Plan Review Stops For Permit 03090979 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2005-05-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-05-17 |
Time |
09:15 |
Rev Time |
1.00 |
Received By |
shill |
Date |
2005-05-16 |
Time |
17:50 |
Sent To |
PC |
|
Notes |
2005-05-17 00:00:00 | REVISED 1.1 AND PRODUCT APPROVAL AS PER | | PROVISO |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2004-10-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-10-07 |
Time |
10:03 |
Rev Time |
2.00 |
Received By |
shill |
Date |
2004-10-07 |
Time |
10:03 |
Sent To |
PC |
|
Notes |
2004-10-07 00:00:00 | ***PROVISO*** | | 1.) SUBMIT PRODUCT APPROVAL FOR SINGLE | | OUTSWING DOOR | | 2.) SUBMIT NEW ENERGY CALCS WITH CORRECT | | SQUARE FOOTAGE | | 3.) SUBMIT REVISION WITH A DECLARED | | BUILDING TYPE OF VI AS PER TELEPHONE | | CONVERSATION WITH ARCHITECT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2004-10-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-10-06 |
Time |
\5:21 |
Rev Time |
3.00 |
Received By |
shill |
Date |
2004-10-06 |
Time |
15:21 |
Sent To |
|
|
Notes |
2004-10-06 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)PLEASE SEE PREVIOUS LISTS IN | | REGARDS TO THE ADDRESS.A RESPONSE WAS | | GIVEN THAT THE ADDRESS WOULD BE CHANGED | | BUT THIS HAS NOT BEEN DONE. | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | AND THE RECEIPT ATTACHED TO THE | | APPLICATION. | | | | 3.)SEPARATE PERMITS REQUIRED FOR THE | | SECOND BUILDING AND THE DUMPSTER | | ENCLOSURE. | | | | 4.)ZONING APPROVAL REQUIRED BEFORE A | | PERMIT CAN BE ISSUED.PLEASE NOTE THAT | | ZONING HAS NOT YET PASSED THIS PLAN. | | | | 5.)WHEN RESUBMITTING, PLEASE REMOVE | | VOIDED SHEETS AND SUBMIT SEPARATELY. | | | | 6.)SEE PREVIOUS LISTS IN REGARDS TO | | TEST REPORTS AND FLORIDA STATE, LOCAL | | OR SITE SPECIFIC PRODUCT APPROVALS | | REQUIRED.ANY REPORTS NOT SUBMITTED | | BEFORE ISSUANCE WILL REQUIRE SEPARATE | | PERMITS WITH A SEPARATE APPLICATION AND | | FEES FOR THOSE ITEMS. | | | | 7.)SEE PREVIOUS LIST, ITEM #15.AS | | PER THE BUILDING OFFICIAL NEIL K. MELICK | | THE FLORIDA EAST COAST RAILROAD IS NOT | | CONSIDERED A PUBLIC WAY.THEREFORE, | | THE TABLE 600 REQUIREMENT OF 0% | | OPENINGS IS REQUIRED (WALL EXHAUST FAN | | SHOWN ON WEST SIDE). | | | | 8.)NOTES ON THE PLAN SHOULD BE JOB | | SPECIFIC.TO AVOID CONFUSION, PLEASE | | REMOVE REFERENCE TO THE HAZARD OCCUPANCY | | SEPARATION (LS, NOTE 7B). | | | | 9.)PLEASE REVISE SHEET 101 AND ANY | | OTHER APPLICABLE SHEETS TO REFLECT THE | | NEW LL OF 125# (SHEET 400). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2004-10-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2004-10-05 |
Time |
12:43 |
Rev Time |
4.00 |
Received By |
shill |
Date |
2004-09-23 |
Time |
13:47 |
Sent To |
PC |
|
Notes |
2004-10-05 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | 1.)THE PLANS (SHEET 3.1) SHOW 6747 SF, | | IMPACT FEE STAMP IS FOR 6020, ENERGY | | CALCS ARE FOR 6700.ALL THREE SHOULD | | BE THE SAME.PLEASE PROVIDE THE RECEIPT | | SHOWING THAT THE IMPACT FEES ASSESSED | | HAVE BEEN PAID. | | | | 2.)REGARDING PRODUCT APPROVALS | | SUBMITTED: | | | | PGT SINGLE HUNG WINDOW; NO SINGLE HUNG | | WINDOWS ARE ON THE PLAN.THE | | ELEVATIONS AND SHEET 10.1 SHOW FIXED | | GLASS. | | | | RUSKIN LOUVER SHOPS; APPEAR TO BE CODE | | COMPLIANT.PROVIDE DADE COUNTY NOA | | 01-0328.04 REFERRED TO ON THE SHOPS. | | THIS MAY BE AVAILABLE AT WWW.MIAMIDADE. | | GOV (FIND A DEPT, BUILDING CODE | | COMPLIANCE, SEARCH). | | | | OVERHEAD DOOR; PROVIDE PRODUCT APPROVAL. | | | | NOA 02-0712.01 IS MISSING SHEETS 7 & 8. | | | | THE SINGLE DOOR IS NOT APPROVED FOR | | USE WHERE WATER INFILTRATION REQUIREMENT | | IS NEEDED; PLEASE ADDRESS. | | | | 3.)SIGN THE OWNER/AGENT LINE OF THE | | ENERGY CALC. | | | | 4.)TYPE V CONSTRUCTION IS DECLARED | | (1.1).EXTERIOR WALLS ARE TO BE OF | | NONCOMBUSTIBLE CONSTRUCTION, 3-6.1 | | SHOWS A WOOD GABLE (FBC607). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2004-08-09 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-09-15 |
Time |
10:24 |
Rev Time |
4.00 |
Received By |
shill |
Date |
2004-08-03 |
Time |
15:20 |
Sent To |
|
|
Notes |
2004-08-04 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | [email protected] | | | | THIRD REVIEW, ARCHITECTURAL PLANS DATED | | 12/22/03, STRUCTURAL PLANS DATED | | 12/19/03. | | | | 1.)SEE PREVIOUS TWO LISTS.PROVIDE A | | SURVEY.THE SITE PLAN, SHEET 2.1 STILL | | DOES NOT HAVE ANY HORIZONTAL CONTROL | | DIMENSIONS TO LOCATE THE BUILDING. | | PROPERTY LINES ARE NOT IDENTIFIED.SEE | | ATTACHED IN REGARDS TO FS553.80(2)(B). | | CODE COMPLIANCE FOR TABLE 600 CANNOT | | BE DETERMINED WITHOUT A DIMENSIONED | | SITE PLAN.DESIGNER OF RECORD IS | | RESPONSIBLE TO SUBMIT ALL PLANS IN | | COMPLIANCE WITH FBC104.3.1.1.SEE | | SECTION (1), SITE REQUIREMENTS. | | | | 2.)THE SHEETS PREPARED BY WE SCHIPSKE | | PE CONTAIN A PHOTOCOPY OF A SIGNATURE. | | THIS MUST BE AN ORIGINAL SIGNATURE | | FAC61G15-23.002.THE EMBOSSED SEAL IS | | TO BE LEGIBLE. | | | | 3.)THE FP SHEETS AND CALCS LACK A | | TITLE BLOCK REQUIRED BY FAC61G15-23.002. | | | | 4.)6-S3, STUCCO IN A VERTICAL | | APPLICATION OVER WIRE LATH IS TO BE | | 7/8" MIN, FBC2405.2.2, ASTM C926.CHECK | | ALL DETAILS (WILL REDLINE). | | | | 5.)SEE PREVIOUS LIST, CORRECTIONS | | 6 THROUGH 10.NOT ADDRESSED.FOR YOUR | | CONVENIENCE, THEY ARE: | | | | PLEASE PROVIDE THE SPECIFICATION FOR THE | | HIGH LIFT GROUTING CALLED OUT IN NOTE | | J(3) ON S3. | | | | COLUMNS SHOWN AS MC1 ARE NOT ON THE | | COLUMN SCHEDULE ON SHEET S3. | | | | THE REQUESTED COLUMN CONNECTINS FOR THE | | TS COLUMNS SHOWN ON SHEETS S1 AND S2 | | HAVE NOT BEEN PROVIDED. | | | | SHEET S3 ROOF WIND ZONE SKETCH.DID | | THE ENGINEER USE THE SIMPLIFIED METHOD | | IN ASCE7-98 SUBSECTION 6.4 OR THE | | ANALYTICAL METHOD IN SECTION 6.5?IN | | EITHER CASE, HOW WERE THE EDGE AREAS OF | | 4' AND 5' DETERMINED FOR A BUILDING WITH | | A LEAST DIMENSION OF 73' AND A MEAN | | ROOF HEIGHT OF 16.5'? | | | | SEE FBC 13-400.3 FOR COMPUTER BASED | | ENERGY CALCULATIONS AND THE ATTENDANT | | METHODS TO BE USED.ALSO, THE 6020 SF | | GROSS AREA INPUT DOES NOT AGREE WITH THE | | PLANS' 6700+ SQUARE FEET CONDITIONED | | AREA.PLEASE REVISE AS