Plan Review Stops For Permit 03092019 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2004-05-03 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-05-03 |
Time |
13:20 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2004-05-03 |
Time |
13:20 |
Sent To |
|
|
Notes |
2004-05-03 00:00:00 | RELOCATE SHAFT 3,4,5&6 FLOORS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2004-02-26 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2004-02-26 |
Time |
12:24 |
Rev Time |
0.50 |
Received By |
jwitmer |
Date |
2004-02-26 |
Time |
12:24 |
Sent To |
|
|
Notes |
2004-02-26 00:00:00 | REVISION (EFIS) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2003-12-03 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-02-18 |
Time |
08:18 |
Rev Time |
3.50 |
Received By |
jwitmer |
Date |
2003-12-03 |
Time |
15:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-10-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2003-10-30 |
Time |
09:00 |
Rev Time |
2.00 |
Received By |
jwitmer |
Date |
2003-10-30 |
Time |
09:00 |
Sent To |
|
|
Notes |
2003-10-30 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 03092019 PHASE 3 | | ADD: 630 CLEARWATER PARK RD | | 3RD -6TH FLOORS | | CONT: THE WHITING-TURNER CO | | TEL: (954)776-0800 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | 1)1606.1.4(1) IN WIND BORNE DEBRIS | | REGIONS, EXTERIOR GLAZING THAT RECEIVES | | POSITIVE PRESSURE IN BUILDINGS SHALL BE | | ASSUMED TO BE OPENINGS UNLESS SUCH | | GLAZING IS IMPACT RESISTANT OR PROTECTED | | WITH AN IMPACT RESISTANT COVERING MEET- | | ING THE REQUIREMENTS OF SSTD 12, ASTM | | E 1886 AND ASTM E 1996 OR MIAMI-DADE. | | | | GLAZED OPENINGS LOCATED WITHIN 30 FT | | OF GRADE SHALL MEET THE REQUIREMENTS OF | | LARGE MISSLE TEST. | | FL BLD CODE 1606.1.5: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORT, SBCCI OR DADE COUNTY | | REPORT ARE ACCEPTED. MISSING ALL PRODUCT | | TESTING REPORTS. | | | | 2) 1707.4.4.2 TAPERED BUCKS: | | SHALL EXTEND BEYOND THE INTERIOR FACE | | OF THE WINDOW OR DOOR FRAME SUCH THAT | | FULL SUPPORT OF THE FRAME IS SUPPORTED. | | | | 3) 1707.4.3 EACH EXTERIOR DOOR | | ASSEMBLY NOT COVERED BY 1707.4.2 | | (GLAZED DOORS) SHALL BE LISTED AND TEST- | | ED FOR A PERIOD EQUAL TO THE QUANITY | | 3600/ V WHERE THE TIME PERIOD IS IN | | SECTIONS AND V IS IN MILES PER HR TAKEN | | FROM FIGURE 1606. THE TIME PERIOD SHALL | | ALSO INCLUDE A 10 SECOND PERIOD AT A | | LOAD EQUAL TO 1.5 TIMES THE DESIGN | | PRESSURE. DADE COUNTY & SBCCI REPORTS | | ARE ACCEPTED. | | | | 4)1707.4.5.1 MULLIONS OCCURRING | | BETWEEN INDIVIDUAL WINDOW AND GLASS | | DOOR ASSEMBLIES. TESTING REPORTS ARE | | REQUIRED BY AN APPROVED TESTING | | LABORATORY OR BE ENGINEERED. | | | | 5)1707.4.5.2 MULLIONS SHALL BE DESIGN- | | ED TO TRANSFER THE DESIGN PRESSURE LOADS | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES | | TO THE ROUGH OPENING SUBTRATE. | | | | 6)1204.2 SURROUNDING MATERIALS; | | THE WALLS & FLOORS OF ALL PUBLIC REST- | | ROOMS SHALL BE LINED WITH NONABSORBANT | | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE | | FLOOR. | | | | 7) EFIS SYSTEMS, EXTERIOR WALL COVERINGS | | ARETO COMPLY WITH 2603.6 (1-7). | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2004-03-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-03-08 |
Time |
13:54 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-03-08 |
Time |
13:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2004-01-28 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-02 |
Time |
10:00 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2004-01-28 |
Time |
09:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-12-02 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2004-01-20 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2003-12-02 |
Time |
15:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-10-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-10-16 |
Time |
14:52 |
Rev Time |
1.00 |
Received By |
dpalmer |
Date |
2003-10-16 |
Time |
14:52 |
Sent To |
|
|
Notes |
2003-10-16 00:00:00 | ************ UNSAT ****************** | | | | 1)NOTE: PLEASE SEE THAT THIS PHASE FOR | | FLRS 3-6 ALSO CONTAIN RISER DIAGRAM | | WHICH HAS NOTHING TO DO WITH ELECTRICAL | | PLANS SUBMITTED. | | PLEASE CLARIFY AND SEE NOTES UNDER | | PERMIT #03091207 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2004-01-20 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2004-01-20 |
Time |
