Plan Review Details - Permit 03100007
Plan Review Stops For Permit 03100007
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-16 Cont ID  
Sent By btrobaug Date 2003-10-16 Time 16:14 Rev Time 0.50
Received By btrobaug Date 2003-10-16 Time 16:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-10-10 Cont ID  
Sent By csiegber Date 2003-10-01 Time 10:36 Rev Time 0.50
Received By btrobaug Date 2003-10-07 Time 17:43 Sent To  
Notes
2003-10-08 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
  
 PLEASE LABEL THE DEVICES AND EQUIPMENT
 WITH BRANCH CIRCUIT NUMBERS
 CORRESPONDING TO THE PANEL SCHEDULE.
  
 RESUBMIT THE CORRECTED PLANS FOR REVIEW
 PRIOR TO CALLING ROUGH ELECTRICAL
 INSPECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-01 Cont ID  
Sent By csiegber Date 2003-10-01 Time 10:36 Rev Time 0.00
Received By csiegber Date 2003-10-01 Time 10:36 Sent To E
Notes
***NONE***