Plan Review Details - Permit 03081246
Plan Review Stops For Permit 03081246
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-27 Cont ID  
Sent By pkrauss Date 2003-08-27 Time 08:57 Rev Time 0.30
Received By pkrauss Date 2003-08-27 Time 08:57 Sent To  
Notes
2003-08-27 00:00:00PROVISO:
 RETURN AIR SHALL COMPLY WITH 2001 FBC(M)
 601.4, REVISION DATED JUNE 30, 2003:
  
 BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved