Plan Review Details - Permit 03081413
Plan Review Stops For Permit 03081413
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By jgomez Date 2003-10-09 Time 15:37 Rev Time 2.50
Received By jgomez Date 2003-10-09 Time 15:37 Sent To P
Notes
2003-10-09 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE SURVEY TO MATCH FLOOR PLANS.
 SEE MASTER BEDROOM.
 2-GLASS BLOCK AT BATHROOM TO BE SAFETY
 GLASS IF FACE THICKNESS IS LESS THAN
 0.25". SEC. 2405.2 FBC 2001.
 3-UPDATE TRUSS ANCHOR SCHEDULE TO COMPLY
 WITH SECTION 1609.4.3 FBC 2001. USE
 USP 2003 CATALOGUE OR SIMPSON HIGH
 WIND-RESISTANT CONSTRUCTION CATALOGUE.
 2003 WHICH ARE THE ONLY ONES BEING
 UPDATED.
 **NOTE:USE SAME FASTENER TYPE AND NUMBER
 AS PUBLISHED OR PROVIDE ENGINEERING
 CALCULATIONS WHEN FASTENERS DO NOT
 MATCH THOSE ON CATALOGUES.
 4-REVISE SPECIFICATIONS FOR INSTALLATION
 OF CEILING AT FRONT AND REAR PORCH.
 SEE ASTM C-1063 FOR PROPER NAIL SIZE.
 SEC. 2504.2 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-29 Time 07:51 Rev Time 4.00
Received By jgomez Date 2003-09-17 Time 10:33 Sent To PC
Notes
2003-09-17 00:00:00BUILDING REVIEW CHECKLIST:
 1-SURVEY HAS INCORRECT/INCOMPLETE INFO.
 A)LEGAL DESCRIPTION: FILL IN INFORMATION
 AND THIS IS PALM BEACH COUNTY, NOT
 MARTIN COUNTY.
 B)SURVEYOR'S NOTES: NEED COMNPLETE AND
 CORRECT INFORMATION ON ITEM #3.
 **ITEM #9: REVISE ADDRESS. THIS IS WEST
 PALM BEACH, NOT PALM BEACH COUNTY.
 **ITEM #10: WPB USES MAP DATED MARCH 1ST
 1979. REVISE MAP AND PANEL # AS REQ'D.
 C)BUILDING FOOTPRINT DOESN'T MATCH
 FLOOR PLANS. REVISE AS REQUIRED.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE AIR HANDLER UNIT COMPLETE
 HANGING DETAILS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2 FBC 2001.
 5-PRIVACY WALL SECTION DETAIL: SPECIFY
 VERTICAL REINFORCEMENT AND ATTACHMENT
 TO CANTILEVERED FOOTING. SECTION
 104.2.1.2 CITY AMENDEMNTS TO FBC 2001.
 6-PROVIDE CALCULATIONS FOR UPLIFT LOADS
 AT REAR COVERED PORCH CONCRETE PADS.
 SEC. 1606.1.3 FBC 2001 AND SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION THRU
 BAY WINDOW AT CAFE AREA. PROVIDE
 SPECS FOR CANTILEVERED BEAM AND THE
 ATTACHMENT TO COLUMNS. ALSO, PROVIDE
 DETAIL AT INTERSECTION OF COVERED
 PORCH BEAM, CAFE BAY WINDOW BEAM AND
 LANAI BEAM. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOES NOT
 ALLOW STEEL STRESS TO BE INCREASED.
 **NOTE: USE SIMPSON HIGH WIND-RESISTANT
 CONSTRUCTION CATALOGUE WHICH HAVE THE
 REVISED VALUES.
 9-SPECIFY WASHERS FOR GARAGE STRUCTURAL
 BUCK DETAIL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 10-PROVIDE COMPLETE DETAIL/SPECS FOR
 CEILING INSTALLATION AT FRONT AND
 REAR PORCHES. SPECIFY ALL MATERIALS
 AND FASTENER TYPE AND SPACING. SEE
 ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
 11-PROVIDE COMPLETE INFORMATION ON TOP
 OF ENERGY CALCULATIONS FORM.
 12-STORM SHUTTERS: CLEARLY MARK ON DWGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO THE DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO.
 13-SITE SPECIFIC PRODUCT APPROVAL FOR
 BUTT GLAZING SYSTEM: A)PANEL TESTED
 HAS THREE PANELS. PANEL SHOWN ON PLANS
 HAS 4 PANELS. PROVIDE COMPLETE ENGINEE
 RING ANALYSIS FOR PROPOSED SYSTEM.
 SEC. 2406.1 AND 2406.2 FBC 2001.
 **NOTE: TEST DOESN'T SPECIFY EDITION
 OF ASTM E330. NEED TO USE THE CRITERIA
 SET ON ASTM E330-84 EDITION WHICH IS
 THE ONE REFERENCED IN THE FBC.
 **PROVIDE ORIGINAL SEALED, SIGNED AND
 DATED TEST REPORTS AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 **PRODUCT APPROVAL SUBMITTED IS FOR
 4500 SERIES STOREFRONT SYSTEM. PRODUCT
 APPROVAL FORM CALLS FOR 4000 SERIES.
 CLARIFY AS REQUIRED.
 **PRODUCT APPROVAL FORM DOESN;T SPECIFY
 THICKNESS FOR 1200 TYPE SILICONE.
  
 14-OWES $6.81 FOR UPDATED VALUATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-07 Cont ID  
Sent By dpalmer Date 2004-06-07 Time 09:32 Rev Time 0.33
Received By dpalmer Date 2004-06-07 Time 09:27 Sent To  
Notes
2004-06-07 00:00:00*** REDLINED **
  
 GFI FOR COND UNITS PER 210.63
 PANEL "C" NOT SHOWN ON PLANS?
  
 REVISE BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-28 Cont ID  
Sent By csiegber Date 2004-06-02 Time 14:42 Rev Time 0.50
Received By dpalmer Date 2003-08-28 Time 14:25 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-02 Cont ID  
Sent By csiegber Date 2004-06-02 Time 14:42 Rev Time 0.00
Received By csiegber Date 2004-06-02 Time 14:42 Sent To E
Notes
2004-06-02 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-02-04 Time 09:28 Rev Time 0.00
Received By csiegber Date 2004-02-04 Time 09:28 Sent To M
Notes
2004-02-04 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 07:51 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 07:50 Sent To B
Notes
2003-09-29 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 16:37 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 16:37 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-25 Cont ID  
Sent By mmclean Date 2003-08-25 Time 13:22 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 11:11 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-12 Cont ID  
Sent By pkrauss Date 2004-02-12 Time 16:45 Rev Time 0.25
Received By pkrauss Date 2004-02-12 Time 16:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-04 Cont ID  
Sent By csiegber Date 2004-02-04 Time 09:28 Rev Time 0.25
Received By pkrauss Date 2003-09-04 Time 07:01 Sent To P
Notes
2003-09-04 00:00:00PROVISO:
 PLEASE NOTE REVISION TO 2001 FBC(M)
 601.4 EFFECTIVE JUNE 30, 2003:
  
 BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-06 Cont ID  
Sent By jgomez Date 2003-10-09 Time 16:54 Rev Time 0.33
Received By kstevens Date 2003-09-06 Time 11:45 Sent To B
Notes
2003-09-06 00:00:00REVISION REQUIRED - RISER TO REFLECT THE
 FLOOR PLAN

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 11:11 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***