NECESSARY. | | | | THE IMPACT FEES AND NOAS CALLED OUT | | IN THE FIRST CHECKLIST REMAIN | | APPLICABLE. | | | | 6.)BEFORE RESUBMITTING, PLEASE | | CONFIRM THAT THE COMPONENTS AND CLADDING | | PRODUCT APPROVALS SUBMITTED COMPLY WITH | | THE DESIGN CRITERIA ON SHEET 4.1. | | SHINGLES | | STEEL DOORS, DOUBLE AND SINGLE | | OVERHEAD DOOR | | LOUVERS | | IMPACT PROTECTION | | WINDOWS | | | | 7.)I SEE FROM THE RESPONSE LETTER | | DATED 12/22/03, ITEM #12, IT INDICATES | | THAT THE DETAIL 11/10.3 DOES NOT EXIST. | | WHY DOES IT STILL APPEAR ON THE BUILDING | | PLANS?THERE IS STILL NO DETAIL FOR | | THE COLUMN.EXPLAINING IN A LETTER | | THE DESIGN INTENTION FOR THAT COLUMN | | DOES NOT PUT THAT ON THE BUILDING PLANS. | | PLEASE REMOVE THE REFERENCE TO THE | | MISSING 11-10.3 ON THE FOUNDATION PLAN | | AND INCLUDE THE METHOD OF ATTACHMENT | | FOR W10X22 TO THE MC1. | | | | 8.)A RESPONSE WAS MADE THAT EACH | | MC1 ON REVISED S1 IS NOW MC4.THE PLANS | | STILL SHOW MC1.EITHER PROVIDE A | | SPECIFICATION FOR MC1 ON THE COLUMN | | SCHEDULE OR CHANGE THE MC1S ON THE PLAN | | TO MC4. | | | | 9.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 10.) FOR MORE INFORMATION REGARDING | | THE IMPACT FEES REQUIRED, CALL 233-5025. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2004-01-20 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2004-01-16 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2004-01-16 |
Time |
14:55 |
Sent To |
|
|
Notes |
2004-01-16 00:00:00 | SECOND CHECKLIST | | ARCHITECTUAL PLANS DATED 12/22/03 AND | | STRUCTURAL PLANS DATED 12/19/03. | | | | THE PREVIOUSLY REQUESTED SURVEY AND SITE | | PLAN HAVE NOT BEEN PROVIDED.SHEET 2.1 | | TITLED SITE PLAN, DOES NOT HAVE ANY | | HORIZONTAL CONTROL DIMENSIONS TO LOCATE | | THE BUILDING OR ANYTHING ELSE ON THE | | PROPERTY.PROPERTY LINES ARE NOT | | IDENTIFIED. SECTION 2, ON SHEET 2.1 | | SHOWS A SITE WALL DETAIL WITH THE NOTE | | THAT THE FF ELEV.IS 27.25' NGVD.IS | | THIS OF RELEVANCE TO THE SITE WALL? | | | | 2THE ARCHITECT'S RESPONSE LETTER | | DATED 12/22/03 STATES THAT A "FIRE | | RISERSCHEMATIC" CAN BE FOUND ON REVISED | | SHEET ME2. SHEET ME2 DATED 12/19/03 | | FROMCHANE, INC. HAS NO FIRE SPRINKLER | | DESIGN INFORMATION ON IT. | | | | 3RESPONSE #3 OF THE ARCHITECT'S | | LETTERSTATES THAT THE ATTIC SPACE WILL | | HOUSE MECHANICAL EQUIPMENT, SEE SHEET | | M1 NOTE 5A FOR GRAVITY LOADS.SHEETS | | M1 AND M2 ARE BEREFT OF ANY NOTES. | | | | 4ARCHITECTS RESPONSE #5 RE: THE | | OUTDATED CODE STANDARDS TO REFER TO | | REVISED SHEET S3.THE S3 SHEET STILL | | CONTAINS ERRONEOUS AND OUTDATED | | INFORMATION.IT IS PARTICULARLY | | TROUBLESOME TO ME THAT A PROFESSIONAL | | ENGINEER USES AN OUDATED PRESCRIPTIVE | | RESIDENTIAL DESIGN FOR A COMMERCIAL | | BUILDING. | | | | 5THE PREVIOUS REQUEST FOR HIGH LIFT | | GROUTING HAS NOT BEEN ADDRESSED.SHEET | | S3 REFERS TO SPECIFICATIONS THAT WERE | | NOT FOUND. | | | | 6COLUMNS SHOWN AS MC1 ARE NOT IN THE | | COLUMN SCHEDULE ON SHEET S3.IS THE | | 12/22/03 LETTER FROM THE ARCHITECT | | INTENDED TO BE MADE A PART OF THE | | PERMIT PLANS SINCE THOSE RESPONSES HAVE | | SOME