2003-09-12 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| THE INTERNAL PRESSURE COEFFICIENT FOR AN |
| ENCLOSED STRUCTURE IS + OR - 0.18. |
| SPECIFY THIS INFORMATION ON THE PLAN FOR |
| THE ADDITION. SOME OF THIS IS ON THE |
| PLANS UNDER ROOF NOTES, HOWEVER ALL OF |
| THE ADDITION IS REQUIRED TO COMPLY. |
| |
| 4) SPECIFY THE POSITIVE AND NEGATIVE |
| WIND LOAD PRESSURES FOR THE WINDOW AND |
| DOOR OPENINGS IN THE ADDITION. |
| |
| 5) ON SHEET S-2 SECTION B-B IS INDICATED |
| ON THE FOUNDATION PLAN AND THE DETAIL IS |
| MARKED G-G. PLEASE CORRECT. SPECIFY THE |
| SPACING OF THE DOWELS SHOWEN IN THE |
| DETAIL. |
| |
| 6) SPECIFY THE LENGTH OF THE 1/2" BOLT |
| IN THE DETAIL ON S-2. THE SPACING OF THE |
| BOLTS IS 4 FT. ON CENTER ON S-2 AND 2 FT |
| ON CENTER ON THE SLOPE AND FLAT ROOF |
| SECTIONS ON D-1. THE FLAT ROOF SECTION |
| SPECS. A 6" EMBED AND THE SLOPED ROOF |
| SECTION HAS 4" EMBED FOR BOLTS. PLEASE |
| CLARIFY. |
| |
| 7) SPECIFY THE SIZE OF THE NEW BATHROOM |
| DOOR. FBC 11-43.23.2 REQUIRES ONE BATH |
| ROOM WITH AT LEAST A 29" CLEAR OPENING. |
| |
| 8) THE RTPGA STRAPS SPECIFIED IN THE |
| ANCHOR SCHEDULE ON R-1 ARE NOT LISTED IN |
| THE 2003 USP CATALOG. PLEASE UPDATE. |
| |
| 9) THE WALL SECTIONS ON D-1 SPECIFY 5/8" |
| STUCCO. ASTM C 926 REQUIRES STUCCO OVER |
| METAL LATH (VERTICAL) TO BE 7/8" THICK. |
| SEE FBC 2504.2.1. |
| |
| 10) UPDATE THE STRAPS AND STUD PLATE |
| TIES TO CONNECTORS LISTED IN CURRENT |
| MANUFACTURERS' CATALOGS. SEE NOTES ON |
| THE PLAN. |
| |
| 11) PLEASE REVIEW DETAILS ON D-1 AND |
| CLARIFY THE SIZE OF THE FRAME WALLS. |
| SPECIFY R-11 INSULATION FOR 2X4 WALLS |
| AND R-19 FOR 2X6 WALLS. USP SPT 4 PLATE |
| CONNECTORS ARE FOR 2X4 WALLS AND SPT 6 |
| ARE FOR 2X6 WALLS. |
| |
| 12) THE PLANS SPECIFY R-30 INSULATION IN |
| THE SINGLE ASSEMBLY ENCLOSED CEILING. |
| THIS WILL INTERFERE WITH VENTILATION. |
| THE CODE WILL ALLOW R-19 FOR THIS |
| APPLICATION. INDICATE THE APPROPRIATE |
| INSULATION ON THE PLAN AND ON THE ENERGY |
| FORM AS REQUIRED BY FBC 11-604.1. |
| |
| 13) NOTE 4 ON T-1 STATES THAT THE |
| EXISTING WALLS ARE CBC AND THE PLANS |
| INDICATE WOOD FRAME WALLS. PLEASE |
| CLARIFY. |
| |
| 14) PROVIDE DETAILS OF THE STRUCTURAL |
| REPAIRS THAT WILL BE MADE TO THE EXIST- |
| ING BEARING WALLS THAT WERE DAMAGED. |
| REVISE NOTE ON T-1 TO SPECIFY THAT THE |
| ENGINEER IS RESPONSIBLE FOR THE REPAIRS |
| TO THE EXISTING STRUCTURE AND THE NEW |
| ADDITION. |
| |
| 15) THE INFORMATION ON THE ENERGY FORM |
| IS INCORRECT. PLEASE CORRECT AND SUBMIT |
| TWO COPIES. |
| |
| 16) THE PRODUCT APPROVALS FOR THE |
| SINGLE HUNG WINDOWS IS ILLEGIBLE. SUBMIT |
| TWO CLEAR READABLE COPIES. |
| |
| 17) THE PRODUCT APPROVALS FOR THE FRENCH |
| DOORS ARE NOT ACCEPTABLE. THE ACCEPTANCE |
| NUMBER ON THE COVER SHEET DOES NOT MATCH |
| THE ONE ON THE DRAWINGS AND PAGES ARE |
| MISSING FROM THE NOA. SUBMIT TWO |
| COMPLETE AND READABLE PRODUCT APPROVALS |
| FOR THE DOUBLE OUTSWING FRENCH DOORS. |
| |
| 18) SUBMIT PRODUCT APPROVALS FOR THE |
| ROOFING MATERIAL. |
| |
| 19) SUBMIT TWO COPIES OF A KEY PLAN AND |
| INSTALLATION SCHEDULE FOR THE STORM |
| PANELS. SPECIFY THE MOUNTING TYPE, |
| ANCHOR TYPE AND ANCHOR SPACING THAT WILL |
| BE USED. |
| |
| IF YOU HAVE QUESTIONS PLEASE CALL: |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |