Plan Review Stops For Permit 03100007 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-10-16 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2003-10-16 |
Time |
16:14 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-10-16 |
Time |
16:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2003-10-10 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-01 |
Time |
10:36 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2003-10-07 |
Time |
17:43 |
Sent To |
|
|
Notes |
2003-10-08 00:00:00 | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE NOTE THAT THE LOAD | | CALCULATIONS NEED TO BE SHOWN. SQ FT/ | | RECEPT LOADS ETC. PER 220-3,220-10, | | 220-11, 220-13. (215-5) | | | | PLEASE LABEL THE DEVICES AND EQUIPMENT | | WITH BRANCH CIRCUIT NUMBERS | | CORRESPONDING TO THE PANEL SCHEDULE. | | | | RESUBMIT THE CORRECTED PLANS FOR REVIEW | | PRIOR TO CALLING ROUGH ELECTRICAL | | INSPECTION. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-10-01 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-01 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-01 |
Time |
10:36 |
Sent To |
E |
|
Notes |
|
|
|