Plan Review Stops For Permit 03081596 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2003-08-27 |
|
|
Cont ID |
|
Sent By |
dbaxter |
Date |
2003-08-27 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
dbaxter |
Date |
2003-08-27 |
Time |
14:20 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2003-09-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2003-09-03 |
Time |
12:07 |
Rev Time |
0.40 |
Received By |
pkrauss |
Date |
2003-09-03 |
Time |
12:07 |
Sent To |
|
|
Notes |
2003-09-03 00:00:00 | DENIED: | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | 2001 FBC(M) TABLE 403.3. | | | | 2.INDICATE SIZE, MATERIAL, & LOCATION | | OF OUTSIDE AIR DUCT. | | | | 3.INDICATE DUCT SMOKE DETECTOR (IF | | REQUIRED). | | | | 4.STANDS FOR CONDENSING UNIT SHALL | | COMPLY WITH 2001 FBC 1511.7. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|