Plan Review Details - Permit 03100308
Plan Review Stops For Permit 03100308
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-11-20 Cont ID  
Sent By lmartine Date 2003-11-20 Time 11:04 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-21 Cont ID  
Sent By lsmith Date 2003-10-21 Time 10:04 Rev Time 0.75
Received By lsmith Date 2003-10-21 Time 10:04 Sent To  
Notes
2003-10-21 00:00:00FAILED:
  
 1. ACCORDING TO FAC 61GL-16.004 ALL
 SIGNED & SEALED PLANS MUST HAVE A TITLE
 BLOCK WITH THE LICENSE NUMBER, ADDRESS
 &NAME OF PERSON SIGNING & SEALING
 DOCUMENTS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-20 Cont ID  
Sent By lmartine Date 2003-11-20 Time 11:11 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-11-20 00:00:00ARCHITECT RE-SIGNED AND SEALED PLANS ON
 11/18/03 AS REQUESTED. LM

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-07 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 15:40 Rev Time 0.33
Received By dpalmer Date 2003-11-07 Time 15:39 Sent To  
Notes
2003-11-07 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE PLANS REQUIRE A
 RAISED VISABLE SEAL FOR ARCH OF RECORD
 PER FS 481.221 AND FAC 61G1-16.004.
  
  
  
  
 NEW NOTE
  
 1)NOTE: PLEASE SEE THAT THIS OFFICE
 HAS BEEN INFORMED SINCE THE LAST REVIEW
 THAT ALL PLANS MUST BE SIGNED WITH A
 "SIGNATURE" FROM ARCH/ ENG CONTAINING
 A MIN OF FIRST/LAST NAME AND /OR HOW
 NAME WAS SIGNED ON ORIGIANL LICENSE
 APPLICATION. PER FS 471/481.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2003-10-14 Time 19:16 Rev Time 0.50
Received By dpalmer Date 2003-10-14 Time 19:16 Sent To  
Notes
2003-10-14 00:00:00********** UNSAT ****************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL REQ'D LICENSE INFORMATION ON TITLE
 BLOCK. AR#/ AA# .
 FS 481
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-19 Cont ID  
Sent By nmccray Date 2003-11-19 Time 13:33 Rev Time 0.00
Received By nmccray Date 2003-11-19 Time 13:33 Sent To  
Notes
2003-11-19 00:00:00*************PROVISO********************
 SEPARATE PLANS AND PERMIT ARE REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-29 Cont ID  
Sent By nmccray Date 2003-10-29 Time 11:04 Rev Time 0.00
Received By nmccray Date 2003-10-29 Time 11:03 Sent To  
Notes
2003-10-29 00:00:001) WHAT IS THE WALL AND CEILING INTERIOR
 FINISH CLASSIFICATION.
  
 2) SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-07 Cont ID  
Sent By csiegber Date 2003-11-07 Time 15:11 Rev Time 0.00
Received By csiegber Date 2003-11-07 Time 15:11 Sent To  
Notes
2003-11-07 00:00:00TO COMM BD#29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-04 Cont ID  
Sent By pkrauss Date 2003-11-04 Time 14:55 Rev Time 0.00
Received By pkrauss Date 2003-10-06 Time 13:46 Sent To  
Notes
2003-10-06 00:00:00TO COMM BD#24

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-19 Cont ID  
Sent By pkrauss Date 2003-11-19 Time 15:16 Rev Time 0.40
Received By pkrauss Date 2003-11-19 Time 15:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-04 Cont ID  
Sent By pkrauss Date 2003-11-04 Time 14:43 Rev Time 0.45
Received By pkrauss Date 2003-11-04 Time 14:43 Sent To  
Notes
2003-11-04 00:00:00DENIED:
 1.SEE COMMENTS BY BUILDING & ELECTRIC,
 TITLE BLOCK REQUIRED AS PER FAC 61G1-16.
 004.
  
 2.PLAN SHEET M-1 AHU MOUNTING DETAIL,
 PAN W/FLOAT SWITCH OR AUXILIARY DRAIN
 LINE.PLEASE INDICATE TERMINATION POINT
 OF THE AUXILIARY DRAIN LINE ( AT A
 CONSPICUOUS POINT).
  
 3.DUCT SMOKE DETECTORS ARE NOT
 IDENTIFIED ON THE PLAN.PLEASE INDICATE
 LOCATIONS OF DUCT SMOKE DETECTORS. SHOW
 COMPLIANCE WITH 2001 606.2.1.
  
 4. FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS AS PER NFPA
 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-11-19 Cont ID  
Sent By kstevens Date 2003-11-19 Time 14:41 Rev Time 0.50
Received By kstevens Date 2003-11-19 Time 14:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By kstevens Date 2003-10-28 Time 11:12 Rev Time 0.50
Received By kstevens Date 2003-10-28 Time 11:12 Sent To  
Notes
2003-10-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1) SHT D1 INDICATES THAT A SINK IS LOCA-
 TED WHERE THE NEW SINK WILL BE INSTALLED
 PLEASE CLAIRFY. 104.2.1
 2) SUBMIT MANUF. SPECIFICATIONS FOR PUMP
 SYSTEM. PUMP SHALL BE LABLED AND LISTED.
 3) A GATE VALVE LOCATED ON THE DISCHARGE
 SIDE OF THE CHECK VALVE SHALL BE INSTAL-
 LED IN THE PUMP OR EJECTOR DISCHARGE
 PIPING BETWEEN THE PUMP OR EJECTOR AND
 THE GRAVITY DRAINAGE SYSTEM.
 4) THE PUMP SYSTEM SHALL TIE INTO A VENT
 LINE. AAV'S ARE NOT DESIGNED FOR POSIT-
 IVE PRESSURE. 916.5.1 & 917.2
 5) SEAL FOR ARCHITECT NOT APPROVED. ALSO
 MORE INFORMATION REQUIRED FOR TITLE
 BLOCK. SEE ATTACHED SHEET. 61G1-16.002
 AND 61G1-16.004
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]