Plan Review Details - Permit 03091348
Plan Review Stops For Permit 03091348
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-01-12 Cont ID  
Sent By rbrown Date 2004-01-12 Time 15:58 Rev Time 0.00
Received By rbrown Date 2004-01-12 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-21 Cont ID  
Sent By rbrown Date 2003-11-21 Time 11:43 Rev Time 0.00
Received By rbrown Date 2003-11-21 Time 11:43 Sent To  
Notes
2003-11-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 10/9/03:
  
 2) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 301.3STORAGE.ANNOTATE THE PLANS
 TO SPECIFY THE MATERIALS THAT ARE TO BE
 STORED.SEE FBC 308 FOR MATERIALS AND
 QUANTITIES THAT ARE CLASSIFIED AS
 HAZARDOUS OCCUPANCY.
  
 3) FBC* F102.2.4ROOF COVERINGS IN THE
 FIRE DISTRICT.THE AMENDMENT MADE TO
 DRAWING SHEET SP1 UNDER MEMBRANE
 ROOFING, ITEM 4, IS NOTED.SUBMIT
 DOCUMENTATION TO SHOW THAT THE PROPOSED
 HONEYWELL INT'L MODIFIED BITUMEN ROOF
 COVERING (SUBMITTED PRODUCT APPROVAL
 NOA# 02-0129.12) CONFORMS TO CLASS A OR
 CLASS B RATING REQUIREMENTS FOR ROOF
 COVERINGS IN THE FIRE DISTRICT.
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL IN THE CLEAR LAKE VICINITY.SUBMIT
 A GEOTECHNICAL REPORT TO VERIFY THE SAFE
 BEARING CAPACITY OF THE SOIL.
  
 7) ROOF COVERING PRODUCT APPROVAL.SEE
 COMMENT (4) ABOVE.
  
 8) PERSONNEL DOOR PRODUCT APPROVAL.THE
 SUBMITTED INTERTEK TESTING SERVICES TEST
 REPORTS MUST BE ACCOMPANIED BY SITE-
 SPECIFIC ENGINEERING SIGNED BY THE
 ENGINEER OF RECORD (SEE ATTACHED
 PRODUCT APPROVAL SUBMITTAL FORM) BEFORE
 THEY CAN BE ACCEPTED IN LIEU OF PRODUCT
 APPROVALS.ALTERNATIVELY, SUBMIT A
 MIAMI-DADE PRODUCT APPROVAL OR SBCCI/ICC
 EVALUATION REPORT FOR THE PROPOSED DOORS
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS/SIZES ARE TO
 BE USED.
  
 9) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-11-18 Time 15:19 Rev Time 0.00
Received By rbrown Date 2003-10-09 Time 11:43 Sent To  
Notes
2003-10-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 1027.1STORAGE ROOM EXIT.A
 MINIMUM OF TWO EXITS FROM THE STORAGE
 ROOM ARE REQUIRED (REF ALSO: 1004.1.2).
 AT LEAST TWO OF THE EXITS SHALL BE
 SEPARATED BY A DISTANCE EQUAL TO NOT
 LESS THAN 1/2 THE DIAGONAL DIMENSION OF
 THE ROOM (REF: 1004.1.4).
  
 2) FBC 301.3STORAGE.ANNOTATE THE
 PLANS TO SPECIFY THE MATERIALS THAT ARE
 TO BE STORED.SEE FBC 308 FOR MATERIALS
 AND QUANTITIES THAT ARE CLASSIFIED AS
 HAZARDOUS OCCUPANCY.
  
 3) AMEND SHEET SP-1 AS FOLLOWS:
 (A) GENERAL NOTE #3 REFERS TO "....2001
 FLORIDA BUILDING CODE, WITH 2002
 AMENDMENTS."THE REFERENCE SHALL ALSO
 INCLUDE THE 2003 AMENDMENTS (EFFECTIVE
 JUNE 30, 2003).
 (B) THE ABOVE COMMENT ALSO APPLIES TO
 THE BUILDING CODE ANALYSIS TABLE.AMEND
 THE TABLE.
 (C) THE BUILDING CODE ANALYSIS TABLE
 STATES "FIRE DISTRICT:N/A".THE
 BUILDING WILL BE IN THE FIRE DISTRICT.
 AMEND THE TABLE.
  
 4) FBC* F102.2.4FIRE DISTRICT.
 ROOF COVERING IN THE FIRE DISTRICT SHALL
 CONFORM TO THE REQUIREMENTS OF CLASS A
 OR CLASS B ROOF COVERINGS AS DEFINED IN
 1505.ANNOTATE THE PLANS TO STATE THE
 REQUIRED FIRE CLASSIFICATION FOR THE
 ROOF COVERING.
  
 5) FBC 1804.1.3 DETAIL 2/S-3. THE BOTTOM
 OF FOUNDATIONS SHALL EXTEND NO LESS THAN
 12 INCHES (305 MM) BELOW FINISH GRADE.
 ANNOTATE THE PLANS TO SHOW THE REQUIRED
 MINIMUM DEPTH.
  
 6) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 7) SUBMIT TWO COPIES OF A PRODUCT
 APPROVAL FOR THE PROPOSED BUILT UP
 ROOFING SYSTEM, OR A SEPARATE ROOFING
 PERMIT, AND FEES, WILL BE REQUIRED.
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS ARE TO BE USED
  
 8) SUBMIT TWO COPIES OF A PRODUCT
 APPROVAL FOR THE PERSONNEL DOORS AND THE
 SECTIONAL DOORS.
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS/SIZES ARE TO
 BE USED.
  
 9) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 11:26 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 11:26 Sent To  
Notes
2004-05-08 00:00:00**** REDLINED *****
  
 1)NOTE: NEUTRAL CONDUCTOR FROM METER TO
 277/480V PANEL SHOWN AS #4 WHICH IS
 RATED FOR 85'S PER 310.16 75 DEGREE
 COL.
 PLEASE SEE NEUTRAL LOAD EXCEEDS RATING
 OF AWG. LOAD SHOWN AT 92.5A'S.
  
 PLANS NOTED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-07 Time 15:35 Rev Time 1.50
Received By dpalmer Date 2004-04-27 Time 19:26 Sent To  
Notes
2004-05-05 00:00:00************* UNSAT ***************
  
 PLEASE SEE RISER DIAGRAM NOW SUBMITTED
 HAS COMPLETELY CHANGED FROM ORIG SET.
  
 PLEASE SEE ATTACH INSPECTIONS.
  
 1)NOTE: PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING CONDUCTORS ARE TO
 BE INSTALLED BETWEEN METEE AND THE FIRST
 MEANS OF DISC.
  
 2)NOTE: RISER IS NOW SHOWING LINE AND
 LOAD BEING INSTALLED IN THE METER????
  
 3)NOTE: PLEASE SEE PLANS ARE NOW SHOWING
 A 54KW WATER HEATER. WHERE IS THIS WH
 BEING FED FROM. THERE IS A WH SHOWN
 ON 100A 120/240 SINGLE PHASE PANEL, YET
 OCP IS SHOWN AS 20A1-POLE?
 THIS WATER HEATER IS RATED FOR 225A'S
 ON A 100A PANEL??
 PLEASE ALSO SEE 422.1,422.13 ETC FOR OCP
  
 4)NOTE: PLEASE BE SURE TO SHOW ALL
 EQUIPMENT AND CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2004-04-27 00:00:00ON HOLD, WAITING FOR TO REVIEW AND GO
 OVER PLANS W/ ELECTRICAL INSPECTOR.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-30 Cont ID  
Sent By csiegber Date 2004-04-26 Time 09:06 Rev Time 0.50
Received By dpalmer Date 2003-12-30 Time 06:51 Sent To  
Notes
2003-12-30 00:00:00******** NOTES REDLINED ***
  
 MAX OCP FOR TRANSFORMER TO BE SET PER
 450.3B OF THE 2002 NEC. (125%)
 REMOVED OLD/VOIDED ELECTRICAL SHEETS AS
 REQUESTED ON PREVIOUS REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-04 Cont ID  
Sent By dpalmer Date 2003-11-04 Time 14:56 Rev Time 0.50
Received By dpalmer Date 2003-11-04 Time 14:56 Sent To  
Notes
2003-11-04 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE THAT MOST NOTES FROM
 FIRST REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE CORRELATE RISER/PANEL SCHEDULES
 ETC.
 PLEASE SEE ORIG NOTES.
  