OF THE INFORMATION THAT IS ABSENT | | FROM THE PLANS? | | | | 7THE REQUESTED COLUMN CONNECTIONS FOR | | THE TS COLUMNS SHOWN ON SHEETS S1 AND | | S2 HAVENOT BEEN PROVIDED. | | | | 8SHEET S3 ROOF WIND ZONE SKETCH.DID | | THE ENGINEER USE THE SIMPLIFIED METHOD | | IN ASCE 7-98 SECTION 6.4 OR THE | | ANALYTICAL METHOD IN SECTION 6.5?IN | | EITHER CASE, HOW WERE EDGE AREAS OF 4' | | AND 5' DETERMINED FOR A BUILDING WITH A | | LEAST DIMENSION OF 73' AND A MEAN ROOF | | HEIGHT OF 16.5'?WHERE ARE ZONES 4&5? | | | | 9SEE FBC 13-400.3 FOR COMPUTER BASED | | ENERGY CALCULATIONS AND THE ATTENDANT | | METHODS TO BE USED.ALSO, THE 6020 SF | | GROSS AREA INPUT DOES NOT AGREE WITH | | THE PLANS' 6700 + SQUARE FEET | | CONDITIONED AREA.PLEASE REVISE AS | | NECESSARY. | | | | 10THE IMPACT FEES AND NOA'S CALLED OUT | | IN THE FIRST CHECKLIST REMAIN | | APPLICABLE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-10-21 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-10-21 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2004-01-16 |
Time |
14:55 |
Sent To |
ENG |
|
Notes |
2003-10-21 00:00:00 | PLEASE PROVIDE A RECENT PROPERTY SURVEY | | AND A SITE PLAN WITH DIMENSIONS LOCATING | | THE PROPOSED BUILDING ON THE PROPERTY. | | SEE FBC 104.2.4. | | | | PLEASE SHOW THE FIRE PROTECTION SYSTEMS | | ON THE PLANS, INCLUDING SPRINKLER | | DESIGN. SEE FBC 104.3.1.1. | | | | SHEET S2.WHAT WILL THE ATTIC SPACE BE | | USED FOR AND WHAT ARE THE DESIGN LIVE | | AND DEAD LOADS? | | | | WHAT WILL THE VAULT SHOWN ON SHEET 3.1 | | BE USED FOR? | | | | THE STANDARDS CITED ON SHEET S3, LIKE | | ACI, ARE NOT THE EDITIONS INVOKED BY | | THE FBC.SEE FBC 3501 AND REVISE AND | | DEMONSTRATE COMPLIANCE AS NECESSARY. | | | | PLEASE PROVIDE THE SPECIFICATION FOR THE | | HIGH LIFT GROUTING CALLED OUT IN NOTE | | J(3) ON S3. | | | | NOTE P3 ON S3 CITES SSTD 10-97 WHICH IS | | NEITHER CURRENT OR APPLICABLE TO THIS | | BUILDING FOR DESIGN OF THE ROOF | | DIAPHRAGM SYSTEM.PLEASE REVISE AND | | DEMONSTRATE COMPLIANCE WITH FBC 2310. | | (DO NOT QUOTE CODE SECTIONS) | | | | THE DOORS SHOWN AS 110 & 111 AND 108 | | ON SHEET 3.1, SWINGING INTO CORRIDORS | | 109 AND 106 RESPECTIVELY, ARE | | PROHIBITTED BY FBC 1012.1.4. | | | | THE WINDOW SCHEDULE AND SHEET 10.1 | | DECLARES A DESIGN WIND SPEED OF 110 | | MPH.THECITY OF WEST PALM BEACH IS IN | | A 140 MPH WIND ZONE.PLEASE REVISE AS | | NECESSARY. | | | | THE ROOF ZONE SKETCH ON SHEET S3 IS NOT | | CLEAR.SEE ASCE 7-98 TABLE 6-5B.WHERE | | ARE THE WALL PRESSURES ZONES 4 & 5 ? | | WHAT IS THE BASE VELOCITY PRESSURE? | | HOW WERE THE DOOR AND WINDOWS PRESSURES | | SHOWN DETERMINED? | | | | SHEET S3 SECTION 5, PLEASE SPECIFY THE | | WELDS TO USED FOR THE HURRICANE STRAPS. | | | | SHEET S2, HOW IS THE W 10X22 CONNECTED | | TO THE MC 1 COLUMN?WHERE IS SECTION | | 11/10.3 FOUND? | | | | MC 1 IS NOT SHOWN ON THE COLUMN | | SCHEDULE. | | | | SHOW THE ATTIC ACCESS AND ATTIC | | VENTILATION IN ACCORDANCE WITH FBC | | 2309.6 AND 2309.7.ALSO SHOW THE FREE | | AREA CALCULATION AND NOTE WHETHER THE | | LATH FREE AREA TOGETHER WITH THE SCREEN | | AREA HAS BEEN