Plan Review Details - Permit 03090238
Plan Review Stops For Permit 03090238 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2003-10-16 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-16 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-10-16 |
Time |
10:55 |
Sent To |
M |
|
Notes |
2003-10-16 00:00:00 | TO PK BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-09-05 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-09-05 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
csiegber |
Date |
2003-09-05 |
Time |
12:59 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2003-10-30 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-10-30 |
Time |
13:14 |
Rev Time |
0.25 |
Received By |
pkrauss |
Date |
2003-10-30 |
Time |
13:14 |
Sent To |
|
|
Notes |
2003-10-30 00:00:00 | AS PER ZONING DEPARTMENT CONDENSER | | UNIT SLAB TO BE A MINIMUM OF 2' FROM | | CBS WALL. | | | | PLEASE NOTE CONDENSERS SHALL HAVE | | SUFFICIENT ACCESS ON THE SERVICE SIDE OF | | EQUIPMENT FOR INSPECTION AND SERVICE. | | | | AS PER 2001 FBC(M) 303.4, EQUIPMENT | | SHALL BE PROTECTED FROM DAMAGE BY | | APPROVED BARRIERS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-09-17 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-10-16 |
Time |
10:55 |
Rev Time |
0.45 |
Received By |
pkrauss |
Date |
2003-09-17 |
Time |
10:13 |
Sent To |
|
|
Notes |
2003-09-17 00:00:00 | PROVISO: | | SEE ATTACHED REQUIREMENT FOR SETBACK | | ON THE CONDENSING UNITS. |
|
|
|