Plan Review Details - Permit 03100255
Plan Review Stops For Permit 03100255
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-05-12 Cont ID  
Sent By jgomez Date 2004-05-12 Time 14:22 Rev Time 0.33
Received By jgomez Date 2004-05-12 Time 14:22 Sent To PC
Notes
2004-05-12 00:00:00CONNECTORS PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:19 Rev Time 1.00
Received By jgomez Date 2004-04-16 Time 14:52 Sent To PC
Notes
2004-04-16 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE INFORMATION FOR STORM SHUTTERS
 UNDER A SEPARATE PERMIT.
 2-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR STRUCTURAL CONNECTORS.
 PRODUCT APPROVAL SUBMITTED WAS FOR
 SIMPSON. NEED FOR USP PRODUCTS AS WELL
 SINCE THEY ARE ALSO SPECIFIED ON PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-19 Cont ID  
Sent By csiegber Date 2004-04-07 Time 14:30 Rev Time 4.00
Received By jgomez Date 2003-12-19 Time 09:43 Sent To PC
Notes
2003-12-19 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE DESIGN PRESSURES SPECIFIED FOR
 DOORS AND WINDOWS. SEE TABLES 1606.2B
 AND 1606.2E FBC 2001 OR PROVIDE CALCS
 FOR VALUES LOWER THAN THOSE SHOWN ON
 FBC TABLES.SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 **ALSO, DESIGN PRESSURES SHOWN ON DESIGN
 PRESSURES FOR OPENINGS CHART SUBMITTED
 WITH PRODUCT APPROVALS DON'T MATCH
 THOSE SHOWN ON PLANS.
 2-SPECIFY SAFETY GLASS FOR WINDOW AT
 MASTER BATH SHOWER. SEC. 2405.2 FBC.
 3-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 4-REVISE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001 WHICH DOESN'T ALLOW
 THE STEEL STRESS TO BE INCREASED.
 PROVIDE ENGINEERING CALCS FOR VALUES
 OTHER THAN THOSE PUBLISHED ON REVISED
 CATALOGUE ACCORDING TO THE NUMBER AND
 TYPE OF NAILS USED.SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 5-ROOF SHEATHING NOTE ON SHEET A3:
 A)REVISE MIN. ROOF SHEATHING THICKNESS.
 NEED 19/32" MIN. THICKNESS.
 B)ZONE 3 AREAS INCLUDE CORNERS.
 SEE TABLE 2306.1 CITY AMENDMENTS TO
 FBC 2001.
  
 6-REVISE SPECIFICATIONS FOR CEILING
 INSTALLATION AT FRONT & REAR PORCHES.
 SEE ASTM C-926 FOR MIN. NAIL SIZE
 REQUIRED.SEC. 2504.2 FBC 2001.
 7-ENERGY CALCULATIONS: REVISE UNDER
 ATTIC AREA. SEE SEC. 604.1.A.1 CHAPTER
 13 FBC 2001.
 8-SIZE OF FOOTING SHOWN ON TYP. WALL
 SECTION DOESN'T MATCH SIZE SPECIFIED
 ON FOUNDATION PLAN. REVISE AS REQ'D.
 9-FLORIDA PRODUCT APPROVALS:
 A)ROOFING REPORT SUBMITTED IS FROM DADE
 COUNTY. FLORIDA PRODUCT APPROVAL CALLS
 FOR SBCCI REPORT. RESUBMIT.
 B)FIXED WINDOWS DADE COUNTY NOAS DON'T
 MATCH NOAS REFERENCED ON FLORIDA
 PRODUCT APPROVAL. RESUBMIT.
 C)MULLIONS DADE COUNTY NOAS SUBMITTED
 DON'T MATCH THOSE REFERENCED ON THE
 FLORIDA PRODUCT APPROVAL. RESUBMIT.
 D)NEED PRODUCT APPROVALS FOR STRUCTURAL
 CONNECTORS. EG: TRUSS ANCHORS.
  
