Plan Review Details - Permit 03090839
Plan Review Stops For Permit 03090839
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-15 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 08:38 Rev Time 0.50
Received By lsmith Date 2003-09-15 Time 14:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-13 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 08:07 Rev Time 0.50
Received By btrobaug Date 2003-11-13 Time 07:28 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-30 Cont ID  
Sent By lsmith Date 2003-10-30 Time 13:00 Rev Time 0.00
Received By lsmith Date 2003-10-30 Time 13:00 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-04 Cont ID  
Sent By kstevens Date 2003-12-04 Time 12:07 Rev Time 1.50
Received By kstevens Date 2003-12-04 Time 12:06 Sent To  
Notes
2003-12-04 00:00:00PLUMBING PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-11-12 Cont ID  
Sent By lsmith Date 2003-10-30 Time 13:00 Rev Time 0.75
Received By kstevens Date 2003-11-12 Time 18:10 Sent To E
Notes
2003-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE NOR DOES IT REFLECT THE FLOOR PLAN.
 SEE ATTACHED SHEET FOR EXAMPLE FOR A
 SANT. RISER DIAGRAM THAT MEETS CODE AND
 REFLECTS THE FLOOR PLAN.
 2) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1
 3) A SEPARATE PLUMBING PERMIT IS REQUIR-
 ED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]