Plan Review Details - Permit 03100206
Plan Review Stops For Permit 03100206
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-11-10 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:00 Rev Time 1.50
Received By lsmith Date 2003-11-10 Time 07:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-10-15 Cont ID  
Sent By jleech Date 2003-10-08 Time 19:25 Rev Time 0.50
Received By btrobaug Date 2003-10-15 Time 13:11 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:00 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 09:00 Sent To B
Notes
2004-02-06 00:00:00TO MISC BOX/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-10 Cont ID  
Sent By mmclean Date 2003-10-06 Time 16:09 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 12:18 Sent To  
Notes
2003-10-24 00:00:00TO KS BOX/1ST RESUB
2003-10-06 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-18 Cont ID  
Sent By pkrauss Date 2004-02-18 Time 07:16 Rev Time 0.30
Received By pkrauss Date 2004-02-18 Time 07:10 Sent To  
Notes
2004-02-18 00:00:00RE-STAMP

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-16 Cont ID  
Sent By btrobaug Date 2003-10-15 Time 13:56 Rev Time 0.50
Received By hmoser Date 2003-10-16 Time 19:20 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-11-08 Cont ID  
Sent By jleech Date 2003-11-08 Time 08:27 Rev Time 0.33
Received By jleech Date 2003-11-08 Time 08:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-31 Cont ID  
Sent By kstevens Date 2003-10-31 Time 18:53 Rev Time 0.50
Received By kstevens Date 2003-10-31 Time 18:53 Sent To  
Notes
2003-10-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN NOR DOES IT MEET
 CODE REQUIREMENTS. PREVIOUS REVIEW
 COMMENTS WERE NOT ADDRESSED. SEE
 ATTACHED EXAMPLE OF A SANITARY RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN AND
 MEETS CODE REQUIREMENTS.
 2) SEE ATTACHED SHEET ABOUT FLORIDA
 STATUTE 553.80(2)(B) AND DESIGN PROFESS-
 IONAL DOCUMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-08 Cont ID  
Sent By jleech Date 2003-10-08 Time 19:25 Rev Time 0.33
Received By jleech Date 2003-10-08 Time 19:24 Sent To E
Notes
2003-10-08 00:00:00DENIED;
 1.W/M AND L/T MUST HAVE A SEPORATE WASTE
 STACK. SEE SEC. 909.1.
 2.W/M SHOULD DUMP BELOW L/T.
 3.SEPORATE STACK REQUIRED FOR BAR SINK.
 SEC. 909.1.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 10:13 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***