13:47 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2004-01-20 |
Time |
13:47 |
Sent To |
E |
|
Notes |
2004-01-20 00:00:00 | REVISION DATED 01-10-04 SHEET E 250 | | PHASE 1A, 1B, 3 & 4 | | | | VISUAL STROBE DEVICES ARE TO REMAIN IN | | DEDICATED HANDICAP ROOMS |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2003-12-08 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-12-08 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-12-08 |
Time |
12:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2003-10-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-10-28 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-10-28 |
Time |
16:41 |
Sent To |
|
|
Notes |
2003-10-28 00:00:00 | 1) PLEASE EXPLAIN RATIONALE ON | | UNDERCUTTING ALL GUESTROOM ENTRY DOORS | | ON PAGE A0.20. | | | | 2) DECORATIVE EIFS STILL SHOWN ON | | ELEVATION DRAWINGS AND ON OTHER PLANS. | | PLEASE SEE APPENDIX F, ARCHITECTURAL | | TRIM LOCATED IN THE FIRE LIMITS. | | | | 3) BUILDING ADDRESS REQUIRED. | | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | 5) PROVIDE SEPARATE PLANS AND PERMITS | | FOR NEW BASE BUILDING AUDIO/VISUAL | | DEVICES PLANNED FOR HOTEL ROOMS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-03-02 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-03-02 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-03-02 |
Time |
10:00 |
Sent To |
E |
|
Notes |
2004-03-02 00:00:00 | TO DP DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-02-18 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-02-18 |
Time |
08:18 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-02-18 |
Time |
08:18 |
Sent To |
B |
|
Notes |
2004-02-18 00:00:00 | TO JW DESK/SUBMITALLS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2004-01-13 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-01-13 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-01-13 |
Time |
08:43 |
Sent To |
|
|
Notes |
2004-01-13 00:00:00 | TO COMM BD#25 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-11-14 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-05-05 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-11-14 |
Time |
14:16 |
Sent To |
|
|
Notes |
2003-11-14 00:00:00 | TO COMM BD#60/3 ROLLS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-11-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-11-03 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2003-10-01 |
Time |
09:40 |
Sent To |
|
|
Notes |
2003-10-01 00:00:00 | COMM BD#2/ON RACK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-11-24 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-11-24 |
Time |
16:09 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2003-11-24 |
Time |
16:09 |
Sent To |
|
|
Notes |
2003-11-24 00:00:00 | PLANS APPROVED 10-31-03 PHK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-11-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-10-31 |
Time |
16:01 |
Rev Time |
1.15 |
Received By |
pkrauss |
Date |
2003-10-31 |
Time |
16:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2003-12-05 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2003-12-05 |
Time |
11:25 |
Rev Time |
1.50 |
Received By |
pschmitz |
Date |
2003-12-05 |
Time |
15:00 |
Sent To |
|
|
Notes |
2003-12-05 00:00:00 | PROVISO: DIFFERENT CLASSES OF ACCOMMOD- | | ATIONS TO COMPLY WITH FBC 2001 CH 11 FOR | | THE VARIOUS CLASSES OF ACCOMMODATIIONS. | | PES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-10-27 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-10-27 |
Time |
14:00 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2003-10-24 |
Time |
18:49 |
Sent To |
|
|
Notes |
2003-10-27 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) THE FOLLOWING CLASSES OF SLEEPING | | ACCOMMODATIONS ARE ON THE PLANS, AND | | ACCESSIBILITY SHALL BE DISPERSED AMONG | | THE VARIOUS CLASSES PER SECTION 11-9.1.4 | | KING GUESTROOM, KING GUESTROOM WITH NEW | | CLOSET, KING GUESTROOM EXTENDED, DOUBLE | | DOUBLE GUESTROOM, DOUBLE DOUBLE GUEST- | | ROOM WITH NEW CLOSET, DOUBLE DOUBLE | | GUESTROOM EXTENDED, SUIT TYPES 1, 2, 3, | | AND 4, VIP SUITE, AND THE CONCIERGE | | LOUNGE. THE ONLY ACCESSIBLE UNITS ARE | | THE KING GUESTROOM AND THE DOUBLE- | | DOUBLE GUESTROOM. PLEASE CLAIRFY. | | 2) INDICATE LOCATION OF ALL UNITS REQ- | | UIRED TO BE ACCESSIBLE PER CODE BY ROOM | | NUMBER SO AS TO COMFIRM THE PROPER NUM- | | BER OF ROOMS WILL BE ACCESSIBLE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|