 2)NOTE: PLEASE SEE NOW ONLY SHEET E-2
 IS SIGNED AND SEALED BY A PE. PLEASE
 SEE FS AND FAC AND FBC, ALL E-SHEETS
 MUST BE SIGNED,DATED AND SEALED BY PE.
 471.003,61G15-23.002, 104.4.1.3
  
 3)NOTE: PLEASE ALSO SEE THAT COMPLETE
 TITLE BLOCKS ARE REQ'F OR ENGINEER OF
 RECORD PER FAC 61G15-23.002, AND ALL
 INFORMATION AS SET FORTH.
  
 4)NOTE; PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) FOR PLANS REVIEW WITH
 THE SAME COMMENTS.THIS IS BEING NOTED
 AFTER SECOND REVIEW AND NEEDS TO HAVE
 ALL COMMENTS ADDRESSED.
  
 PLEASE REMOVE ALL OLD/ VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 PLEASE SEE COMMENTS FROM OTHERE REVIEWER
 -S THAT MAY HAVE AN AFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-06 Cont ID  
Sent By dpalmer Date 2003-10-06 Time 06:36 Rev Time 0.75
Received By dpalmer Date 2003-10-06 Time 06:36 Sent To  
Notes
2003-10-06 00:00:00************** UNSAT *******************
  
 1)NOTE: PLANS REQ'D TO BE SIGNED, DATED
 AND SEALED BY AN ENGINEER. PER FS 471
 AND FAC 553.79(6)(A) FOR 277/480V
 SYSTEMS.
  
 2)NOTE: PLEASE SHOW COMPLETE CONNECTIONS
 FOR GROUNDING ELECTRODE SYSTEM AND TRANS
 -FORMER. 250.50 AND 250.30
  
 3)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 CONDUCTORS FOR X-FORMER FEED WITH RISER
 DIAGRAM. ONE SHOWS # 6'S AND OTHER SHOWS
 #8.
  
 4)NOTE: PLEASE SPECIFY WHAT MATERIALS
 AND/OR ANY CLASS LOCATIONS FOR STORAGE
 AREA. PLEASE SEE 384.7/ 110.26 ALSO.
 AREA ABOUT ELECTRICAL EQUIPMENT SHOULD
 ALSO HAVE FLR AREA STRIPED FOR REQ'D
 CLEARENCES TO REMAIN.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-10-09 Cont ID  
Sent By mamini Date 2003-10-09 Time 16:39 Rev Time 0.00
Received By mamini Date 2003-10-09 Time 16:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-20 Cont ID  
Sent By nmccray Date 2003-11-20 Time 14:51 Rev Time 0.00
Received By nmccray Date 2003-11-20 Time 14:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-30 Cont ID  
Sent By nmccray Date 2003-09-30 Time 14:13 Rev Time 0.00
Received By nmccray Date 2003-09-30 Time 14:13 Sent To  
Notes
2003-09-30 00:00:001) WHAT WILL BE THE CLASSIFICATION OF
 HAZARD OF CONTENTS FOR THE STORAGE AREA,
 LOW, ORDINARY OR HIGH.
  
 2) INDUSTRIAL OR STORAGE OCCUPANCIES ARE
 REQUIRED TO HAVE NOT LESS THAN TWO
 SEPARATE MEANS OF EGRESS AS REMOTELY
 LOCATED FROM EACH OTHER AS PRACTICABLE.
 UNLESS IT'S MEET THE EXCEPTIONS.
  
