Plan Review Details - Permit 03081417
Plan Review Stops For Permit 03081417
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-05 Cont ID  
Sent By kstevens Date 2003-09-03 Time 11:10 Rev Time 2.00
Received By lsmith Date 2003-09-05 Time 13:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-24 Cont ID  
Sent By dpalmer Date 2004-06-24 Time 12:46 Rev Time 0.33
Received By dpalmer Date 2004-06-24 Time 12:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-17 Cont ID  
Sent By mjacobs Date 2004-06-22 Time 10:35 Rev Time 0.33
Received By dpalmer Date 2004-06-17 Time 09:28 Sent To  
Notes
2004-06-17 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE SD IS REQUIRED TO BE
 MOVED INTO MATER BEDROOM. PLAN SHOWS A
 HEADERIN DOORWAY.
 NFPA-72
  
 2)NOTE: PLEASE SEE SEAL IS NOT VISABLE,
 PLEASE SEE SEAL MUST BE IMBOSSED, RAISED
 SEAL, CLEAR AND VISBLE. FS 471.025
  
 3)NOTE: PLEASE SHOW LOCATION OF POOL
 PANEL "C" ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-28 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 15:07 Rev Time 0.50
Received By dpalmer Date 2003-08-28 Time 16:16 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-22 Cont ID  
Sent By mjacobs Date 2004-06-22 Time 10:35 Rev Time 0.00
Received By mjacobs Date 2004-06-22 Time 10:35 Sent To E
Notes
2004-06-22 00:00:00SENT TO DP DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-16 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 15:07 Rev Time 0.00
Received By mjacobs Date 2004-06-16 Time 15:07 Sent To E
Notes
2004-06-16 00:00:00SENT TO DP DESK/DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 09:39 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 09:39 Sent To P
Notes
2003-10-24 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 16:38 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 16:38 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-25 Cont ID  
Sent By mmclean Date 2003-08-25 Time 13:06 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 11:13 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-29 Cont ID  
Sent By dpalmer Date 2003-08-28 Time 16:16 Rev Time 0.25
Received By pkrauss Date 2003-08-29 Time 07:11 Sent To P
Notes
2003-08-29 00:00:00PROVISO:
  
 1. BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 2. ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-31 Cont ID  
Sent By kstevens Date 2003-10-31 Time 18:17 Rev Time 0.50
Received By kstevens Date 2003-10-31 Time 18:17 Sent To  
Notes
2003-10-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM REVISION DOES
 NOT REFLECT THE FLOOR PLAN. PLEAS SUBMIT
 A SANT. RISER DIAGRAM THAT REFLECT THE
 FLOOR PLAN AND ACTUAL INSTALLATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-10-24 Time 09:39 Rev Time 0.33
Received By kstevens Date 2003-09-03 Time 11:10 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 11:13 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***