Plan Review Stops For Permit 03091212 |
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-09-23 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-09-23 |
Time |
10:32 |
Rev Time |
0.33 |
Received By |
pkrauss |
Date |
2003-09-23 |
Time |
10:31 |
Sent To |
|
|
Notes |
2003-09-23 00:00:00 | PROVISO: | | PLEASE NOTE, REVISION TO THE 2001 | | FBC(M) 601.4, EFFECTIVE JUNE 30,2003: | | | | BALANCED AIR RETURN - RETURN/TRANSFER | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM ITS SERVING & THE | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. | | | | 2001 FBC(M)402.3.1(REVISED JUNE 30,2003) | | BATHROOMS SHALL HAVE A WINDOW WITH A | | MINIMUM OF 3 SQ FT CLEAR OPENING OR HAVE | | MECHANICAL VENTILATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|