Plan Review Details - Permit 03090340
Plan Review Stops For Permit 03090340
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-29 Cont ID  
Sent By csiegber Date 2003-12-22 Time 11:27 Rev Time 0.00
Received By rbrown Date 2003-10-29 Time 13:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-07 Cont ID  
Sent By rbrown Date 2003-10-07 Time 18:44 Rev Time 0.00
Received By rbrown Date 2003-10-07 Time 18:44 Sent To  
Notes
2003-10-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FBC 609.2.3PARTITIONS IN TYPE IV
 CONSTRUCTION.DEMONSTRATE COMPLIANCE
 WITH THE CODE BY ANNOTATING THE PLANS TO
 DESCRIBE THE CONSTRUCTION OF THE NEW
 WOOD PARTITIONS.SEE COMMENT 3 BELOW
 ALSO.
  
 3) FBC 803.3INTERIOR FINISHES.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE WITH TABLE 803.3.
  
 4) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-22 Cont ID  
Sent By dpalmer Date 2003-10-22 Time 17:24 Rev Time 0.33
Received By dpalmer Date 2003-10-22 Time 17:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-18 Cont ID  
Sent By csiegber Date 2003-09-08 Time 14:04 Rev Time 0.50
Received By dpalmer Date 2003-09-18 Time 16:55 Sent To  
Notes
2003-09-18 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 THAT WILL HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 2)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
  
 3)NOTE: PLEASE SEE 600.5 FOR REQ'D
 SIGN CIRCUIT. PLEASE SHOW IF NEW OR
 EXISTING.
  
 4)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 INFORMATION REQ'D ON TITLE BLOCK.PLEASE
 PROVIDE FIRM LICENSE # IF APPL.
  
 5)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. (LIGHTING) PER 215.3/230.42 ETC
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-23 Cont ID  
Sent By mcarsill Date 2003-10-23 Time 07:45 Rev Time 0.00
Received By mcarsill Date 2003-10-23 Time 07:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-10 Cont ID  
Sent By mcarsill Date 2003-09-10 Time 15:40 Rev Time 0.00
Received By mcarsill Date 2003-09-10 Time 15:40 Sent To  
Notes
2003-09-10 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ NFPA 101, 2000 EDITION.
  
 2) ANOTHER EXIT SIGN IS NEEDED OUTSIDE
 NEW OFFICE DOOR 104 ON THE STORAGE
 SIDE.
  
 3) PLEASE REVIEW SECTION 7-4 OF THE
 FLORIDA BUILDING CODE TO DETERMINE
 IF A FIRE SEPARATION REQUIREMENT IS
 NEEDED BETWEEN THE OFFICE AND STORAGE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-22 Cont ID  
Sent By csiegber Date 2003-12-22 Time 11:27 Rev Time 0.00
Received By csiegber Date 2003-12-22 Time 11:27 Sent To B
Notes
2003-12-22 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-10-20 Time 08:22 Rev Time 0.00
Received By csiegber Date 2003-10-20 Time 08:22 Sent To  
Notes
2003-10-20 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-08 Time 14:04 Rev Time 0.00
Received By csiegber Date 2003-09-08 Time 14:04 Sent To  
Notes
2003-09-08 00:00:00ON COMM BD#5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-30 Cont ID  
Sent By pkrauss Date 2003-12-30 Time 06:38 Rev Time 0.35
Received By pkrauss Date 2003-12-30 Time 06:38 Sent To  
Notes
2003-12-30 00:00:00PROVISO:
 1.CONDENSING UNIT STAND SHALL COMPLY
 WITH 2001 FBC 1511.7 FOR THE CLEARANCE
 BETWEEN THE ROOF SURFACE AND THE BOTTOM
 OF THE SUPPORT RAIL OF THE STAND.
  
 2.RETURN AIR DUCT IS NOT SIZED.SHOW
 COMPLIANCE WITH REVISION TO THE 2001
 FBC(M) 601.4 #1.DUCTS SHALL BE SIZED
 PRIOR TO INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 09:14 Rev Time 0.40
Received By pkrauss Date 2003-10-01 Time 09:14 Sent To  
Notes
2003-10-01 00:00:00PROVISO:
 CONDENSATE SHALL DISCHARGE A MINIMUM OF
 12" AWAY FROM THE BUILDING STRUCTURE AS
 PER 2001 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-10-07 Cont ID  
Sent By kstevens Date 2003-10-07 Time 07:39 Rev Time 0.25
Received By kstevens Date 2003-10-06 Time 18:57 Sent To  
Notes
***NONE***