Plan Review Details - Permit 03091208
Plan Review Stops For Permit 03091208
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-17 Cont ID  
Sent By jwitmer Date 2004-06-17 Time 13:40 Rev Time 0.33
Received By jwitmer Date 2004-06-17 Time 13:40 Sent To PC
Notes
2004-06-17 00:00:00CHANDELIER LOAD CALCULATIONS, OK JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-04-02 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 13:25 Rev Time 0.50
Received By jwitmer Date 2004-04-02 Time 14:11 Sent To  
Notes
2004-04-02 00:00:00REVISION: 4-02-04 ADD FIRE RATED PARTI-
 TION & DOORS FOR EGRESS CORRIDOR PROTEC-
 TION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 09:15 Rev Time 0.50
Received By jwitmer Date 2004-02-26 Time 12:22 Sent To  
Notes
2004-02-26 00:00:00REVISION (EFIS)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-02 Cont ID  
Sent By csiegber Date 2004-02-18 Time 08:19 Rev Time 4.50
Received By jwitmer Date 2003-12-02 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By jwitmer Date 2003-10-28 Time 16:37 Rev Time 2.00
Received By jwitmer Date 2003-10-28 Time 16:37 Sent To  
Notes
2003-10-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03091208
 FIRST FLOOR PUBLIC AREAS
 ADD: 630 CLEARWATER PARK RD
  
 CONT: THE WHITING-TURNER CONT CO
 TEL: (954)776-0800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) WINDOWS
 B) MULLIONS
 C) EXTERIOR DOORS, GLAZED & SOLID
 D) OVERHEAD ROLL UP
 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST. PROVIDE EITHER
 TESTING FOR LARGE MISSLE IMPACT GLAZING
 OR STORM SHUTTERS, SEE CITY INTERPRETA-
 TION FOR LARGE PROJECTS!
  
 2) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 3) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 4)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 5)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 6)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 7) EFIS SYSTEMS, EXTERIOR WALL COVERING:
 ARE TO COMPLY WITH 2603.6 (1-7).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 09:55 Rev Time 0.10
Received By dpalmer Date 2005-06-13 Time 09:55 Sent To  
Notes
2005-06-13 00:00:00NO REVIEW TO BE DONE, CO ISSUED.
 PLANS NOT A SUBMITTAL.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-02-02 Cont ID  
Sent By dpalmer Date 2005-02-02 Time 13:31 Rev Time 0.50
Received By dpalmer Date 2005-02-02 Time 13:31 Sent To  
Notes
2005-02-02 00:00:00*********** NOTES ******************
  
 1)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 ON EMDP.
 PLEASE ALSO PROVIDE PANEL SCHEDULE FOR
 EMDP, INCLUDING OCP, ETC.
 215.5/220
  
 2)NOTE: PLEASE VERIFY RISER INDICATES
 "NO LOAD " SHOWN ON ON GENERATOR?
 PLEASE CLARIFY THIS NOTE.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 15:47 Rev Time 1.00
Received By dpalmer Date 2004-03-08 Time 15:47 Sent To  
Notes
2004-03-08 00:00:00REDLINED REV'S ON PLANS AS OK.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-02-25 Time 15:55 Rev Time 1.00
Received By btrobaug Date 2004-01-16 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-16 Time 07:49 Rev Time 1.00
Received By dpalmer Date 2004-01-12 Time 09:27 Sent To  
Notes
2004-01-12 00:00:00************UNSAT *****************
  
 PLEASE SEE NEW SHEET E400 IS NOW SHOWING
 TRANSFORMER GROUNDING DETAIL, HOWEVER
 NO GROUNDING/BONDING CONDUCTOR SIZES
 ARE SHOWN?
 PLEASE SEE 250.30, A-D
  
 PLEASE ADJUST E-400.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-02 Cont ID  
Sent By csiegber Date 2003-12-30 Time 13:25 Rev Time 3.00
Received By dpalmer Date 2003-12-02 Time 16:37 Sent To  
Notes
2003-12-02 00:00:00************ PROVISO/ NOTES *******
  
