Plan Review Details - Permit 03090002
Plan Review Stops For Permit 03090002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-16 Cont ID  
Sent By shill Date 2003-12-16 Time 17:05 Rev Time 1.00
Received By shill Date 2003-12-16 Time 17:05 Sent To  
Notes
2003-12-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PLANS MUST BE STAMPED BY
 HISTORIC PRESERVATION DIVISION.THE
 APPLICATION IS INCONSISTENT WITH THE
 PLAN (PLAN SHOWS WINDOWS & DOORS).
  
 2.)ADDITIONAL PERMITS REQUIRED.
  
 3.)SJE DESIGN & CONSTRUCTION IS
 REQUIRED TO HAVE THE GC AND ENGINEERING
 AUTHORIZATION NUMBER ON THE TITLE
 BLOCK.BOTH ARE DELINQUENT.ADDRESS.
  
 4.)A 52" HIGH SINGLE HUNG WINDOW DOES
 NOT COMPLY WITH EMERGENCY EGRESS
 REQUIREMENTS FBC1005.4.
  
 5.)TO EXPEDITE PLAN REVIEWS, INCLUDE
 THE REVISION NUMBER AT THE TOP OF THE
 TITLE BLOCK (WHERE IT SAYS "SHEET
 REVISION").ALL CHANGES SHOULD BE
 CLEARLY MARKED WITH EITHER CLOUDS OR
 TRIANGLES.
  
 6.)SEE PREVIOUS LIST, PROVIDE
 DIMENSIONS FOR EXTERIOR WALL (EXT WALL
 SECTION), FIRESTOP MAY BE REQUIRED
 FBC705.3.
  
 7.)SEE ATTACHED HURRICANE SHUTTER
 INSTALLATION SCHEDULE.IF THIS FORM IS
 NOT SUBMITTED BEFORE PERMIT ISSUANCE,
 A SEPARATE PERMIT FOR HURRICANE
 SHUTTERS WILL BE REQUIRED.
  
 8.)FIREBLOCKING REQUIRED AT TOP
 AND BOTTOM STRINGERS, FBC2305.1.4.
  
 9.)IMPROVEMENTS OVER 50% OF VALUE ARE
 TO COMPLY WITH FBC3401.7.2.6.THIS IS
 TO BE REFLLECTED ON THE PLAN.
  
 10.) SEE PREVIOUS LIST, #14, PROVIDE A
 HANDRAIL DETAIL.
  
 11.) PROVIDE A STAIR RAIL DETAIL.
  
 12.) SHOW NORTH ON THE PLAN.
  
 13.) 6.5 FEET OF THE EAST WALL IS LESS
 THAN 3' FROM THE PROPERTY LINE AND MUST
 COMPLY WITH FBC TABLE 600, 1 HOUR FIRE
 RESISTANCE, RATED FROM BOTH THE INSIDE
 AND THE OUTSIDE, 0% OF OPENINGS.IT
 APPEARS THAT THERE IS A WINDOW WITHIN
 THAT 6' AND THE EXISTING WALL DOES NOT
 COMPLY WITH FBC TABLE 600.
  
 14.)SOME STRUCTURAL DETAILS WHICH WERE
 ON THE PLAN WERE REMOVED FROM THE PLAN.
 CLARIFY.
  
 15.)SEE PREVIOUS LIST IN REGARDS TO
 PRODUCT APPROVALS.ANY PRODUCT
 APPROVALS NOT SUBMITTED BEFORE PERMIT
 ISSUANCE WILL REQUIRE A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-02 Cont ID  
Sent By csiegber Date 2003-12-16 Time 09:58 Rev Time 2.00
Received By sthyng Date 2003-10-02 Time 14:28 Sent To  
Notes
2003-10-06 00:00:00OK FOR HISTORIC (PLANS NOT STAMPED)
 PER SP
2003-10-02 00:00:00******CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)ENGINEER'S LICENSE NUMBER IS
 REQUIRED ON THE TITLE BLOCK, FAC
 61G15-23.002.
  
 3.)SHOW THE WINDOW SIZES, TYPE AND
 SILL HEIGHT FOR BEDROOMS.COMPLY WITH
 FBC1005.4.
  
 4.)IT IS NOT CLEAR AS TO HOW SIMPSON
 H10 IS TO BE INSTALLED (EXTERIOR WALL
 SECTION).CLARIFY.
  
 5.)PROVIDE DIMENSIONS FOR THE EXTERIOR
 WALL.FIRESTOP MAY BE REQUIRED FBC
 705.3.
  
 6.)CHANGES DRAWN ON THE PLAN MUST
 BE INITIALED AND DATED BY THE ENGINEER.
  
 7.)PROVIDE SPACING FOR THE 1/2"X6" EXP
 BOLTS (EXTERIOR WALL SECTION).
  
 8.)IMPACT PROTECTION REQUIRED FBC1606.
 1.4.PROVIDE A HURRICANE SHUTTER
 ATTACHMENT DETAIL.
  
 9.)THE ATTACHMENT SPECIFIED IN THE
 WOOD HEADER DETAIL, TP#X, IS NOT IN THE
 USP2003 CATALOG.CLARIFY.
  
 10.) NAILING FOR THE USP RS100 CONFLICTS
 WITH THE CATALOG.CLARIFY.
  
 11.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 12.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS AS IT APPEARS THAT THEY ARE
 TO BE REPAIRED OR REPLACED. FIREBLOCKING
 REQUIRED AT STAIRS FBC2305.1.4.
  
 13.)IMPROVEMENTS OVER 50% OF VALUE
 ARE TO COMPLY WITH FBC3401.7.2.6.
  
 14.)PROVIDE A HANDRAIL DETAIL.
  
 15.)PROVIDE A SURVEY FOR THIS JOB.
  
 16.)THE WINDOW PRODUCT APPROVAL IS NOT
 COMPLETE.
  
 17.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS FOR:
 SINGLE HUNG WINDOW
 FRONT DOOR
 IMPACT PROTECTION
 PRODUCT APPROVALS MAY BE AVAILABLE AT
 WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING
 CODE COMPLIANCE, PRODUCT CONTROL, SEARCH
 APPROVED PRODUCTS).

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-05 Cont ID  
Sent By csiegber Date 2003-09-04 Time 09:00 Rev Time 0.33
Received By btrobaug Date 2003-09-05 Time 17:59 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 09:58 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 09:58 Sent To B
Notes
2003-12-16 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-09-04 Time 09:00 Rev Time 0.00
Received By csiegber Date 2003-09-04 Time 09:00 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-02 Cont ID  
Sent By dbaxter Date 2003-09-02 Time 13:57 Rev Time 0.00
Received By dbaxter Date 2003-09-02 Time 13:57 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-02 Cont ID  
Sent By csiegber Date 2003-09-02 Time 11:19 Rev Time 0.00
Received By csiegber Date 2003-09-02 Time 11:19 Sent To Z
Notes
***NONE***