USED. | | | | SHOW THE COLUMN CONNECTIONS, TOP AND | | BOTTOM, FOR THE STEEL COLUMNS DEPICTED | | ON SHEET S.2. | | | | SHEET 8.1, SHOW THE FIRE BLOCKING AS | | PROVIDED FOR IN FBC 705.3.1.1 FOR THE | | CHASEWALL SHOWN AS [D], OR THE FIRE | | STOPPING METHOD. | | | | THE ENERGY CODE INPUT DATA SHEET SHOWS | | VALUES FOR THE ROOF CONSTRUCTION | | MATERIAL.FBC 13-404.1ABCD REQUIRES | | THE CEILING TO BE USED WHEN THERE IS A | | VENTED CAVITY.PLEASE REVISE AS | | NECESSARY. | | | | IF TEST REPORTS AND/OR NOA'S FOR THE | | DOORS, WINDOWS AND ROOF COVERING ARE | | NOT INCLUDED WITH THE PERMIT | | APPLICATION, SEPARATE PERMIT(S), FEES | | AND INFORMATION WILL BE REQUIRED. | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | ISSUED IMPACT FEES MUST BE PAID TO THE | | COUNTY, THE PERMIT PLANS STAMPED BY | | THAT OFFICE AND A COPY OF THE PAID | | RECEIPT ATTACHED TO THE PERMIT | | APPLICATION.CALL (561) 233-5025 FOR | | MORE INFORMATION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2004-07-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-07-27 |
Time |
14:52 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-07-27 |
Time |
14:45 |
Sent To |
|
|
Notes |
2004-07-27 00:00:00 | ** REDLINED ** | | | | CONDUCTORS FROM GUTTER TO PANEL "T" TO | | BE SIZED PER 310.16 (75) DEGREE COL. | | 350MCM AS SHOWN IS NOT LARGE ENOUGH. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2004-01-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2004-01-02 |
Time |
06:13 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2004-01-02 |
Time |
06:13 |
Sent To |
|
|
Notes |
2004-01-02 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE SUBMIT/SHOW THE GROUNDING | | ELECTRODE SYSTEM PER 250.50 BLDG/FOOTER/ | | CWP ETC. FIRST REVIEW NOTE. | | | | 2)NOTE: PLEASE SHOW/CLARIFY EQUIPMENT | | GROUNDING BETWEEN MAINAND GUTTER AND | | GUTTER AND PANELS. 250.110, 250.24, SIZE | | PER 250.122 | | | | 3)NOTE: PLEASE SUBMIT AIC RATING FOR | | MAIN. NOTE MENTIONS FPL FAULT CURRENT | | AND PANELS ARE SHOWN WITH BRANCH BRKRS | | RATED AT 42K. 110.9/215.5 | | | | 4)NOTE: RISER SHOWS PARALLEL RUNS TO | | METER YET NOT FROM METER TO MAIN AND | | GUTTER. PLEASE CLARIFY. SAME CONDUCTORS | | ETC ARE CARRIED THROUGH. | | | | PLEASER SEE PLANS ARE COMING BACK FOR | | FIRE REIVEW COMMENTS. PLEASE SEE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-10-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-10-07 |
Time |
06:31 |
Rev Time |
1.50 |
Received By |
dpalmer |
Date |
2003-10-06 |
Time |
16:53 |
Sent To |
|
|
Notes |
2003-10-07 00:00:00 | ************** UNSAT *************** | | | | 1)NOTE: PLEASE CORRELATE ALL CIRCUITING | | ON PLANS WITH PANEL SCHEDULES. | | THERE ARE A SOME CIRCUITS THAT DO NOT | | CORRELATE,SEE A COUPLE OF CIRCUITS SHOWN | | ON PLAN AND NOT ON PANEL SCHEDULE. | | | | 2)NOTE; PLEASE CORRELATE RISER AND PANEL | | (S). PANEL S IS TETC. | | PLEASE CORRECT CONDUCTOR SIZES ACCORD. | | TO PANEL. | | | | 3)NOTE: PLEASE SEE THAT PANEL "T" IS | | SHOWN HAVING NO NEUTRAL, HOWEVER THE | | NEUTRAL IS REQ'D TO TERMINATE IN PANEL | | EVEN IF IT IS GOING TO USED. | | | | 4)NOTE: PLEASE SEE THAT THERE IS NO | | GROUNDING ELECTRODE SYSTEM SHOWN? | | PLEASE SEE 250.50/250.66 | | | | 5)NOTE: PLEASE SEE TOTAL AMPS SHOWN FOR | | "C" PHASE ON PANEL "S". 9595A'S | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | MAIN ETC. 110.9 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. 215.5 IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2003-12-24 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2003-12-24 |
