Plan Review Details - Permit 03081693
Plan Review Stops For Permit 03081693
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-09 Cont ID  
Sent By dpalmer Date 2003-09-30 Time 17:37 Rev Time 0.50
Received By lsmith Date 2003-09-09 Time 14:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-30 Cont ID  
Sent By dpalmer Date 2003-09-30 Time 17:37 Rev Time 0.33
Received By dpalmer Date 2003-09-30 Time 17:37 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-08 Cont ID  
Sent By kstevens Date 2003-09-30 Time 08:15 Rev Time 0.33
Received By dpalmer Date 2003-09-08 Time 16:40 Sent To B
Notes
2003-09-08 00:00:00********* NOTE ********************
  
 PLEASE SEE THAT ELECTRICAL IS OK,
 HOWEVER ,THERE ARE PLUMB COMMENTS AND
 PLUMB AND ELECTRIC IS ON SAME PLAN.
  
 PLEASE PROVIDE SUBMITTAL FOR GAS HEAT?
 FROM A LISTED TESTING LAB.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-16 Time 12:21 Rev Time 0.00
Received By csiegber Date 2003-09-16 Time 12:21 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-28 Cont ID  
Sent By mmclean Date 2003-09-02 Time 15:34 Rev Time 0.00
Received By dbaxter Date 2003-08-28 Time 13:34 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-30 Cont ID  
Sent By kstevens Date 2003-09-30 Time 08:15 Rev Time 0.75
Received By kstevens Date 2003-09-30 Time 08:15 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-06 Cont ID  
Sent By csiegber Date 2003-09-16 Time 12:21 Rev Time 0.50
Received By kstevens Date 2003-09-06 Time 19:24 Sent To E
Notes
2003-09-06 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 2) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 3) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 5) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 6) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED. (ADD TO NOTES)
 7) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-02 Cont ID  
Sent By dbaxter Date 2003-08-28 Time 13:35 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***