Plan Review Details - Permit 03090565
Plan Review Stops For Permit 03090565
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 09:39 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 09:39 Sent To M
Notes
2003-11-10 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-10 Cont ID  
Sent By csiegber Date 2003-09-10 Time 16:00 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 16:00 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2003-11-18 Cont ID  
Sent By pkrauss Date 2003-11-18 Time 12:39 Rev Time 0.00
Received By pkrauss Date 2003-11-18 Time 12:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-18 Cont ID  
Sent By csiegber Date 2003-11-10 Time 09:39 Rev Time 0.15
Received By pkrauss Date 2003-09-18 Time 08:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-10 Time 16:00 Rev Time 0.33
Received By pkrauss Date 2003-09-17 Time 12:40 Sent To  
Notes
2003-09-17 00:00:00DENIED:
 1. RETURN AIR REQUIRED FROM THE OFFICE
 AREA.
 2. RETURN AIR DUCT TO THE MBR, DUCT
 SIZE NOT INDICATED.
 3. RETURN AIR REQUIRED FROM BR2.
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.