Plan Review Stops For Permit 03092071
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-23 Cont ID  
Sent By jgomez Date 2003-12-23 Time 11:55 Rev Time 1.00
Received By jgomez Date 2003-12-23 Time 11:55 Sent To PC
Notes
2003-12-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-25 Cont ID  
Sent By btrobaug Date 2003-12-22 Time 12:35 Rev Time 1.00
Received By jgomez Date 2003-11-25 Time 14:41 Sent To PC
Notes
2003-11-25 00:00:00BUILDING REVIEW CHECKLIST:
 1-PLANS DON'T MATCH. ELECTRICAL PLAN
 DOESN'T MATCH FLOOR PLAN. CLARIFY AS
 REQUIRED.
 2-ENERGY CALCULATIONS DON'T MATCH FLOOR
 PLAN AREA. PLANS SHOW 1400S.F. AND
 ENERGY CALCS SHOW 1092S.F. CLARIFY
 AS REQUIRED.
 3-PROVIDE IMPACT FEES PAID RECEIPT.
 4-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS. INSTALLATION SCHEDULE KEY
 PLAN & CLEARLY MARK ON DWGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 **NOTE: IF INFORMATION IS NOT COMPLETE,
 THEN, CONTRACTOR MAY APPLY FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 5-CONTRACTOR TO UPDATE INSURANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-29 Cont ID  
Sent By btrobaug Date 2003-11-19 Time 18:00 Rev Time 2.00
Received By jgomez Date 2003-10-29 Time 13:26 Sent To PC
Notes
2003-10-29 00:00:00BUILDING CHECKLIST:
 1-PLANS DON'T MATCH. PLANS SUBMITTED ARE
 FOR 2 DIFFERENT MODELS.
 2-NEED LETTER CERTIFICATE FROM THE THIRD
 PARTY AGENCY AS REQ'D BY SEC. 428.4.2
 FBC 2001.
 3-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS & RECEIPT.
 4-SURVEY NEEDS ORIGINAL SIGNATURE, DATE
 AS REQ'D BY CHAPTER 471 FL STATUTES.
 5-ENERGY CALCULATIONS: A)COMPLETE ALL
 INFO. ON TOP OF FORM.
 B)CLARIFY WHY THERE IS NOT INSULATION ON
 THE RAISED FLOOR . SECTION 605 CHAPTER
 13 FBC 2001.
 C)REVISE/CLARIFY VALUE GIVEN FOR UNDER
 ATTIC INSULATION. SEE PLANS FOR RVALUE
 USED.
 D)PREPARER TO SIGN AND DATE BOTTOM OF
 FORM. SEC. 103.1.1 CHAPTER 13 FBC.
 E)OWNER/AGENT TO SIGN AND DATE BOTTOM OF
 FORM. SEC. 103.1.2 CHAPTER 13 FBC 2001
  
 6-LOCAL ENGINEER TO PROVIDE ALL INFO. AS
 LISTED ON SEC. 1606.1.7 FBC 2001.
 7-LOCAL ENGINEER TO PROVIDE ALL HIS INFO
 AS REQ'D BY CHAPTER 471 FL. STATUTES.
 8-STORM SHUTTERS: A)PROVIDE LEGIBLE AND
 COMPLETE DRAWINGS. PAGE ONE AND TWO.
 B)PROVIDE KEY PLAN AND COMPLETE INSTALLA
 TION SCHEDULE.
 C)CLEARLY MARK ON STORM SHUTTER DRAWINGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO THE DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 9-SOIL TEST REPORT TO HAVE ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
 10-CONTRACTOR'S SCREEN CALLS FOR EXPIRED
 INSURANCE. PLEASE, UPDATE CONTRACTOR'S
 INFORMATION WITH PERMIT CLERK.
 11-OWES $171.51 FOR UPDATED VALUE AND
 RADON FEES. PLEASE PAY ATTACHED
 RECEIPT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-22 Cont ID  
Sent By btrobaug Date 2003-12-22 Time 12:35 Rev Time 0.33
Received By btrobaug Date 2003-12-22 Time 12:28 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-19 Cont ID  
Sent By btrobaug Date 2003-11-19 Time 18:00 Rev Time 0.50
Received By btrobaug Date 2003-11-19 Time 13:14 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-11-18 Time 16:53 Rev Time 0.50
Received By dpalmer Date 2003-10-20 Time 15:51 Sent To M
Notes
2003-10-20 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS REFERENCE 1999
 NEC, AS OF 7/1/2003 WE ARE NOW UNDER
 THE 2002 NEC.
  