 1)NOTE: PLEASE SEE THAT SHEET E-400 HAS
 NOT BEEN CHANGED OUT TO INCLUDE NEW
 REVISED SHEET WITH TRASNFORMER GROUNDING
 DETAIL.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR NEW PANELS AND ALL CONTINUOUAS LOADS
 AT 125%. LOADS ARE NOW SHOWN AS CONNECT-
 ED LOADS W/OUT SHOWING CONTINUOUS LOAD
 FACTOR. 215.3,230.42 ETC
  
 3)NOTE: IT HAS BEEN NOTED FOR CONTRACTOR
 TO PROVIDE LOAD CALCULATIONS AND REVISED
 PANEL SCHEDULES AT COMPLETION OF WORK
 IN ORDER TO VERIFY WEATHER OR NOT PANELS
 ARE OVERLOADED. PLEASE BE INFORMED:
 THIS WILL NOT BE PERMITTED AND COMPLETE
 LOAD CALCULATIONS AND CORRELATING PANEL
 SCHEDULES WITH CORRELATING CIRCUIT #`S
 WILL BE REQ'D BEFORE ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. THESE MUST BE
 SUBMITTED FOR REVIEW.
 NEC 215.5, 215.3, 220.
 DUE TO THE MANY ITEMS BEING ADDED TO
 BLDG OVER THE YEARS AND THE AGE OF
 EXISTING PANELS. THERE IS SOME CONCERN
 OVER EXISTING LOADS ON PANELS.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-25 Cont ID  
Sent By btrobaug Date 2003-11-25 Time 10:59 Rev Time 2.00
Received By btrobaug Date 2003-11-20 Time 16:31 Sent To  
Notes
2003-11-25 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} THE REFERENCES TO A GENERATOR BACKED
 SYSTEM ON E-001 ARE NOT SHOWN ON THE
 RISER DIAGRAM. THE PLAN ALSO SHOWS BOTH
 HIGH AND LOW VOLTAGE LIGHTS ON THE
 EMERGENCY SYSTEM.PLEASE PROVIDE DETAILS
 OF THOSE SYSTEMS.(EMERGENCY).
  
 2} RESPONSE 1C REGARDING THE CONTRACTOR
 TO TAKE LOAD READINGS "AT THE COMPLETION
 OF WORK TO ENSURE THAT PANELS ARE NOT
 OVERLOADED" IS UNACCEPTABLE. THE DESIGN
 PROFESSIONAL SHALL DETERMINE THAT
 PANELS ARE NOT OVERLOADED PRIOR TO
 BEGINNING WORK.
  
 3} PLEASE SEE NOTE #2 FROM LAST REVIEW.
 VERIFY CIRCUIT NUMBERS IN THE PANELS AND
 ON PLAN. LABEL THE CIRCUITS SO THAT
 LOADS CAN BE CORRECTLY CALCULATED.
  
 4} THE "ESTIMATED LOADS" ON THE
 CALCULATIONS DO NOT REFLECT CONTINUOUS
 AND NONCONTINUOUS LOADS PER
 210.19,215.2,215.3, 220.3 OR
 220.3(B)(4).REFER TO WATTAGES OF
 RECESSED LUMINAIRES ON SHEET E-002.
  
 5} PLEASE SUPPLY A CONTROL DETAIL
 SHOWING HOW THE "RELAY" FOR THE
 EMERGENCY LIGHTING WILL WORK IN
 CONJUNTION WITH SWITCHES AND DIMMERS
 SHOWN CONTROLLING EMERGENCY FIXTURES ON
 SHEET E-150.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-21 Cont ID  
Sent By dpalmer Date 2003-10-21 Time 11:46 Rev Time 1.00
Received By dpalmer Date 2003-10-21 Time 11:46 Sent To  
Notes
2003-10-21 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE ALSO SEE NOTES UNDER
 #03080042 WHICH WAS IN FOR PLAN REVIEW.
  
 2)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH PANEL SCHEDULE(S) PLEASE SEE
 THAT PANEL SHOWS CIRCUITS 1-?
  