 10-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-12-05 Time 09:51 Rev Time 3.00
Received By jgomez Date 2003-11-03 Time 14:01 Sent To PC
Notes
2003-11-03 00:00:00BUILDING CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE DETAIL CONNECTION AT TRANSOM
 WINDOW ON TOP OF GLASS BLOCK AT MASTER
 BATH. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001. ***NOTE: SEE PRODUCT
 APPROVAL FOR APPROVED INSTALLATIONS.
 3-PROVIDE CONSTRUCTION DETAIL FOR ARCHED
 OPENINGS AT WINDOWS AND ENTRY PORCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-REVISE DESIGN PRESSURES SPECIFIED FOR
 DOORS AND WINDOWS OPENINGS. SEE TABLES
 1606.2B AND 1606.2E FBC 2001. OR PRO-
 VIDE ENGINEERING CALCULATIONS FOR
 DESIGN PRESSURES SHOWN.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-PROVIDE AIR HANDLING UNIT HANGING
 DETAILS. SPECIFY ALL FASTENERS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-DESIGN PARAMETERS ON SHEET A3:
 A)INCLUDE THE ATTIC LIVE LOAD (10PSF OR
 30PSF)AS REQ'D BY TABLE 1604.1 FBC.
 B)WHERE IS THE DESIGN WIND VELOCITY
 PRESSURE TAKEN FROM. SEE SEC. 6.5.12
 OF ASCE 7-98 FOR VELOCITY PRESSURE.
 C)REVISE THE MEAN ROOF HEIGHT. IT IS
 TAKEN FROM FINISH GRADE TO THE AVERAGE
 POINT OF THE HIGHEST ROOF.
 D)SEE COMMENTS ON SHEET A3.
  
 7-PROVIDE COMPLETE DETAIL FOR INSTALLA-
 TION OF DOUBLE FRENCH DOORS MULLED
 TOGETHER. SEE DOOR PRODUCT APPROVAL
 FOR APPROVED INSTALLATIONS. SPECIFY
 ALL MATERIALS AND FASTENERS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 8-PROVIDE BBQ UL LISTING AND SPECS.
 SECTION 2808 FBC 2001.
 9-SPECIFY ON PLANS IF GLASS BLOCK IS
 SAFETY GLASS OR FACE THICKNESS IS NOT
 LESS THAN 0.25". SEC. 2405.2.2 FBC.
 10-PROVIDE STRUCTURAL BUCK DETAIL FOR
 OVAL AND ARCHED WINDOWS. ALSO, REVISE
 DOOR AND WINDOW BUCK DETAIL ON SHEET
 A2 TO COMPLY WITH SEC. 1707.4.4.2 FOR
 CORRECT BUCK INSTALLATION.
 11-DETAIL D/6: SPECIFY ANCHOR EMBEDMENT.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 AND 1606.1.3 FBC 2001.
 12-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ENTRY DOORS. SEE PLANS FOR GAP SHOWN.
 SPECIFY SIZE OF BUCKS AND FASTENERS.
 ALSO, SEE SEC. 1707.4.4.2 FOR PROPER
 BUCK INSTALLATION.
 13-STORM SHUTTERS: A)PROVIDE STATE WIDE
 PRODUCT APPROVAL OR INFORMATION FOR
 LOCAL PRODUCT APPROVAL. SEE ATTACHED
 COPY FOR QUESTIONS & ANSWERS REGARDING
 PRODUCT APPROVAL SUBMITTAL AFTER OCT.
 2001.
 B)PROVIDE KEY PLAN AND COMPLETE INSTALLA
 TION SCHEDULE.
 C)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO.
  
 14-SPECIFY WHICH OPENING IS GOING TO BE
 USED FOR MEANS OF EGRESS THAT COMPLIES
 WITH SEC. 1005.4.5 FBC 2001.
 15-REVISE TRUSS ANCHOR SCHEDULE TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001
 WHICH DOESN'T ALLOW THE STEEL STRESS
 TO BE INCREASED. PROVIDE ENGINEERING
 CALCS FOR VALUES OTHER THAN THOSE
 SHOWN ON PUBLISHED ANCHOR CATALOGUE.
 16-PROVIDE ROOF SHEATHING DIAPHRAGM
 SHOWING NAILING ZONES, FASTENER TYPE
 AND SPACING. SEC. 2306 CITY AMENDMENTS
 17-PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCH.
 SEE ASTM C926 AND ASTM C1063.SECTION
 2504.2 FBC 2001.
 18-ENERGY CALCULATIONS: A)COMPLETE ALL
 INFORMATION ON TOP OF FORM.
 B)REVISE UNDER ATTIC AREA. SEE SECTION
 604.1.A.1. CHAPTER 13 FBC 2001.
 C)OWNER/AGENT TO SIGN AND DATE FORM TOO.
  
