Plan Review Details - Permit 03090250
Plan Review Stops For Permit 03090250
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-05 Cont ID  
Sent By lmartine Date 2003-12-05 Time 17:13 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-12-05 00:00:00 
 "PROVISO"
 -------
  
  
  
 CONCRETE WORK REQUIRES SEPERATE PERMIT
 PER ZONING DEPT.
  
  
  
  
  
  
  
 L. MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 09:57 Rev Time 1.00
Received By jwitmer Date 2003-10-09 Time 09:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:14 Rev Time 1.00
Received By jwitmer Date 2003-09-24 Time 07:26 Sent To  
Notes
2003-09-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03090250
 ADD: 222PICADILLY ST
 CONT: CREATIVE CONST CORP
 TEL: (561)236-8554
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 2)11-4.13.5 DOORWAYS, MINIMUM
 CLEAR WIDTH: DOORWAY SHALL HAVE A MINI-
 MUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP.
  
 3)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-11-17 Cont ID  
Sent By jleahy Date 2003-11-17 Time 11:05 Rev Time 0.30
Received By jleahy Date 2003-11-14 Time 11:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-17 Cont ID  
Sent By btrobaug Date 2003-11-17 Time 08:49 Rev Time 0.50
Received By btrobaug Date 2003-11-17 Time 08:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-15 Cont ID  
Sent By dpalmer Date 2003-10-15 Time 07:43 Rev Time 0.33
Received By dpalmer Date 2003-10-15 Time 07:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-09-10 Time 14:40 Rev Time 0.25
Received By dpalmer Date 2003-09-15 Time 06:23 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-17 Cont ID  
Sent By mcarsill Date 2003-10-17 Time 17:46 Rev Time 0.00
Received By mcarsill Date 2003-10-17 Time 17:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-09-16 Cont ID  
Sent By nmccray Date 2003-09-16 Time 13:47 Rev Time 0.00
Received By nmccray Date 2003-09-16 Time 13:47 Sent To  
Notes
2003-09-16 00:00:00*************PROVISO********************
 MUST AND SHALL PROVIDE EMERGENCY LIGHTS.
 INTERIOR FINISH FOR WALLS AND CEILINGS
 SHALL BE CLASS "A" OR CLASS "B".
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-14 Cont ID  
Sent By csiegber Date 2003-11-14 Time 11:43 Rev Time 0.00
Received By csiegber Date 2003-11-14 Time 11:43 Sent To  
Notes
2003-11-14 00:00:00TO COMM BD#22

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:14 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 09:57 Sent To  
Notes
2003-10-08 00:00:00TO COMM BD#58

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-10 Cont ID  
Sent By dpalmer Date 2003-09-15 Time 06:23 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 14:40 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-05 Cont ID  
Sent By sgraham Date 2003-09-09 Time 11:51 Rev Time 0.00
Received By dbaxter Date 2003-09-05 Time 13:44 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 08:43 Rev Time 0.25
Received By pkrauss Date 2003-10-01 Time 08:43 Sent To  
Notes
2003-10-01 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLAN SHEET 3 OF 3 INDICATES
 SOME HVAC DROPS TO BE RELOCATED.DOES
 NOT INDICATE NEW DUCTWORK OR EQUIPMENT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-23 Cont ID  
Sent By kstevens Date 2003-10-23 Time 14:53 Rev Time 0.50
Received By kstevens Date 2003-10-23 Time 14:53 Sent To  
Notes
2003-10-23 00:00:00PASSED/PROVISO
  
 ALL CAPPED PLUMBING LINES SHALL BE IN-
 SPECTED PRIOR TO COVERING.
  
 WATER COOLER TO COMPLY WITH ARI-1010
 MANUF. SPEC. SHEETS REQUIRED AT TIME OF
 PLUMBING FINAL.
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-02 Cont ID  
Sent By kstevens Date 2003-10-02 Time 10:04 Rev Time 1.00
Received By kstevens Date 2003-10-02 Time 10:04 Sent To  
Notes
2003-10-02 00:00:00PASSED/PROVISO
  
 ALL CAPPED PLUMBING LINES SHALL BE IN-
 SPECTED PRIOR TO COVERING.
  
 PER ARCHITECT:
 WATER COOLER TO BE INSTALLED IN LOUNGE
 AREA. COOLER SHALL BE ARI-1010 COMPLIANT
 MANUF. SPECIFICATION SHEET REQUIRED AT
 PLUMBING FINAL. - TABLE 403.1
  
 SINK IN LOUNGE SHALL BE COMPLIANT WITH
 SECTION 11-4.24

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-09 Cont ID  
Sent By dbaxter Date 2003-09-05 Time 13:44 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***