2003-09-25 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| W.P.B. CITY CODE |
| |
| 1) SHT A.5.3 DETAIL 7, SINK SHALL COMPLY |
| WITH 11-4.24 AND ALL SUBSECTIONS. PROVI- |
| DE DETAILS, SHOW CLEAR FLOOR SPACE, |
| HEIGHT & CLEARANCES, FAUCETS, PIPES AND |
| SURFACES, ECT. |
| 2) CERTIFICATE OF AUTHORIZATION REQUIRED |
| ON EACH SHEET. SEE ATTACHED SHEET. |
| 61G15-23.002(2) - ALSO ENGINEER SHALL |
| LEGIBLY INDICATE THEIR NAME AND LICENSE |
| NUMBER ON EACH SHEET. |
| 2) A RPZ BACKFLOW IS REQUIRED. 608.13.2. |
| 3) SUBMIT CALCULATIONS FOR PRIMARY AND |
| SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| & 1107 AND ALL SUBSECTIONS. (NEW ROOFS & |
| PARAPETS) SHOW 1/2 AREA OF ALL VERTICAL |
| WALLS AND ALL AREAS OF ROOFS THAT DRAIN |
| ONTO THE ROOF FROM ABOVE ADDED TO CALCU- |
| LATIONS. PROVIDE A ROOF PLAN TO SHOW |
| LOCATIONS OF PRIMARY & SECONDARY ROOF |
| DRAINS. SHOW SIZE OF DRAINS, AND IF |
| SCUPPERS ARE USED PROVIDE A DETAIL SHOW- |
| ING WIDTH AND HEIGHT OF OPENING ECT. PER |
| SECTION 1511.6.4.3 AND SECTION 1107. |
| 4) DRESSING ROOM BENCH TO BE FIXED TO |
| THE WALL ALONG THE LONGER DIMENSION, 17" |
| TO 19" ABOVE FINISHED FLOOR. SECTION |
| 11-4.35.4 |
| 5) THE FOLLOWING INFORMATION REQUIRED |
| FOR GAS PERMIT. SEPARAGE GAS PERMIT REQ- |
| UIRED. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| FBC-2001 FUEL GAS 402.3 |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| F. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| H. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| J. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| 6) GREASE INTERCEPTOR THAT IS BEING |
| ABANDONED SHALL BE CLEANED OUT, AND RE- |
| MOVED ENTIRELY, OR CLEANED OUT, THE TOP |
| REMOVED, THE BOTTOM BUSTED UP AND FILLED |
| WITH CLEAN FILL. BOTH LINES INTO AND OUT |
| OF THE GREASE INTERCEPTOR SHALL BE CAPP- |
| ED AND INSPECTED PRIOR TO COVERING. |
| |
| REVIEW BY KEN STEVENS |