Plan Review Details - Permit 03091689
Plan Review Stops For Permit 03091689
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-08 Cont ID  
Sent By rmcdouga Date 2003-12-08 Time 09:47 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-12-08 00:00:00PROVISO
  
 1)SUBMIT THE MANUFACTURER'S INSTALLATION
 DRAWINGS FOR THE STORM PANELS. SPECIFY
 THE MOUNT TYPE AND FASTENER TYPE. SUBMIT
 REVISED INSTALLATION SCHEDULE INDICATING
 THAT THE FRONT FRENCH DOORS WHICH ARE
 IMPACT RESISTANT IN ORDER TO COMPLY WITH
 EGRESS (FBC 1005.4.5) ARE NOT TO BE
 SHUTTERED. THIS IS REQUIRED TO BE
 SUBMITTED FOR REVIEW PRIOR TO INSTALLING
 STORM PANELS.
  
 (2) SUBMIT UL LISTING NUMBER FOR GAS BBQ
 ON THE COVERED PORCH BEFORE INSTALLING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-21 Cont ID  
Sent By dpalmer Date 2003-12-04 Time 07:50 Rev Time 3.00
Received By rmcdouga Date 2003-10-21 Time 13:48 Sent To  
Notes
2003-10-21 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A PAID RECEIPT FOR THE IMPACT
 FEES.
  
 3) SUBMIT A SUB-SURFACE SOIL REPORT
 INDICATING THE SAFE BEARING CAPACITY OF
 THE SOIL AS REQUIRED BY FBC 1804.2.2.
  
 4) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT. IN
 ORDER TO TAKE THE CEILING FAN CREDIT ON
 THE ENERGY CALCS, A MINIMUM OF ONE
 CEILING FAN IS REQUIRED IN ALL PRIMARY
 LIVING AREAS. THERE IS NO CEILNG FAN
 SPECIFIED IN THE LIVING ROOM. PLEASE
 INDICATE THE REQUIRED SIZES OF THE FANS
 ON THE PLANS. SEE FBC 13-607.2.A.3.1 AND
 TABLE 6-6.
  
 5) SUBMIT A SIGNED AND SEALED SURVEY.
  
 6) INDICATE ON THE PLANS THE SQFT
 BREAKDOWN OF THE STRUCTURE. (A/C AREA,
 GARAGE, COVERED PORCHES, ETC.)
  
 7) THE GARAGE BUCK DETAIL 3B ON 4S4
 REQUIRES A MINIMUM OF 8X16 BLOCK WITH
 TWO FILLED CELLS WITH ONE #5 ON EACH
 SIDE OF THE GARAGE OPENINGS. THE PLAN
 SPECIFIES ONE REINFORCED FILLED CELL ON
 EACH SIDE OF THE OPENINGS. PLEASE
 CORRECT.
  
 8) THE FOUNDATION PLAN ON SHEET 4
 SPECIFIES WIRE MESH IN THE SLAB AND
 DETAIL 1 ON 4S1 SPECIFIES FIBER MESH
 CONCRETE FOR THE SLAB. PLEASE CLARIFY.
  
 9) THE SECTION AT THE GARAGE DOOR ON 4
 IS MISLABELED. IT SHOULD BE LABELED 3
 ON 4S1.
  
 10) DETAIL 8 ON 4S1 FOR THE SECTION AT
 THE INTERIOR GARAGE WALL REFERENCED ON
 SHEET 4 HAS BEEN CROSSED OUT. PLEASE
 CORRECT.
  
 11) PLEASE MAKE CORRECTIONS TO CONNECTOR
 CHART ON 5B. THE 775# UPLIFT VALUE IS
 FOR 10D NAILS. THE VALUE FOR 10D X 1-1/2
 NAILS 735#. THE USP TAPR216 CONNECTOR IS
 NO LONGER LISTED IN THE CATALOG. SPECIFY
 A CURRENT CONNECTOR. THE LONGER HTT 22
 STRAP WILL BE REQUIRED FOR THE (32) 10D
 NAILS FOR A 5370# UPLIFT. THE UPLIFT FOR
 THE NFM6X16 HAS BEEN REVISED TO 1325# IN
 THE 2003 USP CATALOG. PLEASE REVISE.
 SEE 2003 USP CATALOG.
  
 12) PLEASE PROVIDE MANUFACTURER'S SPECS.
 AND LISTING INFORMATION FOR GAS COOK TOP
 ON COVERED PATIO.
  
 13) SUBMIT MANUFACTURER'S SPECIFICATIONS
 INDICATING THE HORIZONTAL SLIDING
 WINDOW IN BEDROOM #4 MEETS THE EGRESS
 REQUIREMENTS OF FBC 1005.4.
  