 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 210.12.
 PLEASE SEE THAT IS IT NO LONGER JUST
 RECEPTS.
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 COMPLETE WITH CONDUCTORS/CONDUITS AND
 LOAD CALCULATIONS FOR MIN REQ'D PER
 NEC 220. 215.5MIN LOADS PER NEC 220
  
 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250.50.
  
 5)NOTE: PLEASE CLARIFY REQ'D SD'S PER
 NFPA-72 2-5. PLEASE SEE THAT PLANS SHOW
 WHAT APPEAR TO BE TELEPHONE OUTLETS
 AT LOCATIONS FOR SD'S?
  
 6)NOTE: PLEASE SHOW A/C UNITS AND RECEPT
 -S PER 210.63.
  
 7)NOTE: PLEASE SEE MISSING RECEPT FOR
 2' OF WALL SPACE PER 210.52. BR#3
  
 8)NOTE: PLEASE SEE FS 471.025 AND FAC
 61G15-23.002. PLANS ARE REQ'D TO BE
 ORIGINAL SIGNATURE,DATED AND SEALED BY
 ENGINEER OF RECORD. THIS COMMENT IS
 FOR ALL PAGES INCLUSIVE OF OTHER TRADES
 ALSO,WEATHER OR NOT IT IS ANOTHER REVIEW
 -ERS COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-18 Cont ID  
Sent By csiegber Date 2003-11-18 Time 16:53 Rev Time 0.00
Received By csiegber Date 2003-11-18 Time 16:52 Sent To E
Notes
2003-11-18 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-07 Cont ID  
Sent By mmclean Date 2003-10-09 Time 10:06 Rev Time 0.00
Received By shernand Date 2003-10-07 Time 14:32 Sent To Z
Notes
2003-10-07 00:00:00CONTR HIGHLIGHTED LANDSCAPE PLAN FOR
 ZONING, SENT TO ZONING.SH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By mmclean Date 2003-10-03 Time 16:05 Rev Time 0.00
Received By csiegber Date 2003-10-01 Time 09:54 Sent To  
Notes
2003-10-09 00:00:0010/09/2003 TO SFD RACK/E
2003-10-06 00:00:00TO SFD RACK/E
2003-10-01 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-10-22 Cont ID  
Sent By dpalmer Date 2003-10-20 Time 15:51 Rev Time 0.15
Received By pkrauss Date 2003-10-22 Time 07:50 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-10-14 Cont ID  
Sent By jleech Date 2003-10-14 Time 16:42 Rev Time 0.25
Received By jleech Date 2003-10-14 Time 16:42 Sent To E
Notes
2003-10-14 00:00:00PREFAB HOUSE NO PLUMBING PLAN REVIEW.
 WATER AND SEWER HOOK-UP ONLY

Review Stop Z ZONING
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By mmclean Date 2003-10-09 Time 10:06 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-10-09 00:00:0010/9/03 PASS PER ANGELLA JONES-VANN MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-10-03 Cont ID  
Sent By shernand Date 2003-10-07 Time 14:32 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-10-03 00:00:0010/3/03 DENIED, NEED LANDSCAPE PLAN 1
 SHADED TREE FOR EACH 1200SQ FT OF OPEN
 SPACE & 1 SCRUB FOR 500SQ FT OF OPEN
 SPACE CALLED CONTRACTOR PASS ON PLANS
 TO OTHER REVIEWERS MM