Plan Review Details - Permit 03081071
Plan Review Stops For Permit 03081071
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-19 Cont ID  
Sent By csiegber Date 2003-08-19 Time 15:22 Rev Time 0.00
Received By csiegber Date 2003-08-19 Time 15:22 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-21 Cont ID  
Sent By csiegber Date 2003-08-19 Time 15:22 Rev Time 0.35
Received By pkrauss Date 2003-08-21 Time 13:53 Sent To  
Notes
2003-08-21 00:00:00PROVISO:
  
 1. AHU LOCATED IN ATTIC SHALL COMPLY
 WITH 2001 FBC CHAPTER 13 SUB-SECTION
 610.1.ABC.3.5.2.
  
 2. BATHROOM SHALL HAVE A WINDOW WITH A
 MINIMUM OF 3 SQ FT CLEAR OPENING OR
 BE MECHANICALLY VENTILATED AS PER 2001
 FBC(M) 402.3.1.
  
 3. BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.