREAS OF ABOVE COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-02-18 Cont ID  
Sent By dpalmer Date 2004-02-18 Time 17:06 Rev Time 1.00
Received By dpalmer Date 2004-02-18 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-07 Cont ID  
Sent By dpalmer Date 2004-01-07 Time 16:33 Rev Time 2.00
Received By dpalmer Date 2004-01-07 Time 16:29 Sent To  
Notes
2004-01-07 00:00:00*********** UNSAT ****************
  
 BLDG "G"
  
 1)NOTE: PLEASE SEE NOTE FOR MAIN AND
 SERVICE ENT CONDUCTORS. PLEASE SEE COND
 ARE RATED FOR 670A'S AND NOTHING TO
 LIMIT LOAD FOR SERVICE. OCP ADDS UP TO
 910A'S. PLEASE SEE 230.42B
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 06:45 Rev Time 1.50
Received By dpalmer Date 2003-11-03 Time 06:45 Sent To  
Notes
2003-11-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT WE ARE NOW UNDER
 THE 2002 NEC. PLEASE ADJUST PLANS.
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AND COMMENTS FROM OTHER REVIEWERS THAT
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 3)NOTE: PLEASE SEE 210.62 FOR "SHOW "
 WINDOW RECEPTS REQ'D.
  
 4)NOTE: PLEASE SEE 2002 NEC FOR CHANGES
 IN ARC FAULT PROTECTION. PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 240.4C. DEVICES
 RATED OVER 800A'S. SEC'S CONDUCTORS
 MUST MEEET OR EXCEED RATING OF MAIN.
 CONDUCTORS SHOWN ARE RATED FOR A TOTAL
 OF 930A'S.310.16
  
 6)NOTE: PLEASE SIZE GEC TO FOOTER STEEL
 PER 250.66. PER 250.50
  
 7)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF LTS, SEEE FIRE REVIEW COMMENTS.
  
 8)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3, 230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2005-12-08 Cont ID  
Sent By mamini Date 2005-12-08 Time 08:19 Rev Time 0.50
Received By mamini Date 2005-12-08 Time 08:19 Sent To  
Notes
2005-12-08 00:00:00PASSED:
  
 1. REVIEWED FOR THE REVISION SHEET A.1,
 SIDEWALK CONNECTING TO S. DIXIE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-08-25 Cont ID  
Sent By mamini Date 2004-08-25 Time 09:55 Rev Time 0.50
Received By mamini Date 2004-08-25 Time 09:55 Sent To  
Notes
2004-08-25 00:00:00PASSED:
 1. REVISION TO CIVIL/SITE PLANS DUE TO
 CHANGES / ADDITIONS SUBMITTED, SEE #
 01031264.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2004-07-21 Cont ID  
Sent By mamini Date 2004-07-21 Time 16:26 Rev Time 0.50
Received By mamini Date 2004-07-21 Time 16:26 Sent To  
Notes
2004-07-21 00:00:00FAILED:
 1. MUST SUBMIT REVISIONS TO CIVIL/SITE
 PLANS DUE TO THE PROPOSED CHANGES/
 ADDITION, PERMIT # 01031264.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-11-04 Cont ID  
Sent By mamini Date 2003-11-04 Time 09:46 Rev Time 0.50
Received By mamini Date 2003-11-04 Time 09:45 Sent To  
Notes
2004-07-21 00:00:00PASSED:
 1. SEE PERMIT # 01031264 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-09-21 Cont ID  
Sent By nmccray Date 2004-09-21 Time 14:30 Rev Time 0.00
Received By nmccray Date 2004-09-21 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-07-14 Cont ID  
Sent By nmccray Date 2004-07-14 Time 16:17 Rev Time 0.00
Received By nmccray Date 2004-07-14 Time 16:17 Sent To  
Notes
2004-07-14 00:00:00REVISION DATED 6-22-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-10 Cont ID  
Sent By mcarsill Date 2004-02-10 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2004-02-10 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-31 Cont ID  
Sent By mcarsill Date 2003-10-31 Time 15:51 Rev Time 0.00
Received By mcarsill Date 2003-10-31 Time 15:51 Sent To  
Notes
2003-10-31 00:00:001) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS. BUILDINGS ARE REQUIRED
 TO BE FIRE SPRINKLER PROTECTED PER
 FS 553.895(2).
  
 2) PLANS DO NOT DISPLAY ANY FIRE ALARM
 EQUIPMENT. THE REQUIRED FIRE SPRINKLER
 SYSTEM IS REQUIRED TO BE MONITORED.
  
 3) PLEASE INDICATE PRESCRIPTIVE FOR
 HANDRAILS.
  
 4) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 5) UNIT ENTRY DOORS ARE TO BE AT LEAST
 20 MINUTE FIRE RATED.
  
 6) PLEASE INDICATE ON PLANS THE SINGLE
 EXIT DESIGN WITHIN THE UNITS.
  
