Plan Review Details - Permit 03080874
Plan Review Stops For Permit 03080874
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-08-28 Cont ID  
Sent By jleech Date 2003-09-24 Time 19:49 Rev Time 1.50
Received By lsmith Date 2003-08-28 Time 08:17 Sent To P
Notes
2003-08-28 00:00:00A NOTICE OF COMMENCEMENT MUST BE
 SUBMITTED BEFORE A PERMIT IS ISSUED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-20 Cont ID  
Sent By jleahy Date 2004-04-20 Time 08:40 Rev Time 0.15
Received By jleahy Date 2004-04-20 Time 08:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-14 Cont ID  
Sent By jleahy Date 2004-04-14 Time 14:48 Rev Time 0.15
Received By jleahy Date 2004-04-14 Time 14:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-05 Cont ID  
Sent By csiegber Date 2004-04-13 Time 12:06 Rev Time 0.50
Received By btrobaug Date 2003-12-05 Time 15:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-26 Cont ID  
Sent By csiegber Date 2003-12-04 Time 14:01 Rev Time 0.50
Received By btrobaug Date 2003-08-26 Time 15:01 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 12:06 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 12:06 Sent To E
Notes
2004-04-13 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:41 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 13:41 Sent To P
Notes
2004-03-04 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-13 Time 11:32 Rev Time 0.00
Received By csiegber Date 2004-02-13 Time 11:32 Sent To M
Notes
2004-02-13 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-04 Cont ID  
Sent By csiegber Date 2003-12-04 Time 14:01 Rev Time 0.00
Received By csiegber Date 2003-12-04 Time 14:01 Sent To E
Notes
2003-12-04 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 14:53 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 14:52 Sent To P
Notes
2003-09-12 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-03 Cont ID  
Sent By dbaxter Date 2003-09-03 Time 16:40 Rev Time 0.00
Received By dbaxter Date 2003-09-03 Time 16:40 Sent To P
Notes
2003-09-03 00:00:00TO KSTEVENS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-21 Cont ID  
Sent By btrobaug Date 2003-08-21 Time 11:45 Rev Time 0.00
Received By btrobaug Date 2003-08-21 Time 11:45 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-15 Cont ID  
Sent By mmclean Date 2003-08-20 Time 15:35 Rev Time 0.00
Received By dbaxter Date 2003-08-15 Time 13:53 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-23 Cont ID  
Sent By pkrauss Date 2004-02-23 Time 15:49 Rev Time 0.25
Received By pkrauss Date 2004-02-23 Time 15:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-08-28 Cont ID  
Sent By csiegber Date 2004-02-13 Time 11:32 Rev Time 0.25
Received By pkrauss Date 2003-08-28 Time 06:40 Sent To P
Notes
2003-08-28 00:00:00PROVISO:
  
 BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-03-19 Cont ID  
Sent By kstevens Date 2004-03-19 Time 18:44 Rev Time 0.50
Received By kstevens Date 2004-03-19 Time 18:44 Sent To  
Notes
2004-03-19 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-03-10 Cont ID  
Sent By kstevens Date 2004-03-10 Time 08:35 Rev Time 0.50
Received By kstevens Date 2004-03-10 Time 08:35 Sent To  
Notes
2004-03-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. LAUNDRY SINK NOT SHOWN.
 TUB BATH SHOWS SHOWER, LAV ON WRONG WALL
 AND BATHROOM SHALL BE LOCATED NEAR THE
 GARAGE PAST WASH MACHINE. SEE RED LINE
 CORRECTIONS AND MAKE CHANGES AND RE-
 SUBMIT. ALL REVISIONS SHALL REFLECT THE
 ACTUAL INSTALLATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-09-24 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:41 Rev Time 0.33
Received By jleech Date 2003-09-24 Time 19:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-06 Cont ID  
Sent By csiegber Date 2003-09-12 Time 14:53 Rev Time 0.50
Received By kstevens Date 2003-09-06 Time 13:07 Sent To  
Notes
2003-09-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) LAUNDRY SINK SHALL CONNECT DOWN-
 STREAM OF THE BATHROOM FIXTURES. SECTION
 909.1
 B) WASH MACHINE SHALL NOT DRAIN PAST
 THE TUB. SECTION 712.3.5
 C) BIDET IN MASTER BATHROOM NOT VENTED.
 D) SECOND LAV IN MASTER BATH NOT SHOWN
 ON SANT. RISER.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-28 Cont ID  
Sent By dbaxter Date 2003-09-03 Time 16:40 Rev Time 0.50
Received By kstevens Date 2003-08-28 Time 08:53 Sent To  
Notes
2003-08-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN.
 A) BATH #3 TO BE CONNECTED TO BLDG.
 DRAIN DOWNSTREAM OF W/M - L/T.
 B) BATH #2 TO BE CONNECTED TO THE
 RIGHT SIDE OF THE BLDG DRAIN.
 C) BIDET MISSING FROM THE MASTER BATH.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-20 Cont ID  
Sent By dbaxter Date 2003-08-15 Time 13:53 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***