Plan Review Details - Permit 03081117
Plan Review Stops For Permit 03081117
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-27 Cont ID  
Sent By hpiskura Date 2003-08-27 Time 16:57 Rev Time 0.00
Received By hpiskura Date 2003-08-27 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-11-25 Cont ID  
Sent By btrobaug Date 2003-11-25 Time 14:22 Rev Time 0.50
Received By btrobaug Date 2003-11-25 Time 14:03 Sent To  
Notes
2003-11-25 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 SEE SHEET EO.1.RECEPTACLE LOAD ADDED
 BUT LOAD CALC DID NOT CHANGE. ALL
 CHANGES MUST BE MADE BY THE ENGINEER OF
 RECORD,MR CARTER SIGNED THE PLAN ON
 11.14.03 AND CHANGES WERE MADE AND
 INITIALED ON 11.21.03.
  
 PLEASE CORRECT CHANGES TO PLAN AND RESUB
 MIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2003-10-14 Time 14:52 Rev Time 1.50
Received By dpalmer Date 2003-10-14 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-28 Cont ID  
Sent By csiegber Date 2003-10-06 Time 13:50 Rev Time 0.50
Received By dpalmer Date 2003-08-28 Time 06:47 Sent To  
Notes
2003-08-28 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/
 PANELS/ PLANS. PLEASE SEE RISER SHOWS
 A PANEL L2F? PLEASE CLARIFY WHERE THIS
 IS ON PLANS AND PANEL SCHEDULE.215.5
  
 2)NOTE: PLEASE PROVIDE PANEL SCHEDULE
 FOR L2A, PLEASE ALSO NOTE:
 ALL CONTINUOUS LOADS ARE TO BE SHOWN AT
 125%. 215.3,230.42 ETC
  
  
 PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWERS THAT MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS,
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-09-02 Cont ID  
Sent By mcarsill Date 2003-09-02 Time 16:34 Rev Time 0.00
Received By mcarsill Date 2003-09-02 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-25 Cont ID  
Sent By csiegber Date 2003-11-25 Time 11:18 Rev Time 0.00
Received By csiegber Date 2003-11-25 Time 11:18 Sent To  
Notes
2003-11-25 00:00:00TO COMM BD#47

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 13:50 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 13:50 Sent To E
Notes
2003-10-06 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-20 Cont ID  
Sent By csiegber Date 2003-08-20 Time 15:10 Rev Time 0.00
Received By csiegber Date 2003-08-20 Time 15:10 Sent To  
Notes
2003-08-20 00:00:00COMM BOX #16

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-17 Cont ID  
Sent By pkrauss Date 2003-09-17 Time 07:23 Rev Time 0.40
Received By pkrauss Date 2003-09-17 Time 07:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-12-13 Cont ID  
Sent By kstevens Date 2003-12-13 Time 13:47 Rev Time 0.75
Received By kstevens Date 2003-12-13 Time 13:47 Sent To  
Notes
2003-12-13 00:00:00DENIED
 REFERENCE: FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) ENGINEERS SIGNATURE REQUIRED ON SEAL.
 61G-15-23.002(1) & FS 471.025. INITIALS
 ARE NOT ACCEPTABLE PER FBPE & BLDG.
 OFFICIAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-22 Cont ID  
Sent By kstevens Date 2003-09-22 Time 16:39 Rev Time 0.50
Received By kstevens Date 2003-09-22 Time 16:39 Sent To  
Notes
***NONE***