Plan Review Stops For Permit 03100308 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2003-11-20 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2003-11-20 |
Time |
11:04 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-10-21 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2003-10-21 |
Time |
10:04 |
Rev Time |
0.75 |
Received By |
lsmith |
Date |
2003-10-21 |
Time |
10:04 |
Sent To |
|
|
Notes |
2003-10-21 00:00:00 | FAILED: | | | | 1. ACCORDING TO FAC 61GL-16.004 ALL | | SIGNED & SEALED PLANS MUST HAVE A TITLE | | BLOCK WITH THE LICENSE NUMBER, ADDRESS | | &NAME OF PERSON SIGNING & SEALING | | DOCUMENTS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2003-11-20 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2003-11-20 |
Time |
11:11 |
Rev Time |
1.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2003-11-20 00:00:00 | ARCHITECT RE-SIGNED AND SEALED PLANS ON | | 11/18/03 AS REQUESTED. LM |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2003-11-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-11-07 |
Time |
15:40 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-11-07 |
Time |
15:39 |
Sent To |
|
|
Notes |
2003-11-07 00:00:00 | ************ UNSAT **************** | | | | 1)NOTE: PLEASE SEE PLANS REQUIRE A | | RAISED VISABLE SEAL FOR ARCH OF RECORD | | PER FS 481.221 AND FAC 61G1-16.004. | | | | | | | | | | NEW NOTE | | | | 1)NOTE: PLEASE SEE THAT THIS OFFICE | | HAS BEEN INFORMED SINCE THE LAST REVIEW | | THAT ALL PLANS MUST BE SIGNED WITH A | | "SIGNATURE" FROM ARCH/ ENG CONTAINING | | A MIN OF FIRST/LAST NAME AND /OR HOW | | NAME WAS SIGNED ON ORIGIANL LICENSE | | APPLICATION. PER FS 471/481. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-10-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-10-14 |
Time |
19:16 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-10-14 |
Time |
19:16 |
Sent To |
|
|
Notes |
2003-10-14 00:00:00 | ********** UNSAT **************** | | | | 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR | | ALL REQ'D LICENSE INFORMATION ON TITLE | | BLOCK. AR#/ AA# . | | FS 481 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2003-11-19 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-11-19 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-11-19 |
Time |
13:33 |
Sent To |
|
|
Notes |
2003-11-19 00:00:00 | *************PROVISO******************** | | SEPARATE PLANS AND PERMIT ARE REQUIRED | | FOR FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS REMODEL. | | | | NATE MCCRAY, CAPTAIN | | 805-6722 OR 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2003-10-29 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2003-10-29 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2003-10-29 |
Time |
11:03 |
Sent To |
|
|
Notes |
2003-10-29 00:00:00 | 1) WHAT IS THE WALL AND CEILING INTERIOR | | FINISH CLASSIFICATION. | | | | 2) SEPARATE PLANS AND PERMITS ARE | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | ALARM SYSTEMS REMODEL. | | | | NATE MCCRAY, CAPTAIN | | 805-6722 OR 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-11-07 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-11-07 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-11-07 |
Time |
15:11 |
Sent To |
|
|
Notes |
2003-11-07 00:00:00 | TO COMM BD#29 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-11-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-11-04 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2003-10-06 |
Time |
13:46 |
Sent To |
|
|
Notes |
2003-10-06 00:00:00 | TO COMM BD#24 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-11-19 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-11-19 |
Time |
15:16 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2003-11-19 |
Time |
15:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2003-11-04 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-11-04 |
Time |
14:43 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2003-11-04 |
Time |
14:43 |
Sent To |
|
|
Notes |
2003-11-04 00:00:00 | DENIED: | | 1.SEE COMMENTS BY BUILDING & ELECTRIC, | | TITLE BLOCK REQUIRED AS PER FAC 61G1-16. | | 004. | | | | 2.PLAN SHEET M-1 AHU MOUNTING DETAIL, | | PAN W/FLOAT SWITCH OR AUXILIARY DRAIN | | LINE.PLEASE INDICATE TERMINATION POINT | | OF THE AUXILIARY DRAIN LINE ( AT A | | CONSPICUOUS POINT). | | | | 3.DUCT SMOKE DETECTORS ARE NOT | | IDENTIFIED ON THE PLAN.PLEASE INDICATE | | LOCATIONS OF DUCT SMOKE DETECTORS. SHOW | | COMPLIANCE WITH 2001 606.2.1. | | | | 4. FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | IN NORMALLY OCCUPIED AREAS AS PER NFPA | | 90A 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2003-11-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-11-19 |
Time |
14:41 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-11-19 |
Time |
14:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-10-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-10-28 |
Time |
11:12 |
Rev Time |
0.50 |
Received By |
kstevens |
Date |
2003-10-28 |
Time |
11:12 |
Sent To |
|
|
Notes |
2003-10-28 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | | | 1) SHT D1 INDICATES THAT A SINK IS LOCA- | | TED WHERE THE NEW SINK WILL BE INSTALLED | | PLEASE CLAIRFY. 104.2.1 | | 2) SUBMIT MANUF. SPECIFICATIONS FOR PUMP | | SYSTEM. PUMP SHALL BE LABLED AND LISTED. | | 3) A GATE VALVE LOCATED ON THE DISCHARGE | | SIDE OF THE CHECK VALVE SHALL BE INSTAL- | | LED IN THE PUMP OR EJECTOR DISCHARGE | | PIPING BETWEEN THE PUMP OR EJECTOR AND | | THE GRAVITY DRAINAGE SYSTEM. | | 4) THE PUMP SYSTEM SHALL TIE INTO A VENT | | LINE. AAV'S ARE NOT DESIGNED FOR POSIT- | | IVE PRESSURE. 916.5.1 & 917.2 | | 5) SEAL FOR ARCHITECT NOT APPROVED. ALSO | | MORE INFORMATION REQUIRED FOR TITLE | | BLOCK. SEE ATTACHED SHEET. 61G1-16.002 | | AND 61G1-16.004 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|