Plan Review Stops For Permit 03090340 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2003-10-29 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-12-22 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-10-29 |
Time |
13:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2003-10-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2003-10-07 |
Time |
18:44 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2003-10-07 |
Time |
18:44 |
Sent To |
|
|
Notes |
2003-10-07 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6716 | | E-MAIL: [email protected] | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | 1) THE NOTICE OF COMMENCEMENT SHALL BE | | RECORDED AT PALM BEACH COUNTY COURTHOUSE | | AND A COPY SUBMITTED TO THIS OFFICE | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | 2) FBC 609.2.3PARTITIONS IN TYPE IV | | CONSTRUCTION.DEMONSTRATE COMPLIANCE | | WITH THE CODE BY ANNOTATING THE PLANS TO | | DESCRIBE THE CONSTRUCTION OF THE NEW | | WOOD PARTITIONS.SEE COMMENT 3 BELOW | | ALSO. | | | | 3) FBC 803.3INTERIOR FINISHES. | | ANNOTATE THE PLANS TO DEMONSTRATE | | COMPLIANCE WITH TABLE 803.3. | | | | 4) IF NEW PLAN SHEETS ARE REQUIRED, IN | | ORDER TO ADDRESS THE ABOVE COMMENTS, THE | | OLD SHEETS SHALL BE REMOVED AND THE NEW | | SHEETS INSERTED.ONE COPY OF EACH OLD | | SHEET SHALL BE INCLUDED WITH THE | | RESUBMITTAL FOR COMPARISON OF REVISIONS. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6716ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2003-10-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2003-10-22 |
Time |
17:24 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2003-10-22 |
Time |
17:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2003-09-18 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-08 |
Time |
14:04 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2003-09-18 |
Time |
16:55 |
Sent To |
|
|
Notes |
2003-09-18 00:00:00 | ************* UNSAT **************** | | | | 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS | | THAT WILL HAVE AN AFFECT ON ELECTRICAL | | PLANS. | | | | 2)NOTE: PLEASE PROVIDE CIRCUITING ON | | PLANS AND CORRELATE WITH A PANEL | | SCHEDULE TO BE SUBMITTED. | | | | 3)NOTE: PLEASE SEE 600.5 FOR REQ'D | | SIGN CIRCUIT. PLEASE SHOW IF NEW OR | | EXISTING. | | | | 4)NOTE: PLEASE SEE FAC 61G1-16.004 FOR | | INFORMATION REQ'D ON TITLE BLOCK.PLEASE | | PROVIDE FIRM LICENSE # IF APPL. | | | | 5)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | -ING OF EM/EXT LTS. | | | | 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | AT 125%. (LIGHTING) PER 215.3/230.42 ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2003-10-23 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-10-23 |
Time |
07:45 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-10-23 |
Time |
07:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2003-09-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2003-09-10 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2003-09-10 |
Time |
15:40 |
Sent To |
|
|
Notes |
2003-09-10 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. | | SHOULD READ NFPA 101, 2000 EDITION. | | | | 2) ANOTHER EXIT SIGN IS NEEDED OUTSIDE | | NEW OFFICE DOOR 104 ON THE STORAGE | | SIDE. | | | | 3) PLEASE REVIEW SECTION 7-4 OF THE | | FLORIDA BUILDING CODE TO DETERMINE | | IF A FIRE SEPARATION REQUIREMENT IS | | NEEDED BETWEEN THE OFFICE AND STORAGE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2003-12-22 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-12-22 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-12-22 |
Time |
11:27 |
Sent To |
B |
|
Notes |
2003-12-22 00:00:00 | TO PK BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-10-20 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-20 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-20 |
Time |
08:22 |
Sent To |
|
|
Notes |
2003-10-20 00:00:00 | TO COMM BD#50 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-09-08 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-08 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-09-08 |
Time |
14:04 |
Sent To |
|
|
Notes |
2003-09-08 00:00:00 | ON COMM BD#5 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-12-30 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-12-30 |
Time |
06:38 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2003-12-30 |
Time |
06:38 |
Sent To |
|
|
Notes |
2003-12-30 00:00:00 | PROVISO: | | 1.CONDENSING UNIT STAND SHALL COMPLY | | WITH 2001 FBC 1511.7 FOR THE CLEARANCE | | BETWEEN THE ROOF SURFACE AND THE BOTTOM | | OF THE SUPPORT RAIL OF THE STAND. | | | | 2.RETURN AIR DUCT IS NOT SIZED.SHOW | | COMPLIANCE WITH REVISION TO THE 2001 | | FBC(M) 601.4 #1.DUCTS SHALL BE SIZED | | PRIOR TO INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-10-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-10-01 |
Time |
09:14 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2003-10-01 |
Time |
09:14 |
Sent To |
|
|
Notes |
2003-10-01 00:00:00 | PROVISO: | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2003-10-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2003-10-07 |
Time |
07:39 |
Rev Time |
0.25 |
Received By |
kstevens |
Date |
2003-10-06 |
Time |
18:57 |
Sent To |
|
|
Notes |
|
|