Time |
11:03 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2003-12-24 |
Time |
11:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2003-10-22 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2003-10-21 |
Time |
11:02 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2003-10-22 |
Time |
14:27 |
Sent To |
|
|
Notes |
2003-10-22 00:00:00 | FAILED: | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | APPLICATION AND FEES FOR" UNDERGROUND | | UTILITIES AND SITE WORK" IS REQUIRED, | | SUBMIT CIVIL PLANS ONLY,SIGNED & SEALED. | | 2. CIVIL PLANS MUST INCLUDE DRANAGE SYS. | | IT MUST BE DESIGNED PER CITY OF WEST | | PALM BEACH CRITERIA AND REQUIREMENT. | | 2. PLEASE SUBMIT STORM WATER CALCULATION | | ,IT SHOULD INCLUDE CALC. FOR PERVIOUS, | | IMPERVIOUS AND TOTAL SITE AREA,(SIGNED & | | SEALED). | | 3. PLEASE INCLUDE POLLUTION PREVENTION | | PLANS IT SHOULD BE INSTALLED IN FIELD | | PRIOR TO ANY EARTH/SITE WORK. | | 4. PLEASE LABEL F.D.C AS SHOWN, SITE | | PLAN 1 OF 2. | | 5. ALL PIPES CONNECTING TO CITY SERVICES | | MUST BE SIZED, METER,BACKFLOW PREVENTERS | | ,DDCV,PIPES, ETC.. | | 6. PLEASE SUBMIT TWO SETS OF CIVIL PLANS | | TO PUBLIC UTILITIES & ENGINEERING ATT: | | JIM SPEACH, FOR THE APPROVAL OF THE | | CONNECTIONS TO THE CITY SERVICES. | | 659-8040 EXT. 2317 | | 7. ALL THE CITY STANDARD MAY BE OBTAINED | | FROM PUBLIC UTILITIES & ENGINEERING | | 659-8040,JIM SPEACH. | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2004-09-23 |
|
|
Cont ID |
|
Sent By |
nmccray |
Date |
2004-09-23 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
nmccray |
Date |
2004-09-23 |
Time |
11:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2004-07-28 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2004-07-28 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2004-07-28 |
Time |
15:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2003-12-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-12-29 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-12-29 |
Time |
16:42 |
Sent To |
|
|
Notes |
2003-12-29 00:00:00 | 1) ALL DOORS THAT COULD BE SUBJECT | | TO TRAFFIC OF 100 OR MORE PERSONS | | SHALL HAVE PANIC HARDWARE. DOORS | | 103A, 104A, AND 109 SHOULD ALSO HAVE | | PANIC HARDWARE. | | | | 2) FIRE SPRINKLER DRAWINGS ARE REQUIRED | | AT TIME OF PERMIT. | | | | 3) COULD NOT LOCATE PAGE 3.2. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2003-09-19 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-09-19 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-09-19 |
Time |
16:15 |
Sent To |
|
|
Notes |