 7) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 8) NO EMERGENCY LIGHTS SHOWN FOR
 EXTERIOR STAIRS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 11:28 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 11:28 Sent To ENG
Notes
2005-12-05 00:00:00TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 13:07 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 13:07 Sent To B
Notes
2005-04-14 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-28 Cont ID  
Sent By adarroug Date 2005-03-28 Time 14:34 Rev Time 0.00
Received By adarroug Date 2005-03-28 Time 14:34 Sent To B
Notes
2005-03-28 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-19 Cont ID  
Sent By csiegber Date 2004-10-19 Time 12:36 Rev Time 0.00
Received By csiegber Date 2004-10-19 Time 12:36 Sent To B
Notes
2004-10-19 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-19 Cont ID  
Sent By csiegber Date 2004-08-19 Time 09:16 Rev Time 0.00
Received By csiegber Date 2004-08-19 Time 09:14 Sent To  
Notes
2004-08-19 00:00:00TO COMM BD#37

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-07-01 Cont ID  
Sent By csiegber Date 2004-07-01 Time 08:23 Rev Time 0.00
Received By csiegber Date 2004-07-01 Time 08:22 Sent To  
Notes
2004-07-01 00:00:00TO COMM BD#38

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 11:48 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 11:48 Sent To  
Notes
2004-02-09 00:00:00TO COMM BD#37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-29 Cont ID  
Sent By csiegber Date 2003-12-29 Time 09:19 Rev Time 0.00
Received By csiegber Date 2003-12-29 Time 09:19 Sent To  
Notes
2003-12-29 00:00:00TO COMM BD#53

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-11-15 Cont ID  
Sent By pkrauss Date 2005-11-15 Time 14:58 Rev Time 0.55
Received By pkrauss Date 2005-11-15 Time 14:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-07-15 Cont ID  
Sent By pkrauss Date 2004-07-15 Time 16:39 Rev Time 1.20
Received By pkrauss Date 2004-07-15 Time 16:24 Sent To  
Notes
2004-07-15 00:00:00ADDITION TO EXISTING BUILDING/NOT A
 REVISION TO THE ORIGINAL SUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-02-18 Cont ID  
Sent By pkrauss Date 2004-02-18 Time 09:21 Rev Time 0.45
Received By pkrauss Date 2004-02-18 Time 07:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-01-07 Cont ID  
Sent By pkrauss Date 2004-01-07 Time 07:45 Rev Time 0.55
Received By pkrauss Date 2004-01-07 Time 07:11 Sent To  
Notes
2004-01-07 00:00:00DENIED:
 RESIDENTIAL:
 1.PER 2001 FBC(M) 403.3, VENTILATION
 SYSTEMS, FOR OTHER THAN R-3 (ONE & TWO
 FAMILY DWELLINGS), SHALL BE DESIGNED TO
 TO SUPPLY THE MINIMUM OUTSIDE AIR IN
 ACCORDANCE WITH TABLE 403.3.PLEASE
 PROVIDE OUTSIDE AIR CALCULATIONS.
 INDICATE OUTSIED AIR DUCT SIZE,
 MATERIAL, LAYOUT AND INTAKE ON THE PLAN.
  
 2.PLAN SHEET AC.3 INDICATES DUCT TO
 2ND FLOOR IN RATED SHAFT. PLEASE PROVIDE
 SHAFT DETAIL.
  
 RETAIL:PLANS ARE CODE COMPLIANT.
  
 PLEASE NOTE:
 PLANS DO NOT INDICATE THE USE OF THE
 RETAIL SPACE.BECAUSE OF THE LOCATION
 AND PROPERTY LINES, ALLOWANCE FOR A
 RESTAURANT MAY BE DIFFICULT SHOULD
 CONSIDERATION NOT BE GIVEN FOR THE
 INSTALLATION OF GREASE DUCT NOT BE MADE
 AT THE BEGINNING OF CONSTRUCTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-04 Cont ID  
Sent By pkrauss Date 2003-11-03 Time 15:33 Rev Time 2.00
Received By pkrauss Date 2003-11-03 Time 13:13 Sent To  
Notes
2003-11-03 00:00:00DENIED: BUILDING G
 1. OUTSIDE AIR REQUIRED AS PER 2001 FBC
 (M) TABLE 403.3.
  
 2. CEILING FIRE DAMPERS REQUIRED AS
 DICTATED BY BUILDING CONSTRUCTION, SEE
 1 HR RATED ASSEMBLY ON PLAN SHEET A.11.
 SEE ALSO DETAIL 15 ON PLAN SHEET A.15.
 PLEASE INDICATE LOCATION OF DAMPERS AS
 REQUIRED PER 2001 FBC(M) 607.6.
  
 3. ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 4. PLAN SHEET AC.2 INDICATES TOILET
 EXHAUST AS 4" DRYER DUCT. PLEASE CLARIFY
  
 5. PLEASE CLARIFY IF THE "DUCT SHAFTS"
 HAVE A FIRE RATING. REFERENCE PLAN
 SHEET A.11, FLOOR/CEILING ASSEMBLY.
  
 RETAIL:
 1. FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE AS PER
 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3.
  