 19-NEED STATE WIDE OR LOCAL PRODUCT
 APPROVAL FOR ALL DOORS, WINDOWS,
 MULLIONS, GLASS BLOCK, ROOF FINISHES.
 SEE ATTACHED QUESTIONS & ANSWERS COPY
 NOTE:
 ***ADDITIONALLY MARK ON SUBMITTED DWGS
 THE SPECIFIC COMPONENTS TO BE USED. EG:
 IMPACT GLAZING OR NOT, SPECIFIC MULLION
 SIZE AND ANCHOR SPACING, ETC.
 20-SEE COMMENTS ON SHEET A6 AND PLEASE
 RETURN REVIEWED SET OF DRAWINGS AFTER
 CORECTIONS ARE DONE TO ORIGINAL CAD
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
 21-VALUATION AND SQUARE FOOTAGE WAS
 UPDATED. TOTAL PERMIT FEE IS $3532.98.
 PLEASE BRING PAID RECEIPT TO ADJUST
 PAYMENTS AND PAY THE BALANCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-06 Cont ID  
Sent By btrobaug Date 2004-08-06 Time 12:45 Rev Time 0.50
Received By btrobaug Date 2004-08-06 Time 12:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-08-05 Time 13:37 Rev Time 0.33
Received By dpalmer Date 2004-04-20 Time 09:51 Sent To P
Notes
2004-04-20 00:00:00**REDLINED NOTES***
  
 MISSING EQUIPMENT FROM MAINS TO PANELS
 SIZE PER 250.122
 MISSING RECEPT FOR 2' OF WALL. 210.52
 BDRM #4

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-10-16 Cont ID  
Sent By jleech Date 2003-10-14 Time 17:38 Rev Time 0.75
Received By btrobaug Date 2003-10-16 Time 08:37 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-05 Cont ID  
Sent By csiegber Date 2004-08-05 Time 13:37 Rev Time 0.00
Received By csiegber Date 2004-08-05 Time 13:37 Sent To E
Notes
2004-08-05 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 15:17 Sent To B
Notes
2004-04-28 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-04-07 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-04-07 Time 14:29 Sent To B
Notes
2004-04-07 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-19 Cont ID  
Sent By csiegber Date 2003-12-05 Time 09:51 Rev Time 0.00
Received By jgomez Date 2003-12-05 Time 09:51 Sent To PC
Notes
2003-12-05 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-03 Cont ID  
Sent By mmclean Date 2003-10-06 Time 16:09 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 12:15 Sent To PC
Notes
2003-10-06 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-21 Cont ID  
Sent By btrobaug Date 2003-10-16 Time 13:30 Rev Time 0.33
Received By pkrauss Date 2003-10-21 Time 06:47 Sent To B
Notes
2003-10-21 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-24 Cont ID  
Sent By kstevens Date 2004-04-24 Time 15:55 Rev Time 0.50
Received By kstevens Date 2004-04-24 Time 15:55 Sent To  
Notes
2004-04-24 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 SHEET A4 OF 6 SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN. BATH #4
 SHOWS SHOWER ON RIGHT SIDE OF W/C AND
 LAV ON LEFT SIDE ON FLOOR PLAN BUT SHOWS
 A TUB ON THE LEFT SIDE AND A LAV ON THE
 RIGHT ON THE RISER DIAGRAM. - THE RISER
 DIAGRAM SHOWS A 2ND WASH MACHINE BEHIND
 THE LAV OF BATH #3 NOT SHOWN ON FLOOR
 PLAN. PLEASE CORRECT REVISION AND RE-
 SUBMIT FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2004-04-20 Time 09:53 Rev Time 0.33
Received By jleech Date 2003-10-14 Time 17:37 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-06 Cont ID  
Sent By mmclean Date 2003-10-06 Time 16:09 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***