Plan Review Details - Permit 03081254
Plan Review Stops For Permit 03081254
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-02 Cont ID  
Sent By hpiskura Date 2003-09-02 Time 08:07 Rev Time 0.00
Received By hpiskura Date 2003-09-02 Time 08:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-18 Cont ID  
Sent By btrobaug Date 2003-12-18 Time 15:37 Rev Time 0.50
Received By btrobaug Date 2003-12-18 Time 15:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-29 Cont ID  
Sent By csiegber Date 2003-12-17 Time 16:38 Rev Time 0.50
Received By dpalmer Date 2003-08-29 Time 07:06 Sent To  
Notes
2003-08-29 00:00:00********** NOTES REDLINED **********
  
 MISSING SIGN CIRCUIT, 600.5
 MISSING SHOW WINDOW RECEPTS, 210.62

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-21 Cont ID  
Sent By nmccray Date 2003-10-21 Time 11:08 Rev Time 0.00
Received By nmccray Date 2003-10-21 Time 11:07 Sent To  
Notes
2003-10-21 00:00:00************PROVISO*********************
 SEPARATE PLANS AND PERMITS ARE REQUIRED
 FOR THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-04 Cont ID  
Sent By mcarsill Date 2003-09-04 Time 07:49 Rev Time 0.00
Received By mcarsill Date 2003-09-04 Time 07:48 Sent To  
Notes
2003-09-04 00:00:001) FIRE ALARM NOTES # 17 INDICATES
 A SUPERVISORY SIGNAL WHEN DUCT
 SMOKE DETECTORS ARE ACTIVATED. ALARM
 SIGNALS ALLOWED ONLY.
  
 2) FIRE ALARM NOTES # 19 INCORRECT.
 FIRE ALARM CIRCUITS SHALL BE CLASS A,
 STYLE D.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM REMODEL.
  
 4) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 16:38 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 16:38 Sent To E
Notes
2003-12-17 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-03 Cont ID  
Sent By csiegber Date 2003-12-03 Time 09:51 Rev Time 0.00
Received By csiegber Date 2003-12-03 Time 09:51 Sent To P
Notes
2003-12-03 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 16:15 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 16:15 Sent To  
Notes
2003-10-09 00:00:00TO COMM BD#63

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-21 Cont ID  
Sent By csiegber Date 2003-08-21 Time 15:46 Rev Time 0.00
Received By csiegber Date 2003-08-21 Time 15:46 Sent To  
Notes
2003-08-21 00:00:00COMM BD #46

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-23 Cont ID  
Sent By pkrauss Date 2003-09-23 Time 12:25 Rev Time 0.45
Received By pkrauss Date 2003-09-23 Time 11:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-01-09 Cont ID  
Sent By kstevens Date 2004-01-09 Time 13:05 Rev Time 0.50
Received By kstevens Date 2004-01-09 Time 13:05 Sent To  
Notes
2004-01-09 00:00:00REVISION OK - ADD TWO W/C'S FOR DISPLAY
 ONLY - WORKING MODELS

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-12-17 Cont ID  
Sent By kstevens Date 2003-12-17 Time 17:28 Rev Time 0.33
Received By kstevens Date 2003-12-17 Time 17:28 Sent To  
Notes
2003-12-17 00:00:00DENIED
 REFERENCE: FLA. ADMIN. CODE
 FLA. STATUTES
  
 ENGINEERS SIGNATURE REQUIRED ON SEAL PER
 FAC 61G15-23.002(1) & FS 471.025. - PER
 RULING BY FBPE AND BLDG. OFFICIAL THE
 SIGNATURE SHALL CONTAIN MINIMUM OF FIRST
 AND LAST NAME. INITIALS ARE NOT ACCEPT-
 ABLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-12-03 Time 09:51 Rev Time 0.50
Received By kstevens Date 2003-10-27 Time 11:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-25 Cont ID  
Sent By kstevens Date 2003-10-25 Time 14:58 Rev Time 0.33
Received By kstevens Date 2003-10-25 Time 14:30 Sent To  
Notes
2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SECTION 402.1 SUBMIT MANUFACTURE IN-
 FORMATION, (SPECIFICATION SHEETS) SHOW-
 ING THAT THE DRINKING FOUNTAIN AND THE
 LAUNDRY TUB CONFORM TO STANDARDS CITED
 IN THIS CODE.SECOND NOTICE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-23 Cont ID  
Sent By kstevens Date 2003-09-23 Time 07:54 Rev Time 1.25
Received By kstevens Date 2003-09-23 Time 07:54 Sent To  
Notes
2003-09-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P0.1 DOMESTIC WATER ISOMETRIC,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALL. INSTRUCT. (SEE NOTE
 #13 OF THE PLUMING NOTES).
 2) SUBMIT PRODUCT APPROVAL SHEETS FOR
 TOTO FIXTURES, DRINKING FOUNTAIN, AND
 LAUNDRY TUB.
 3) 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING
 AT DRINKING FOUNTAIN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]