Plan Review Details - Permit 03081544
Plan Review Stops For Permit 03081544
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-24 Cont ID  
Sent By hpiskura Date 2003-10-24 Time 10:09 Rev Time 0.00
Received By hpiskura Date 2003-10-24 Time 10:09 Sent To  
Notes
2003-10-24 00:00:00THIS BUILDING WILL BE AN R1 OCCUPANCY
 AND IS REQUIRED TO BE DESIGNED, SIGNED,
 SEALED AND DATED BY A FLORIDA
 REGISTERED ARCHCITECT OR ENGINEER.THE
 ENGINEER SENG-CHAI TAN DECLARES
 STRUCTURAL RESPONSIBILITY ONLY.THE
 REMAINDER OF THE DESIGNMUST BE BY AN
 ARCHITECT OR ENGINEER ALSO.
  
 THIS BUILDING WILL BE LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND MUST
 COMPLY WITH FBC F102.2.5, AS AMENDED BY
 THE CITY,WHICH REQUIRES TWO STORY
 BUILDINGS TO BE ONE HOUR PROTECTED
 UNLESS, FIRE SPRINKLERED THROUGH OUT
 OR OF TYPE III CONSTRUCTION.PLEASE
 REVISE AS NECESSARY.
  
 THE WINDOW BUCKS ON SHEET A1 MUST COMPLY
 WITH FBC 1707.4.4.
  
 FBC TABLE 600 REQUIRES A TWO HOUR FIRE
 RATED EXTERIOR WALL WHEN LOCATED FROM
 THREE TO TEN FEET OF A COMMON OR
 ASSUMED PROPERTY LINE, AND FBC
 705.1.1.2 REQUIRES PROTECTED OPENINGS.
 THE EAST AND WEST ELEVATIONS ARE
 SUBJECT TO THIS.
  
 SHOW HOW THE EXISTING BUILDING TO THE
 EAST WILL COMPLY WITH TABLE 600 AND THE
 ASSUMED PROPERTY LINE.SEE FBC 504.
 SEE ALSO FBC 1006.2.2 FOR THE EXTERIOR
 STAIR EXPOSURE ALLOWANCE.
  
 PLEASE PROVIDE A SITE PLAN WITH
 TOPOGRAPHIC INFORMATION SO THAT
 HANDICAP SITE ACCESSIBILITLY MAY BE
 DETERMINED.
  
 THE WINDOWS, DOORS AND ANY OTHER
 OPENINGS IN THE TEN FEET PRESCRIBED
 AREA FOR THE STAIRS AS NOTED INFBC
 1006.2.4 MUST BE PROTECTED.
  
 SHEET A2.PLEASE CLARIFY THE
 REINFORCEMENT SCHEDULE FOR THE F2 PADS
 WITH 4 #5'S VERTICAL.
  
 HOW WILL THE WOOD COLUMNS CONNECT TO
 THE PADS?ABOVE OR BELOW GRADE?
  
 ENGINEER, PLEASE CLARIFY THE COLUMN
 SCHEDULE AS TO 8X12 BLOCK 8X8 BLOCK,
 ETC.ARE THESE IN FACT COLUMNS OR
 REINFORCED MASONRY?SEE ACI 530-99 AND
 PROVIDE THE REQUISITE SPECIFICATIONS
 AND DETAILS.SHOW THE DELEGATED
 ENGINEERING REQUIREMENTS FOR THE ROOF
 AND FLOOR TRUSSES.
  
 SHEET A5, SEE FBC 1608.2 FOR THE
 MINIMUM STRUCTURAL DESIGN CRITERIA FOR
 HAND AND GUARD RAILS.
  
 THE STAIR RISE AND RUN DOESN'T COMPLY
 WITH FBC 1007.3.ALSO, SHOW A
 CONSTRUCTIONDETAIL, INCLUDING
 FASTENERS, FOUNDATION AND DESIGN LOADS
 FOR THE STAIRS,
 BALCONIES, ETC.
  
 SHOW THE ATTIC ACCESS AND VENTILATION AS
 PROVIDED FOR IN FBC 2309.6 AND 2309.7.
  
 SHOW THE STAIR AND HAND RAIL DETAILS FOR
 THE FRONT PORCH, (SOUTH ELEVATION).
  
 HOW WILL THE HANDICAP TOILETS ON THE
 NORTH SIDE BE ACCESSED?THE PORCH IS
 SHOWN 20" ABOVE THE SURROUNDING GRADE.
  
 PLEASE PROVIDE THE FIRE DESIGN NUMBER
 FOR THE RATED WALLS, FLOORS, ROOF AND
 COLUMN ASSEMBLIES TOGETHER WITH THE
 METHOD OF PENETRATION PROTECTION.SEE
 FBC 104.2 AND FBC 701.
  
 SHEET A5 SEC AA, WHAT IS THE SPACING
 FOR THE 3/4" BOLT THROUGH THE 2-2X8'S?
  
 THE ENERGY CODE DECLARES R30 CEILING
 INSULATION NOT SHOWN ON THE PLANS.
 PLEASE REVISE AS NECESSARY.
  
 SEE FBC 13-600.3 FOR THE REQUIREMENT OF
 AN ARCHITECT OR ENGINEER TO SIGN AND
 SEAL THE ENERGY CODE AND INCORPORATE
 THEM INTO THE PLANS AND SPECIFICATIONS.
  
