Plan Review Details - Permit 03090508
Plan Review Stops For Permit 03090508
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-10-03 Cont ID  
Sent By jleech Date 2003-09-23 Time 18:43 Rev Time 2.00
Received By lsmith Date 2003-10-03 Time 13:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-31 Cont ID  
Sent By dpalmer Date 2003-10-31 Time 15:13 Rev Time 0.33
Received By dpalmer Date 2003-10-31 Time 15:13 Sent To  
Notes
2003-10-31 00:00:00REV FOR FAN SYMBOL

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-30 Cont ID  
Sent By dpalmer Date 2003-09-30 Time 07:14 Rev Time 0.33
Received By dpalmer Date 2003-09-30 Time 07:14 Sent To  
Notes
2003-09-30 00:00:00NOTE REDLINED, ACTUAL INSTALLATION TO
 CORRELATE WITH LTR. NOT OPT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-24 Time 16:44 Rev Time 0.33
Received By dpalmer Date 2003-09-17 Time 18:48 Sent To M
Notes
2003-09-17 00:00:00NOTE REDLINED FOR 2002 NEC AS OF
 7/1/2003

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-24 Time 16:44 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 16:44 Sent To E
Notes
2003-09-24 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-11 Cont ID  
Sent By csiegber Date 2003-09-11 Time 16:24 Rev Time 0.00
Received By csiegber Date 2003-09-11 Time 16:24 Sent To E
Notes
2003-09-11 00:00:00TO SFD RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-10 Cont ID  
Sent By mmclean Date 2003-09-11 Time 14:52 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 11:50 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-23 Cont ID  
Sent By dpalmer Date 2003-09-17 Time 18:48 Rev Time 0.25
Received By pkrauss Date 2003-09-23 Time 07:11 Sent To P
Notes
2003-09-23 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-23 Cont ID  
Sent By pkrauss Date 2003-09-23 Time 07:12 Rev Time 0.25
Received By jleech Date 2003-09-23 Time 18:42 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-11 Cont ID  
Sent By csiegber Date 2003-09-10 Time 11:50 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***