Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2003-09-03 |
|
|
Cont ID |
|
Sent By |
csiegber |
Date |
2003-08-25 |
Time |
09:41 |
Rev Time |
0.30 |
Received By |
pkrauss |
Date |
2003-09-03 |
Time |
07:24 |
Sent To |
|
|
Notes |
2003-09-03 00:00:00 | PROVISO: | | | | 1. BALANCE AIR RETURN - RETURN TRANSFER | | SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL | | AREA (SQ INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM IT'S SERVING & THE | | DOOR HAVING AN UNRESTRICTED 1" UNDERCUT. | | PLEASE NOTE ALL SUPPLY AIR INTO THE | | MASTER SUITE SHALL BE INCLUDED (EXCEPT | | FOR THE BATHROOM). 2001 FBC(M) 601.4. | | | | 2. BATHROOMS SHALL HAVE A WINDOW WITH | | A MINIMUM OF 3 SQ FT OF OPEN SPACE OR | | BE MECHANICALLY VENTILATED. 2001 FBC(M) | | 402.3.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|