Plan Review Details - Permit 03092019
Plan Review Stops For Permit 03092019
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-05-03 Cont ID  
Sent By jwitmer Date 2004-05-03 Time 13:20 Rev Time 0.55
Received By jwitmer Date 2004-05-03 Time 13:20 Sent To  
Notes
2004-05-03 00:00:00RELOCATE SHAFT 3,4,5&6 FLOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-26 Cont ID  
Sent By jwitmer Date 2004-02-26 Time 12:24 Rev Time 0.50
Received By jwitmer Date 2004-02-26 Time 12:24 Sent To  
Notes
2004-02-26 00:00:00REVISION (EFIS)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-03 Cont ID  
Sent By csiegber Date 2004-02-18 Time 08:18 Rev Time 3.50
Received By jwitmer Date 2003-12-03 Time 15:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-30 Cont ID  
Sent By jwitmer Date 2003-10-30 Time 09:00 Rev Time 2.00
Received By jwitmer Date 2003-10-30 Time 09:00 Sent To  
Notes
2003-10-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03092019 PHASE 3
 ADD: 630 CLEARWATER PARK RD
 3RD -6TH FLOORS
 CONT: THE WHITING-TURNER CO
 TEL: (954)776-0800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING ALL PRODUCT
 TESTING REPORTS.
  
 2) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 3) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 4)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 5)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 6)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 7) EFIS SYSTEMS, EXTERIOR WALL COVERINGS
 ARETO COMPLY WITH 2603.6 (1-7).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 13:54 Rev Time 0.33
Received By dpalmer Date 2004-03-08 Time 13:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-03-02 Time 10:00 Rev Time 0.50
Received By dpalmer Date 2004-01-28 Time 09:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-02 Cont ID  
Sent By nmccray Date 2004-01-20 Time 13:48 Rev Time 0.00
Received By dpalmer Date 2003-12-02 Time 15:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-16 Cont ID  
Sent By dpalmer Date 2003-10-16 Time 14:52 Rev Time 1.00
Received By dpalmer Date 2003-10-16 Time 14:52 Sent To  
Notes
2003-10-16 00:00:00************ UNSAT ******************
  
 1)NOTE: PLEASE SEE THAT THIS PHASE FOR
 FLRS 3-6 ALSO CONTAIN RISER DIAGRAM
 WHICH HAS NOTHING TO DO WITH ELECTRICAL
 PLANS SUBMITTED.
 PLEASE CLARIFY AND SEE NOTES UNDER
 PERMIT #03091207
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-01-20 Cont ID  
Sent By nmccray Date 2004-01-20 Time 13:47 Rev Time 0.00
Received By nmccray Date 2004-01-20 Time 13:47 Sent To E
Notes
2004-01-20 00:00:00REVISION DATED 01-10-04 SHEET E 250
 PHASE 1A, 1B, 3 & 4
  
 VISUAL STROBE DEVICES ARE TO REMAIN IN
 DEDICATED HANDICAP ROOMS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-12-08 Cont ID  
Sent By mcarsill Date 2003-12-08 Time 12:29 Rev Time 0.00
Received By mcarsill Date 2003-12-08 Time 12:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-10-28 Cont ID  
Sent By mcarsill Date 2003-10-28 Time 16:41 Rev Time 0.00
Received By mcarsill Date 2003-10-28 Time 16:41 Sent To  
Notes
2003-10-28 00:00:001) PLEASE EXPLAIN RATIONALE ON
 UNDERCUTTING ALL GUESTROOM ENTRY DOORS
 ON PAGE A0.20.
  
 2) DECORATIVE EIFS STILL SHOWN ON
 ELEVATION DRAWINGS AND ON OTHER PLANS.
 PLEASE SEE APPENDIX F, ARCHITECTURAL
 TRIM LOCATED IN THE FIRE LIMITS.
  
 3) BUILDING ADDRESS REQUIRED.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 5) PROVIDE SEPARATE PLANS AND PERMITS
 FOR NEW BASE BUILDING AUDIO/VISUAL
 DEVICES PLANNED FOR HOTEL ROOMS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-03-02 Time 10:00 Rev Time 0.00
Received By csiegber Date 2004-03-02 Time 10:00 Sent To E
Notes
2004-03-02 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 08:18 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 08:18 Sent To B
Notes
2004-02-18 00:00:00TO JW DESK/SUBMITALLS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 08:43 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 08:43 Sent To  
Notes
2004-01-13 00:00:00TO COMM BD#25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-14 Cont ID  
Sent By csiegber Date 2004-05-05 Time 15:47 Rev Time 0.00
Received By csiegber Date 2003-11-14 Time 14:16 Sent To  
Notes
2003-11-14 00:00:00TO COMM BD#60/3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-03 Cont ID  
Sent By pkrauss Date 2003-11-03 Time 08:39 Rev Time 0.00
Received By pkrauss Date 2003-10-01 Time 09:40 Sent To  
Notes
2003-10-01 00:00:00COMM BD#2/ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 16:09 Rev Time 0.25
Received By pkrauss Date 2003-11-24 Time 16:09 Sent To  
Notes
2003-11-24 00:00:00PLANS APPROVED 10-31-03 PHK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-03 Cont ID  
Sent By pkrauss Date 2003-10-31 Time 16:01 Rev Time 1.15
Received By pkrauss Date 2003-10-31 Time 16:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-05 Cont ID  
Sent By pschmitz Date 2003-12-05 Time 11:25 Rev Time 1.50
Received By pschmitz Date 2003-12-05 Time 15:00 Sent To  
Notes
2003-12-05 00:00:00PROVISO: DIFFERENT CLASSES OF ACCOMMOD-
 ATIONS TO COMPLY WITH FBC 2001 CH 11 FOR
 THE VARIOUS CLASSES OF ACCOMMODATIIONS.
 PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-27 Cont ID  
Sent By kstevens Date 2003-10-27 Time 14:00 Rev Time 1.00
Received By kstevens Date 2003-10-24 Time 18:49 Sent To  
Notes
2003-10-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) THE FOLLOWING CLASSES OF SLEEPING
 ACCOMMODATIONS ARE ON THE PLANS, AND
 ACCESSIBILITY SHALL BE DISPERSED AMONG
 THE VARIOUS CLASSES PER SECTION 11-9.1.4
 KING GUESTROOM, KING GUESTROOM WITH NEW
 CLOSET, KING GUESTROOM EXTENDED, DOUBLE
 DOUBLE GUESTROOM, DOUBLE DOUBLE GUEST-
 ROOM WITH NEW CLOSET, DOUBLE DOUBLE
 GUESTROOM EXTENDED, SUIT TYPES 1, 2, 3,
 AND 4, VIP SUITE, AND THE CONCIERGE
 LOUNGE. THE ONLY ACCESSIBLE UNITS ARE
 THE KING GUESTROOM AND THE DOUBLE-
 DOUBLE GUESTROOM. PLEASE CLAIRFY.
 2) INDICATE LOCATION OF ALL UNITS REQ-
 UIRED TO BE ACCESSIBLE PER CODE BY ROOM
 NUMBER SO AS TO COMFIRM THE PROPER NUM-
 BER OF ROOMS WILL BE ACCESSIBLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]