2003-10-24 00:00:00 | THIS BUILDING WILL BE AN R1 OCCUPANCY |
| AND IS REQUIRED TO BE DESIGNED, SIGNED, |
| SEALED AND DATED BY A FLORIDA |
| REGISTERED ARCHCITECT OR ENGINEER.THE |
| ENGINEER SENG-CHAI TAN DECLARES |
| STRUCTURAL RESPONSIBILITY ONLY.THE |
| REMAINDER OF THE DESIGNMUST BE BY AN |
| ARCHITECT OR ENGINEER ALSO. |
| |
| THIS BUILDING WILL BE LOCATED IN THE |
| DESIGNATED FIRE DISTRICT AND MUST |
| COMPLY WITH FBC F102.2.5, AS AMENDED BY |
| THE CITY,WHICH REQUIRES TWO STORY |
| BUILDINGS TO BE ONE HOUR PROTECTED |
| UNLESS, FIRE SPRINKLERED THROUGH OUT |
| OR OF TYPE III CONSTRUCTION.PLEASE |
| REVISE AS NECESSARY. |
| |
| THE WINDOW BUCKS ON SHEET A1 MUST COMPLY |
| WITH FBC 1707.4.4. |
| |
| FBC TABLE 600 REQUIRES A TWO HOUR FIRE |
| RATED EXTERIOR WALL WHEN LOCATED FROM |
| THREE TO TEN FEET OF A COMMON OR |
| ASSUMED PROPERTY LINE, AND FBC |
| 705.1.1.2 REQUIRES PROTECTED OPENINGS. |
| THE EAST AND WEST ELEVATIONS ARE |
| SUBJECT TO THIS. |
| |
| SHOW HOW THE EXISTING BUILDING TO THE |
| EAST WILL COMPLY WITH TABLE 600 AND THE |
| ASSUMED PROPERTY LINE.SEE FBC 504. |
| SEE ALSO FBC 1006.2.2 FOR THE EXTERIOR |
| STAIR EXPOSURE ALLOWANCE. |
| |
| PLEASE PROVIDE A SITE PLAN WITH |
| TOPOGRAPHIC INFORMATION SO THAT |
| HANDICAP SITE ACCESSIBILITLY MAY BE |
| DETERMINED. |
| |
| THE WINDOWS, DOORS AND ANY OTHER |
| OPENINGS IN THE TEN FEET PRESCRIBED |
| AREA FOR THE STAIRS AS NOTED INFBC |
| 1006.2.4 MUST BE PROTECTED. |
| |
| SHEET A2.PLEASE CLARIFY THE |
| REINFORCEMENT SCHEDULE FOR THE F2 PADS |
| WITH 4 #5'S VERTICAL. |
| |
| HOW WILL THE WOOD COLUMNS CONNECT TO |
| THE PADS?ABOVE OR BELOW GRADE? |
| |
| ENGINEER, PLEASE CLARIFY THE COLUMN |
| SCHEDULE AS TO 8X12 BLOCK 8X8 BLOCK, |
| ETC.ARE THESE IN FACT COLUMNS OR |
| REINFORCED MASONRY?SEE ACI 530-99 AND |
| PROVIDE THE REQUISITE SPECIFICATIONS |
| AND DETAILS.SHOW THE DELEGATED |
| ENGINEERING REQUIREMENTS FOR THE ROOF |
| AND FLOOR TRUSSES. |
| |
| SHEET A5, SEE FBC 1608.2 FOR THE |
| MINIMUM STRUCTURAL DESIGN CRITERIA FOR |
| HAND AND GUARD RAILS. |
| |
| THE STAIR RISE AND RUN DOESN'T COMPLY |
| WITH FBC 1007.3.ALSO, SHOW A |
| CONSTRUCTIONDETAIL, INCLUDING |
| FASTENERS, FOUNDATION AND DESIGN LOADS |
| FOR THE STAIRS, |
| BALCONIES, ETC. |
| |
| SHOW THE ATTIC ACCESS AND VENTILATION AS |
| PROVIDED FOR IN FBC 2309.6 AND 2309.7. |
| |
| SHOW THE STAIR AND HAND RAIL DETAILS FOR |
| THE FRONT PORCH, (SOUTH ELEVATION). |
| |
| HOW WILL THE HANDICAP TOILETS ON THE |
| NORTH SIDE BE ACCESSED?THE PORCH IS |
| SHOWN 20" ABOVE THE SURROUNDING GRADE. |
| |
| PLEASE PROVIDE THE FIRE DESIGN NUMBER |
| FOR THE RATED WALLS, FLOORS, ROOF AND |
| COLUMN ASSEMBLIES TOGETHER WITH THE |
| METHOD OF PENETRATION PROTECTION.SEE |
| FBC 104.2 AND FBC 701. |
| |
| SHEET A5 SEC AA, WHAT IS THE SPACING |
| FOR THE 3/4" BOLT THROUGH THE 2-2X8'S? |
| |
| THE ENERGY CODE DECLARES R30 CEILING |
| INSULATION NOT SHOWN ON THE PLANS. |
| PLEASE REVISE AS NECESSARY. |
| |
| SEE FBC 13-600.3 FOR THE REQUIREMENT OF |
| AN ARCHITECT OR ENGINEER TO SIGN AND |
| SEAL THE ENERGY CODE AND INCORPORATE |
| THEM INTO THE PLANS AND SPECIFICATIONS. |
| |
| SHOW THE DRAFTSTOPPING IN ACCORDANCE |
| WITH FBC 2305.2.2. |
| |
| BEFORE A PERMIT TO CONSTRUCT MAY BE |
| ISSUED IMPACT FEES MUST BE PAID TO THE |
| COUNTY, THE PERMIT PLANS STAMPED BY |
| THAT OFFICE AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION.CALL 561-233-5025 FOR |
| MORE INFORMATION. |