2003-09-19 00:00:00 | 1) NO FIRE SPRINKLER PLANS OR | | HYDRAULIC CALCULATIONS PROVIDED WITH | | DRAWINGS. THE CODE SUMMARY BOX | | INDICATES THAT THE BUILDING WILL BE | | FIRE SPRINKLER PROTECTED. | | | | 2) PLEASE INDICATE THE PROPOSED OCCUPANT | | LOAD FOR THE BUILDING. | | | | 3) PANIC HARDWARE IS REQUIRED ON | | EXIT DOORS IF 100 OR MORE PERSONS | | ARE EXPECTED. | | | | 4) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | 5) THE ACCORDIAN FOLDING PARTITION IS | | COMPRISED OF WHAT CONSTRUCTION. | | | | 6) BUILDING ADDRESS IS REQUIRED ON | | PROPER ELEVATION. A MINIMUM OF 6" | | NUMBERS ARE REQUIRED. | | | | 7) AT LEAST TWO OF THE DOORS APPEAR | | TO SWING TOO FAR INTO THE CORRIDOR. | | PLEASE EXPLAIN RATIONALE. | | | | 8) PLEASE ENSURE THAT ALL FIRE SAFETY | | EQUIPMENT AND OR DEVICES ARE SHOWN | | ON THE PLANS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2004-09-15 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-09-15 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-09-15 |
Time |
10:24 |
Sent To |
B |
|
Notes |
2004-09-15 00:00:00 | TO COMM BD#40 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2004-07-14 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2004-07-14 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2004-07-14 |
Time |
15:33 |
Sent To |
|
|
Notes |
2004-07-14 00:00:00 | TO COMM BD#39 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-12-23 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-12-23 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-12-23 |
Time |
11:29 |
Sent To |
|
|
Notes |
2003-12-23 00:00:00 | TO COMM BD#3 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-09-19 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-19 |
Time |
08:41 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-09-19 |
Time |
08:41 |
Sent To |
|
|
Notes |
2003-09-19 00:00:00 | ON COMM BD# | | ON COMM BD #17 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-09-17 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2003-09-18 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-09-17 |
Time |
14:05 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2004-07-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-07-21 |
Time |
07:37 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2004-07-21 |
Time |
06:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2004-01-06 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2004-01-06 |
Time |
07:14 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2004-01-06 |
Time |
07:03 |
Sent To |
|
|
Notes |
2004-01-06 00:00:00 | DENIED: | | PLEASE NOTE THE VAULT ROOM IS INDICATED | | AS A 3 HR FIRE RESISTANCE RATING.FIRE | | DAMPERS ARE NOT INDICATED AT THE WALL | | PENETRATION OR CEILING PENETRATIONS. | | PLEASE CLARIFY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2003-10-10 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-10-10 |
Time |
12:59 |
Rev Time |
0.55 |
Received By |
pkrauss |
Date |
2003-10-10 |
Time |
12:59 |
Sent To |
|
|
Notes |