 3) INTERIOR WALL AND CEILING FINISH
 CLASSIFICATION SHALL BE CLASS "A" CLASS
 "B" OR CLASS "C".
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-05-07 Cont ID  
Sent By csiegber Date 2004-05-07 Time 15:35 Rev Time 0.00
Received By csiegber Date 2004-05-07 Time 15:35 Sent To E
Notes
2004-05-07 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-04-26 Time 09:06 Rev Time 0.00
Received By csiegber Date 2004-04-26 Time 09:06 Sent To E
Notes
2004-04-26 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 08:53 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 08:53 Sent To  
Notes
2003-12-17 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-11-18 Cont ID  
Sent By csiegber Date 2003-11-18 Time 15:18 Rev Time 0.00
Received By csiegber Date 2003-11-18 Time 15:18 Sent To B
Notes
2003-11-18 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-14 Cont ID  
Sent By csiegber Date 2003-11-14 Time 16:36 Rev Time 0.00
Received By csiegber Date 2003-11-14 Time 16:36 Sent To  
Notes
2003-11-14 00:00:00TO COMM BD#25

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-04 Time 10:33 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 10:33 Sent To  
Notes
2003-11-04 00:00:00TO COMM BD#63

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-24 Time 14:30 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 14:30 Sent To  
Notes
2003-09-24 00:00:00TO COMM BD #22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-23 Time 08:31 Rev Time 0.00
Received By csiegber Date 2003-09-23 Time 08:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-01-06 Cont ID  
Sent By pkrauss Date 2004-01-06 Time 08:00 Rev Time 0.30
Received By pkrauss Date 2004-01-06 Time 07:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 15:09 Rev Time 0.40
Received By pkrauss Date 2003-11-24 Time 15:09 Sent To  
Notes
2003-11-24 00:00:00PROVISO:
 SEE BUILDING PLAN REVIEW NOTE #2.
 APPROVAL FOR MECHANICAL REVIEW IS NOT
 APPROVAL FOR "HAZARDOUS" OCCUPANCY.SEE
 2001 FBC(M) 510 FOR REQUIREMENTS FOR
 HAZARDOUS EXHAUST.RESUBMIT REVISED
 PLANS SHOULD THIS BE CLASSIFIED AS
 HAZARDOUS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-08 Cont ID  
Sent By pkrauss Date 2003-10-08 Time 14:30 Rev Time 0.35
Received By pkrauss Date 2003-10-08 Time 14:29 Sent To  
Notes
2003-10-08 00:00:00DENIED:
 1.PLEASE PROVIDE INFORMATION AS TO
 WHAT WILL BE KEPT IN THE "STORAGE AREA".
 (CHEMICALS, CLEANERS?)
  
 2.PLEASE NOTE THE LOCATION OF THE
 EXHAUST FAN IN RELATION TO THE DOOR.
 AS PER 2001 FBC(M) 401.4.1.
  
 3.EXHAUST SHALL NOT BE DIRECTED ONTO
 WALKWAYS, 2001 FBC(M) 401.5.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-11-19 Cont ID  
Sent By kstevens Date 2003-11-19 Time 10:22 Rev Time 0.50
Received By kstevens Date 2003-11-18 Time 18:55 Sent To  
Notes
2003-11-19 00:00:00PASSED/PROVISO-ALL PIPING TO FLOOR
 DRAINS TO BE 4"

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-06 Cont ID  
Sent By kstevens Date 2003-10-06 Time 15:50 Rev Time 1.00
Received By kstevens Date 2003-10-06 Time 15:49 Sent To  
Notes
2003-10-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SUBMIT A SANITARY RISER DIAGRAM (ISO-
 METRIC). SHOW ALL PIPE SIZES, VENTS ECT.
 2) SUBMIT A PLUMBING LAYOUT FOR SHEET
 P1
 3) SUBMIT A WATER RISER DIAGRAM. SHOW
 ALL PIPE SIZES, WATER HAMMER ARRESTORS,
 WHERE WATER CONNECTS TO SERVICE ECT.
 4) CONTACT R. COMPO, ENVIRONMENTAL COM-
 PLIANCE TO DETERMINE IF A OIL/SAND INTER
 CEPTOR IS REQUIRED.
 5) INDICATE TYPE AND QUANTITY OF MATER-
 IAL TO BE STORED IN STORAGE ROOM.
 6) PIPING SCHEMATIC INDICATES THAT THE
 WATER HEATER IS A GAS WATER HEATER. THE
 FOLLOWING INFORMATION WILL BE REQUIRED
 FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-23 Time 08:31 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***