 SHOW THE DRAFTSTOPPING IN ACCORDANCE
 WITH FBC 2305.2.2.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-07 Cont ID  
Sent By dpalmer Date 2003-10-07 Time 07:23 Rev Time 1.00
Received By dpalmer Date 2003-10-07 Time 07:23 Sent To  
Notes
2003-10-07 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
  
 2)NOTE: PLEASE SEE THAT PANEL SHALL NOT
 BE LOCATED IN BATHROOM.240.24E
  
 3)NOTE: PLEASE CORRELATE OCP FOR A/C
 UNITS WITH WHAT IS SHOWN ON MECH DETAIL.
 ONE SHOWN AS 25A OCP OTHER SHOWN AS 30A
  
 4)NOTE: PLEASE SEE THAT SD'S ARE NOT TO
 BE LOCATED W/IN 3' OF BATHROOM DOORS.
 NFPA-72 8-1.4.2
  
 5)NOTE: PLEASE SEE THAT CIRCUITS ARE
 SHOWN ON PANEL W/#14AWG AND 20A OCP.
 PLEASE SEE 310.16 AND NOTES TO TABLE.
  
 6)NOTE: PLEASE SEE THE MIN REQ'D FOR
 BATH GFI. 210.52D, 210.11.C3 , PLEASE
 SEE THAT ALL BATH GFI'S ARE BEING SHOWN
 ON ONE CIRCUIT?
  
 7)NOTE: NOTE TO PANEL/MAIN AIC RATING IS
 SHOWN AS A/C RATING. PLEASE CORRECT.
  
 8)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 PER 220.
  
 9)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 481. PLEASE SEE THAT TITLE BLOCK IS
 MISSING REQ'D LICENSE # INFORMATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-10-24 Cont ID  
Sent By hpiskura Date 2003-10-24 Time 14:51 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 15:02 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 15:02 Sent To  
Notes
2003-10-03 00:00:001) ALL NEW LODGING OR ROOMING HOUSES
 SHALL BE PROTECTED WITH AN AUTOMATIC
 FIRE SPRINKLER SYSTEM.
  
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. A MINIMUM OF 6"
 NUMERALS REQUIRED.
  
 3) RISE AND TREAD SIZES ARE WRONG FOR
 THE STAIRS. TREADS SHALL BE A MINIMUM
 OF 11" WIDE. RISERS SHALL BE A MINIMUM
 OF 4" AND A MAXIMUM OF 7".
  
 4) WINDOW AND AT LEAST ONE DOOR NOTED
 WITHIN 10 FEET OF EXIT STAIR.
  
 5) SMOKE DETECTORS ON FIRST FLOOR
 MAY BE LOCATED TOO CLOSE TO BATHROOMS
 WHERE STEAM WOULD CAUSE FALSE ALARMS.
  
 6) PLEASE EXPLAIN EXITING RATIONALE
 FROM SECOND FLOOR. IT APPEARS A SINGLE
 EXIT IS PROVIDED. IS NO SECONDARY EXIT
 OR MEANS OF ESCAPE PROVIDED.
  
 7) NO HANDRAILS PROVIDED AT THE TWO
 SETS OF STEPS FROM THE FRONT PORCH.
  
 8) NO FIRE ALARM SYSTEM INDICATED ON
 DRAWINGS.
  
 9) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
  
 10) PLEASE INDICATE ANY TENANT OR
 FLOOR SEPARATIONS BETWEEN SUITES.
  
 11) BATHROOM AND CLOSET DOORS SHALL
 MEET CERTAIN REQUIREMENTS. CLOSET
 DOORS SHALL BE OPERABLE FROM THE
 INSIDE. BATHROOM DOORS SHALL BE
 OPENABLE FROM THE OUTSIDE.
  
 12) BUILDING MAY BE LOCATED IN THE
 CITY FIRE LIMITS. CERTAIN RESTRICTIONS
 MAY APPLY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 09:20 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 09:19 Sent To  
Notes
2003-09-19 00:00:00ON COMM BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-26 Cont ID  
Sent By mmclean Date 2003-09-18 Time 10:03 Rev Time 0.00
Received By csiegber Date 2003-08-26 Time 14:19 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 11:18 Rev Time 0.25
Received By pkrauss Date 2003-10-01 Time 11:17 Sent To  
Notes
2003-10-01 00:00:00BREAD & BREAKFAST SUITES:
 TRANE PKG TERM A/C, MODEL 4-PTED1501G-A
 DUCTLESS UNITS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-21 Cont ID  
Sent By kstevens Date 2003-10-21 Time 08:21 Rev Time 1.50
Received By kstevens Date 2003-10-21 Time 08:21 Sent To  
Notes
2003-10-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) MINIMUM FIXTURES REQUIRED PER TABLE
 403.1. A KITCHEN SINK, AND AN AUTOMATIC
 CLOTHES WASHER CONNECTION IS REQUIRED.
 2) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-18 Cont ID  
Sent By csiegber Date 2003-08-26 Time 14:19 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-09-18 00:00:009/18/03 PASS ZONING PER DANA LITTLES
 URBAN DESIGN MM