 3)NOTE: PLEASE SEE COMMENTS UNDER PERMIT
 #03092018 FOR RISER DIAGRAM COMMENTS.
 EACH PHASE SEEMS TO HAVE SUBMITTED SAME
 RISER DIAGRAM.
 PLEASE CORRELATE ALL PHASES AND PLANS.
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS
 FOR REVIEW AND STAMPING. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-11-03 Cont ID  
Sent By pkrauss Date 2003-11-03 Time 08:35 Rev Time 0.00
Received By pkrauss Date 2003-11-03 Time 08:35 Sent To  
Notes
2003-11-03 00:00:00APPROVED PER ASST. FIRE MARSHAL MIKE
 CARSILLO

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 14:40 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 14:40 Sent To E
Notes
2005-05-24 00:00:00TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-01-31 Cont ID  
Sent By mjacobs Date 2005-01-31 Time 14:43 Rev Time 0.00
Received By mjacobs Date 2005-01-31 Time 14:43 Sent To E
Notes
2005-01-31 00:00:00TO "DP" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 13:17 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 13:17 Sent To B
Notes
2004-06-15 00:00:00TO JW DESK CHANDLIER SUPPORT

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 09:15 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 09:15 Sent To B
Notes
2004-03-26 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-03-02 Time 09:57 Rev Time 0.00
Received By csiegber Date 2004-03-02 Time 09:57 Sent To P
Notes
2004-03-02 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 15:55 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 15:55 Sent To E
Notes
2004-02-25 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 08:19 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 08:19 Sent To B
Notes
2004-02-18 00:00:00TO JW DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 07:49 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 07:49 Sent To E
Notes
2004-01-16 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 13:25 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 13:25 Sent To E
Notes
2003-12-30 00:00:00TO DP DESK/REV/LOAD CALCS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 15:58 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 15:58 Sent To  
Notes
2003-11-10 00:00:00TO COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 14:40 Rev Time 0.00
Received By lmartine Date 2003-10-01 Time 09:50 Sent To  
Notes
2003-10-01 00:00:00TO COMM BD#2/ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-23 Cont ID  
Sent By pkrauss Date 2004-02-23 Time 06:50 Rev Time 0.33
Received By pkrauss Date 2004-02-23 Time 06:50 Sent To  
Notes
2004-02-23 00:00:00REVISION:
 MECH MEZZ PLAN DEMO & NEW WORK- MODIFY
 RETURN DUCT ROUTING FROM AHU-1 TO THE
 EMPLOYEE DINING RM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-31 Cont ID  
Sent By pkrauss Date 2003-10-31 Time 14:47 Rev Time 1.15
Received By pkrauss Date 2003-10-31 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-03-11 Cont ID  
Sent By kstevens Date 2004-03-11 Time 08:40 Rev Time 0.50
Received By kstevens Date 2004-03-11 Time 08:40 Sent To  
Notes
2004-03-11 00:00:00REVISION OK - EXPANSIONB TANK FOR BOILER

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By csiegber Date 2004-03-02 Time 09:57 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2003-12-04 00:00:00PROVISO: SEE SHT MP-301 SHOCK ARRESTORS
 PER MFG. PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-27 Cont ID  
Sent By kstevens Date 2003-10-27 Time 16:41 Rev Time 1.50
Received By kstevens Date 2003-10-27 Time 16:41 Sent To  
Notes
2003-10-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) RESPONSE TO COMENT #1 FROM PREVIOUS
 REVIEW NOTED: INSPECTION FOR CAPPED
 PLUMBING LINES REQUIRED TO VERIFY THAT
 LINES ARE CAPPED PER CODE. SEE SHEETS
 MP-60 & MP-61.
 2) DATE NOT ON SEAL AS REQUIRED BY SEC.
 61G15-23.002(1) SEE ATTACHED SHEET FOR
 REFERENCE.
 3) SHT MP-201 DETAIL 2/MP-201 MEN'S AND
 WOMEN'S POOL TOILETS 1ST FLOOR NEW - TO
 BE ROUTED TO THE PALM BEACH CTNY HEALTH
 UNIT DIVISION OF ENVIRONMENTAL HEALTH
 901 EVERNIA STREET FOR REVIEW & APPROVAL
 4) HOSPITALITY ROOM, EXERCISE ROOM AND
 CONFERENCE ROOM TO BE ACCESSIBLE. SHT
 MP-201. PROVIDE DETAILS.
 5) SHT MP-301 ALL WATER RISER DIAGRAMS,
 ALL WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES IN AN "EFFECT-
 IVE RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
  
 REVIEW BY KEN STEVENS