Plan Review Details - Permit 03090004
Plan Review Stops For Permit 03090004
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-02 Cont ID  
Sent By csiegber Date 2003-09-02 Time 09:59 Rev Time 0.00
Received By csiegber Date 2003-09-02 Time 09:59 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-09-02 Time 09:59 Rev Time 0.33
Received By pkrauss Date 2003-09-15 Time 13:11 Sent To  
Notes
2003-09-15 00:00:00PROVISO:
 IF SPACE ALLOWS, SHOW COMPLIANCE WITH
 REVISION TO THE 2001 FBC(M) 601.4,
 EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.