2003-10-10 00:00:00 | DENIED: | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | AS PER 2001 FBC(M) 606.2.1 WITH | | NOTIFICATION TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS AS PER NFPA 90A | | 4-4.4.3. | | | | ROOF STANDS FOR THE CONDENSING UNITS | | SHALL COMPLY WITH 2001 FBC 1511.7 SEE | | ATTACHED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2004-07-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-07-30 |
Time |
08:24 |
Rev Time |
0.75 |
Received By |
kstevens |
Date |
2004-07-30 |
Time |
08:24 |
Sent To |
|
|
Notes |
2004-07-30 00:00:00 | PASSED/PROVISO | | | | AN RPZ BACKFLOW IS REQUIRED ON THE WATER | | SERVICE & THERMAL EXPANSION CONTROL IS | | REQUIRED. 608.13.2/607.3.2 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2004-01-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2004-01-13 |
Time |
18:44 |
Rev Time |
1.00 |
Received By |
kstevens |
Date |
2004-01-13 |
Time |
18:39 |
Sent To |
|
|
Notes |
2004-01-13 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 BUILDING | | | | 1) PER CALCULATIONS PROVIDED IN RESPONSE | | TO 1ST REVIEW, MORE FIXTURES WILL BE RE- | | QUIRED PER TABLE 403. WITH THE CHURCH | | OCCUPANCY BEING 2958 DEVIDED BY 7 NET = | | 422.57 ROUNDED UP TO 423 DIVIDED BY 2 = | | 111.5 ROUNDED UP TO 112. PER POTTY PARI- | | TY THAT IS 2 FOR MEN & 3 FOR WOMEN. THE | | BUSINESS AREA IS 2824 DIVIDED BY 100 = | | 28.24 ROUNDED UP TO 29 IS ONE WATER | | CLOSET AND STORAGE IS 965 DIVIDED BY | | 300 (TABLE 1003.1) = 3.21 ROUNDED UP TO | | 4. ADDED TO THE 29 FROM BUSINESS THERE | | WILL STILL BE ONE MORE WATER CLOSET REQ- | | UIRED MINIMUM. IF ADDED TO THE MENS | | TOILET ROOM THEN POTTY PARITY IS NOT | | BEING ADDRESSED. | | 2) SHT ME2 HAS NOT CHANGED. INFORMATION | | HAS BEEN TRANSFERRED TO SHT ME1 AND ME2 | | STILL HAS INCORRECT WATER RISER. A NEW | | SHEET SP-1 HAS BEEN ADDED FOR INFORMAT- | | ION PREVIOUSLY ON SHT ME1. PLEASE | | CLAIRFY, AS THE INFORMATION CAN NOT BE | | APPROVED. | | 3) ENGINEERS NAME AND LICENSE NUMBER | | MISSING FROM SHTS ME2 AND SP-1. | | 61G15-23.002(2) & FS 471 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2003-10-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-10-15 |
Time |
12:27 |
Rev Time |
1.25 |
Received By |
kstevens |
Date |
2003-10-15 |
Time |
12:27 |
Sent To |
|
|
Notes |
2003-10-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 BUILDING | | FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | | | 1) PROVIDE CALCULATIONS FOR MINIMUM | | FIXTURE FACILITIES PER TABLE 403.1 | | PLUMBING AND TABLE 1003.1 BUILDING. | | SHOW SQUARE FOOTAGE FOR EACH OCCUPANCY | | OF THE BUILDING, ASSEMBLY, BUSINESS, & | | STORAGE. | | 2) SECTION 4.3.1.1 IN ASSEMBLY OCCUPAN- | | CIES, RESTROOMS WHICH ARE OPEN TO THE | | PUBLIC MUST HAVE A RATIO OF 3 TO 2 W/C'S | | PROVIDED FOR WOMEN AS THE COMBINED TOTAL | | OF W/C'S AND URNALS PROVIDED FOR MEN. AS | | IT SHOWN, A MINIMUM OF 5 W/C'S WILL BE | | REQUIRED FOR WOMEN. (3 X 1.5 = 4.5 ROUND | | UP TO 5). | | 3) SHT ME2 WATER ISOMETRIC, AIR CHAMBERS | | ARE NOT APPROVED. SECTION 604.9 | | DELETE AIR CHAMBERS FROM ISOMETRIC. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2003-09-18 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-17 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
|
Time |
|
Sent To |
I |
|
Notes |
|
|