 14)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 15) INDICATE THE LOCATION AND SIZE OF
 THE ATTIC ACCESS REQUIRED BY FBC 2309.6.
  
 16) SUBMIT THE ENGINEERED INSTALLATION
 DRAWINGS FOR THE STORM PANELS. SUBMIT A
 KEY PLAN THAT CORRESPONDS TO THE
 INSTALLATION SCHEDULE. THE NUMBERS AND
 SIZES ON THE SHUTTER SCHEDULE DOES NOT
 CORRESPOND WITH THE SHUTTER SCHEDULE ON
 4S4.
  
 17) SUBMIT SITE SPECIFIC ENGINEERING W/
 DETAILED SHOP DRAWINGS, SPECIFICATIONS
 AND RATIONAL ANALYSIS AND/OR TEST DATA
 ASSURING SAFE PERFORMANCE FOR THE BUTT
 GLASS ASSEMBLY IN THE MORNING ROOM. THE
 PRODUCT APPROVAL FOR THE STORE FRONT
 THAT WAS SUBMITTED IS NOT FOR A BUTT
 GLASS ASSEMBLY.
  
 18) THE PRODUCT APPROVAL SUBMITTED FOR
 THE HORIZONTAL SLIDING WINDOWS DOES NOT
 LIST A THREE PANEL WINDOW AS SHOWN FOR
 BEDROOM #4. SUBMIT APPROPRIATE PRODUCT
 APPROVAL.
  
 19) THE REQUIRED WINDLOAD PRESSURES FOR
 THE 36SH WINDOWS IN THE MASTER BEDROOM
 EXCEED THE NEGATIVE PRESSURE OF -43.10
 IN THE PRODUCT APPROVAL FOR 3/16"
 ANNEALED GLASS. SUBMIT APPROPRIATE
 PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By dpalmer Date 2003-12-04 Time 07:50 Rev Time 0.50
Received By dpalmer Date 2003-12-04 Time 07:36 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-02 Cont ID  
Sent By pkrauss Date 2003-12-03 Time 15:12 Rev Time 1.00
Received By dpalmer Date 2003-10-02 Time 17:44 Sent To M
Notes
2003-10-02 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE FBC/ADMIN 104.2.1,
 PLEASE PROVIDE INFORMATION FOR PERSON
 RESPONSIBLE FOR PLANS.
  
 2)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 FOR BOTH PANELS A&B. PLEASE LIST AWG AND
 OCP FOR ALL CIRCUITS.PLEASE LIST ALL
 MIN CIRCUITS.215.5
 3)NOTE: PLEASE LIST THE REQ'D DEDICATED
 BATH(S) CIRCUIT(S) 210.52D/ 210.11C3
  
 4)NOTE: PLEASE LIST ALL ARC FAULT
 PROTECTED CIRCUITS. 210.12
 IT WAS NOTED ON PLAN.
  
 5)NOTE: PLEASE SEE THAT AS OF JULY 1ST,
 2003 WE ARE UNDE RTHE 2002 NEC.
  
 6)NOTE: PLEASE RELOCATE SD IN MASTER
 BEDROOM HALL INTO BEDROOM AREA.
 NFPA-72 8-1.4.2
  
 7)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 BEDROOM #2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-11-24 Time 12:46 Rev Time 0.00
Received By csiegber Date 2003-11-24 Time 12:46 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-29 Cont ID  
Sent By dbaxter Date 2003-09-29 Time 15:39 Rev Time 0.00
Received By dbaxter Date 2003-09-29 Time 15:39 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-25 Cont ID  
Sent By mmclean Date 2003-09-29 Time 12:39 Rev Time 0.00
Received By csiegber Date 2003-09-25 Time 14:30 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-03 Cont ID  
Sent By pkrauss Date 2003-12-03 Time 15:11 Rev Time 0.33
Received By pkrauss Date 2003-12-03 Time 14:51 Sent To E
Notes
2003-12-03 00:00:00PLEASE NOTE THE M-1 SHEET DOES NOT
 MATCH THE FLOOR PLAN INDICATED ON THE
 STRUCURAL OR FLOOR PLAN INDICATED ON
 SHEET 5.PLAN IS REVERSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-10-07 Cont ID  
Sent By csiegber Date 2003-11-24 Time 12:46 Rev Time 0.50
Received By hmoser Date 2003-10-07 Time 16:45 Sent To P
Notes
2003-10-07 00:00:00NO PLANS
 HAROLD MOSER

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-10-08 Cont ID  
Sent By hmoser Date 2003-10-07 Time 16:46 Rev Time 0.33
Received By jleech Date 2003-10-08 Time 16:35 Sent To B
Notes
2003-10-08 00:00:00NOT ENOUGH INFORMATION TO DO A PLUMBING
 PLAN REVIEW. NO RISER DIAGRAM.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-25 Time 14:30 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***