 2. PLANS DO NOT INDICATE USE OF THE
 RETAIL SPACE.BECAUSE OF THE LOCATION
 AND PROPERTY LINES, ALLOWANCE FOR A
 RESTAURANT MAY BE DIFFICULT SHOULD
 CONSIDERATION NOT BE GIVEN FOR THE
 INSTALLATION OF GREASE DUCT NOT BE MADE
 AT THE BEGINNING OF CONSTRUCTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-10-12 Cont ID  
Sent By kstevens Date 2004-10-12 Time 11:39 Rev Time 1.00
Received By kstevens Date 2004-10-12 Time 11:39 Sent To  
Notes
2004-10-12 00:00:00REVISIONS OK SHTS P-1, P-2, P-3, P-4, &
 P-5

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-09-17 Cont ID  
Sent By kstevens Date 2004-09-16 Time 15:13 Rev Time 1.00
Received By kstevens Date 2004-09-16 Time 15:13 Sent To  
Notes
2004-09-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1) ALL ENGINEERED PLANS SHALL BE SIGNED
 WITH FULL SIGNATURE. FAC 61G15-23.002(1)
 (2) & FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-07-23 Cont ID  
Sent By kstevens Date 2004-07-23 Time 17:25 Rev Time 2.00
Received By kstevens Date 2004-07-23 Time 17:25 Sent To  
Notes
2004-07-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ALL ENGINEERED PLANS SHALL BE SIGNED
 WITH FULL SIGNATURE. FAC G1G15-23.002(1)
 (2) & FS 471.025.
 2) SHT P-3 SANT. RISER DIAGRAM, SHOW ALL
 PIPE SIZES AND DRAINAGE FIXTURE UNITS AS
 THEY ACCUMULATE IN THE BLDG. DRAIN. SEC
 104.2.1.
 3) SHT P-4 IF ICE MAKER LINE TO REFRIG.,
 A WATER HAMMER ARRESTOR IS REQUIRED PER
 SECTION 604.9.
 4) SUBMIT A DETAIL FOR TOILET ROOMS IN
 THE RETAIL SPACES. SHOW COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS, SEC
 11-4.1.3(10)(A) FOR THOSE WHO HAVE DIFF-
 ICULTY BENDING OR STOOPING, SECTION 11-4
 .16 AND ALL SUBSECTIONS, 11-4.19 AND ALL
 SUBSECTIONS, & 11-4.22 AND ALL SUBSECT-
 IONS.
 5) SUBMIT A FINISH SCHEDULE FOR TOILET
 ROOMS IN THE RETAIL SPACES. SECTION
 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-14 Cont ID  
Sent By kstevens Date 2004-01-14 Time 12:58 Rev Time 0.33
Received By kstevens Date 2004-01-14 Time 12:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-11-03 Cont ID  
Sent By kstevens Date 2003-11-03 Time 18:26 Rev Time 1.00
Received By kstevens Date 2003-11-03 Time 18:25 Sent To  
Notes
2003-11-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P.1 PLUMBING NOTES #15, WATTS
 530C NOT APPROVED FOR MULTI-HEATER USE
 PER MANUFACTURE INFORMATION. WATTS 530
 APPROVED FOR INDIVIDUAL HEATER USE ONLY.
 PROVIDE INFORMATION FOR THERMAL EXPANS-
 ION CONTROL PER 607.3.2 ALSO SEE WATER
 RISER DIAGRAM SHT P.4 AND WATER HEATER
 DETAIL SHT P.5.
 2) SHT P.4 WATER HAMMER ARRESTORS ARE
 REQUIRED PER SECTION 604.9 FOR WASH
 MACHINES, DISHWASHERS, AND ICE MAKERS.
 SHOW WATER HAMMER ARRESTORS ON THE WATER
 RISER LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 3) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2005-12-02 Cont ID  
Sent By jroach Date 2005-12-02 Time 08:45 Rev Time 0.00
Received By jroach Date 2005-12-02 Time 08:45 Sent To  
Notes
2005-12-02 00:00:00GIVEN TO INCOMING FOR ENGINEERING REVIEW

Review Stop Z ZONING
Rev No 3 Status P Date 2004-08-30 Cont ID  
Sent By jroach Date 2004-08-30 Time 10:58 Rev Time 0.00
Received By jroach Date 2004-08-30 Time 10:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2004-07-20 Cont ID  
Sent By jroach Date 2004-07-20 Time 11:42 Rev Time 0.00
Received By jroach Date 2004-07-20 Time 11:42 Sent To  
Notes
2004-07-20 00:00:007/20/04 - FAILED.
 1) EASEMENT RELOCATION AGREEMENT MUST BE
 RECORDED PRIOR TO ISSUANCE OF PERMIT.
 2) LANDSCAPE PLANS MUST BE SIGNED AND
 SEALED.
 3) PLANS MUST BE SIGNED OFF BY HISTORIC
 PRESERVATION DIVISION.
 CALL JOHN ROACH, PLANNER 659.8031

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-03 Cont ID  
Sent By mmclean Date 2003-11-03 Time 11:18 Rev Time 0.00
Received By mmclean Date 2003-11-03 Time 11:18 Sent To I
Notes
2003-11-03 00:00:0011/3/03 OK PER ERIC SCHNEIDER MM