Plan Review Details - Permit 03090921
Plan Review Stops For Permit 03090921
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-25 Cont ID  
Sent By pkrauss Date 2003-09-25 Time 08:17 Rev Time 0.50
Received By lsmith Date 2003-09-25 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-13 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 14:33 Rev Time 0.50
Received By btrobaug Date 2003-11-13 Time 14:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-11-12 Time 16:18 Rev Time 0.50
Received By btrobaug Date 2003-09-23 Time 07:52 Sent To M
Notes
2003-09-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE CORRECTIONS TO
 DRAWINGS AND RESUBMIT FOR REVIEW.
  
 1} SHEET A1 SHOWS AN EXISTING PANEL
 BEHIND THE WATER HEATER,AND ANOTHER
 EXISTING PANEL IN THE KITCHEN.PLEASE
 CLARIFY.
  
 2} INDICATE SIZE OF THE EXISTING
 SERVICE ON THE RISER DIAGRAM.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-12 Cont ID  
Sent By csiegber Date 2003-11-12 Time 16:18 Rev Time 0.00
Received By csiegber Date 2003-11-12 Time 16:18 Sent To E
Notes
2003-11-12 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-16 Time 09:44 Rev Time 0.00
Received By csiegber Date 2003-09-16 Time 09:44 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-25 Cont ID  
Sent By btrobaug Date 2003-09-23 Time 07:58 Rev Time 0.25
Received By pkrauss Date 2003-09-25 Time 08:16 Sent To B
Notes
2003-09-25 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-09-25 Cont ID  
Sent By pkrauss Date 2003-09-25 Time 08:17 Rev Time 0.00
Received By pkrauss Date 2003-09-25 Time 08:17 Sent To  
Notes
***NONE***